Owner's Manual

DN-7070:P • 3/8/17 — Page 1 of 8
NFS2-3030
Intelligent Addressable
Fire Alarm System
Intelligent Fire Alarm Control Panels
DN-7070:P • A-10
NFS2-3030 (left)
and NFS2-3030 with DVC audio option (right)
7070covg.jpg
General
The NFS2-3030 is an intelligent Fire Alarm Control Panel
(FACP) designed for medium- to large-scale facilities. Fire
emergency detection and evacuation are extremely critical to
life safety, and the NFS2-3030 is ideally suited for these appli-
cations. The NFS2-3030 is part of the ONYX
®
Series of prod-
ucts from NOTIFIER. The NFS2-3030 is ideal for virtually any
application because it features a modular design that is config-
ured per project requirements. With one to ten Signaling Line
Circuits (SLCs), the NFS2-3030 supports up to 3,180 intelli-
gent addressable devices.
Information is critical to fire evacuation personnel, and the
NFS2-3030’s large 640-character Liquid Crystal Display (LCD)
presents vital information to operators concerning a fire situa-
tion, fire progression, and evacuation details.
A host of other options are available, including single- or multi-
channel voice; firefighter’s telephone; LED, LCD, or PC-based
graphic annunciators; networking; advanced detection prod-
ucts for challenging environments; wireless fire protection; and
many additional options.
Features
Certified for seismic applications when used with the appro-
priate seismic mounting kit.
Approved for Marine applications when a marine-listed ver-
sion is used with marine-listed compatible equipment. See
DN-60688.
Complies with UL 2572 Mass Notification Systems (NFS2-
3030 version 20 or higher).
One to ten isolated intelligent Signaling Line Circuits (SLC)
Style 4, 6 or 7.
Wireless fire protection using SWIFT Smart Wireless Inte-
grated Fire Technology. See DN-60820.
Up to 159 detectors and 159 modules per SLC; 318 devices
per loop/3,180 per FACP or network node.
Detectors can be any mix of ion, photo, thermal, or multi-
sensor; wireless detectors are available for use with the
FWSG.
Modules include addressable pull stations, normally open
contact devices, two-wire smoke detectors, notification, or
relay; wireless modules are available for use with the
FWSG.
Large 16 line, 640 character LCD backlit display or use
display-less as a network node.
Network options:
High-speed network for up to 200 nodes (NFS2-3030,
NFS2-640, NFS-320(C), NFS-320SYS, NCA-2,
DVC-EM,
ONYXWorks, NFS-3030, NFS-640, and NCA).
Standard
network for up to 103 nodes (NFS2-3030,
NFS2-640, NFS-320(C), NFS-320SYS, NCA-2,
DVC-EM,
ONYXWorks, NCS, NFS-3030, NFS-640, NCA, AFP-200,
AFP-300/400, AFP-1010, and AM2020). Up to 54 nodes
when
DVC-EM is used in network paging.
Built-in Alarm, Trouble, Security, and Supervisory relays.
VeriFire
®
Tools online/offline program option.
With built-in Degraded Mode operation, the system is capa-
ble of general alarm if a fire alarm condition is present even
if the central processing unit (CPU) fails.
Weekly Occupancy Schedules allow changing sensitivity by
time of day and day of week.
EIA-485 annunciators, including custom graphics.
History file with 4000-event capacity in nonvolatile memory,
plus separate 1000-event alarm-only file.
Advanced history filters allow sorting by event, time, date,
or address.
Alarm Verification selection per point, with automatic
counter.
Autoprogramming and Walk Test reports.
Multiple central station communication options:
Standard UDACT
Internet
Internet/GSM
Positive Alarm Sequence (PAS) Presignal.
Silence Inhibit and Auto Silence timer options.
Field-programmable on panel or on PC, with VeriFire Tools
program, also check, compare.
Non-alarm points for lower priority functions.
Remote ACK/Signal Silence/System Reset/Drill via monitor
modules.
Up to 1000 powerful Boolean logic equations.
Supports SCS Series smoke control system in both HVAC
and FSCS modes.
FM6320 approved Gas Detection System with FMM-4-20
module and any FM listed gas detector.
EIA-232 printer port.
EIA-485 annunciator port.
firealarmresources.com

Summary of content (8 pages)