FUNCTION TOUCHPOINTS
•Menu
•Login
• Acknowledge
• Signal Silence
• System Reset
Ack (Acknowledge) Tap this touchpoint to acknowledge off all
active events.
Silence (Signal Silence) Tap this touchpoint to turn off all control
modules, notification appliance circuits, and panel output circuits
that have been programmed as Silenceable.
Reset (System Reset) Tap this touchpoint to clear all latched
alarms and other events and clear event indicators.
MENU FUNCTION TOUCHPOINTS
Menu function touchpoint are accessible though the menu dialogs.
• ABOUT – tap this touchpoint to view current firmware and hard-
ware revision numbers.
• DISPLAY – tap this touchpoint to adjust display settings.
• LAMP TEST – tap this touchpoint to test display pixels, LED indi-
cators and piezo.
Specifications
Temperature and humidity ranges: This system meets NFPA
requirements for operation at 0°C to 49°C (32°F to 120°F); and at a
relative humidity (non-condensing) of 85% at 30°C (86°F) per
NFPA. However, the useful life of the system’s standby batteries
and the electronic components may be adversely affected by
extreme temperature ranges and humidity. Therefore, it is recom-
mended that this system and all peripherals be installed in an envi-
ronment with a nominal room temperature of 15°C to 27°C (60°F to
80°F). Product weight is 3 lbs (1.36 kilograms).
ELECTRICAL REQUIREMENTS
The NCD may be powered from any UL Listed non-resettable 24
VDC source from a NOTIFIER compatible fire panel (see panel
data sheets). Power source: 1) AMPS-24 (120 VAC, 50/60 Hz) or
AMPS-24E (240 VAC, 50/60 Hz) power supply; 2) the NFS2-640
and NFS-320 on-board power supply; or 3) a supervised +24 VDC
power supply that is UL-listed for fire protective service. The cur-
rent consumption of the NCD is 360 mA.
Product Line Information
NCD: Network Control Display. Requires a network communica-
tions module for networking. In direct connect applications, the
NCM is not required.
NCM-W, NCM-F: Standard Network Communications Modules.
Wire and multi-mode fiber versions available. See DN-6861.
HS-NCM-W/MF/SF/WMF/WSF/MFSF: High-speed network com-
munications modules. Wire, single-mode fiber, multi-mode fiber,
and media conversion models are available. See DN-60454.
ABS-TD: Ten inch display annunciator Backbox, Surface, black.
Mounts NCD and one network control module.
CAB-4 Series Enclosure: Available in four sizes, “AA” through
“D”. Backbox and door ordered separately; requires BP2-4 battery
plate. See DN-6857.
DP-GDIS2: Graphic Annunciator Dress Plate. Dress plate is used
when the 10" graphic display is mounted in CAB-4 Series cabinet,
except top row.
DP-GDIS1: Graphic Annunciator Dress Plate. Dress plate is used
when the 10" graphic display is mounted in the top row of a CAB-4
Series cabinet.
Agency Listings and Approvals
These listings and approvals apply to the NCD. In some cases,
certain modules or applications may not be listed by certain
approval agencies, or listing may be in process. Consult factory for
latest listing status.
UL Listed: S635.
CSFM: 7300-0028:0507.
FM Approved.