Current regulations must be complied with when calculating the thermal power of radiators for installation.
When determining the number of elements in a radiator, remember that the nominal thermal power refers
to a
T – the difference between the average water temperature and the room temperature – of 50K.
Therefore, in order to save energy and improve environmental comfort, it is advisable to use for the system
a design
T of less than 50K, (e.g. 30K
÷
40K) and decrease the water delivery temperature.
The thermal power of radiators for values other than
T is obtained by multiplying the rated thermal power
by a coefficient C calculated from the formula:
C=(
T / 50 K)n
where n is the exponent of the equation Q=B
Tn
which expresses the thermal power of the heating element and is shown in the table for the various models.
This gives
Q(
T)=Q(50 K) x C
for automatic calculation go to Calculate
T
When determining the number of elements, remember that in installations in which the water enters and
leaves from the bottom or with a single- or double-pipe valve, the thermal power may drop to 10-12%
(fig. A) and 20%, respectively (fig. B), due to the particular water distribution inside the radiator. For radiators
installed below shelves, in alcoves or – worse still – when using radiator covers – the thermal power may
drop to 10-12% (fig. C).
for the first approximation go to Heating requirements calculation