Instruction Manual
B610LPPLUG-INDETECTORBASE
INSTALLATIONINSTRUCTIONS
FORUSEWITHTHEFOLLOWINGSMOKEDETECTORMODELS:
INUS: CP-651,SD-651
INEUROPE: CP-651E,SD-651E
Beforeinstallingdetectors,pleasethoroughlyreadmanualI56-407,GuideforProperUseofSystemSmokeDetectors,
whichprovidesdetailedinformationondetectorspacing,placement,zoning,wiring,andspecialapplications.Copiesof
thismanualareavailablefromNotieroraNotierdistributor.
NOTICE:Thismanualshouldbeleftwiththeowner/userofthisequipment.
IMPORTANT:ThedetectorusedwiththisbasemustbetestedandmaintainedregularlyfollowingNFPA72requirements.
Thedetectorusedwiththisbaseshouldbecleanedatleastonceayear.
GENERALDESCRIPTION
TheModelB610LPdetectorbaseisdesignedforusewithNotiermodelSD-651andSD-651Ephotoelectronicdetector
headsandCP-651andCP-651Eionizationdetectorheads.Thistwo-wirebaseisequippedwithscrewterminalsforthe
connectionofpower,ground,andanoptionalremoteannunciator.
SPECIFICATIONS
BaseDiameter: 6.1inches(155mm)
BaseHeight: 0.95inches(24mm)
Weight: 0.3lb.(137g)
Mounting: 4-inchsquareboxwithorwithoutplasterring.Min.depth–1.5inches
3-1/2-inchoctagonbox.Min.depth–1.5inches
OperatingTemperatureRange: 0°to49°C(32°to120°F)
OperatingHumidityRange: 10%to93%RelativeHumidity,Noncondensing
ELECTRICALRATINGS-includesbaseanddetector
SystemVoltage: 12/24VDC
MaximumRippleVoltage: 4Voltspeak-to-peak
Start-upCapacitance: 0.02µFMaximum
StandbyRatings: 8.5VDCMinimum
35VDCMaximum
120µAMaximum
AlarmRatings: 4.2VDCMinimumat10mA
6.6VDCMaximumat100mA
(Alarmcurrentmustbelimitedto100mAbythecontrolpanel.
Ifitisused,theRA400ZRemoteAnnunciatoroperateswithinthe
specieddetectoralarmcurrents.)
ResetVoltage: 2.5VDCMinimum
ResetTime: 0.3SecondsMinimum
Start-upTime: 34.0SecondsMaximum
N550-01-00 1 I56-646-02R
Notier,12ClintonvilleRd.,Northeld,CT06472-1652(203)484-7161
N550-01-00 4 I56-646-02R
©2001Notier
PleaserefertoinsertfortheLimitationsofFireAlarmSystems