Owner's Manual

DN-60974:C • 3/5/19 — Page 1 of 2
NCD
NCD Network Control Display
General
The Network Control Display (NCD) is the next generation of net-
work control annunciators for the NOTI•FIRE•NET™ network. With
a new modern contemporary design, the NCD meets todays build-
ing aesthetic needs. The intuitive 1024 x 600 10” color touch
screen provides color coded information of detailed system status
and point information. It is compatible with ONYX Series nodes
such as the NFS2-3030, NFS-320, and NFS2-640 fire alarm con-
trol panels, as well as the NCA-2. The NCD provides system con-
trol and display capabilities for all, or for selected network nodes.
Additionally in a standalone configurations, the NCD can be used
as the primary display for control and status capabilities on display-
less node by utilizing Direct Connect.
When connected to one or more networked panels, the NCD pro-
vides network control and status/history display capabilities.
Hardware Features
Full supervision of all inputs and network integrity.
High definition 10” 1024 x 600 color touchscreen display.
LED status indicators
Requires 24 VDC, and a network connection or direct connect.
Three USB 2.0 connections, USB C, USB Micro, and USB A.
Trouble Relay.
Tamper and Trouble inputs.
Function Features
Device information, including point address and description, can
be quickly identified.
Network-wide: Acknowledge, Silence, Reset.
•Lamp Test.
Interactive Summary Event Count display and event handling.
Intuitive user guidance program.
Fully programmable node-mapping subsystem.
Environmental adjustment controls to maximize display legibility.
Color coded Icon based event notification.
Can be used as FACP primary display.
Supports standard and high speed network systems.
Event vectoring for quick viewing of event groups.
Virtual alphanumeric QWERTY keypad and numeric keypad dis-
plays when data input is needed.
Individual Enable/Disable or group Enable/Disable for networked
ONYX series panels.
Control ON/OFF for networked ONYX series panel control points.
Read Status networked ONYX series panel points and zones.
History Buffer (10,000 events, 3000 displayed).
Up to 50 unique users and 5 different user levels.
Read Status from event display.
History filters for report displaying.
Timer control for Auto Silence, AC Fail Delay.
Custom wallpaper
NCD Indicators and Controls
LED INDICATORS
Green LED illuminates when 24 VDC power is applied; When on
battery backup, the green LED will not illuminate.
Yellow LED illuminates when an off normal condition exists.
VIRTUAL EVENT INDICATORS
FIRE ALARM (red) illuminates when at least one fire alarm event
exists.
CO Alarm (blue) illuminates when at least one CO alarm event
exists.
SUPERVISORY (yellow) illuminates when at least one supervi-
sory event exists (i.e., sprinkler valve off normal, low pressure,
fire pump running, guard’s tour, etc.).
TROUBLE (yellow) illuminates when at least one trouble event
exists.
POINT DISABLED (yellow) illuminates when at least one disable
exists on the network or in the system.
OTHER (varies) illuminates for SECURITY, PRE-ALARM, CO
PRE-ALARM, and CRITICAL PROCESS.
SIGNALS SILENCED (yellow) illuminates if the NCD Silence
touch point has been pressed or if any other node sent a Network
Silence command.