3.6 Wire assignments
The connection must be carried out in de-energized state! Risk of
damage!
To ensure reliable functioning, ensure that a possible extension of the 4 m
connecting cable does not exceed 152 m (condition: no external voltage
supply unit is required). For extension purposes up to 152 m an additional
JY(ST)Y (6x2x0.6 mm) cable can be used.
The reader can be used remotely for extension purposes at a distance of
max. 1220 m. We recommend using a Cat 5 connecting cable (condition:
an external voltage supply unit for the reader is required).
In general, by use of RS-485 interface: When the reader is the last user
on the RS-485 bus, a 120 Ω end-of-line resistor (from TRX+ to TRX-)
must be installed in front of the reader. For further information, refer to the
description of the corresponding controller.
InterfaceWire color
Wiegand RS-485
red POWER (+U_b) POWER (+U_b)
black GND (0 V) GND (0 V)
white D1 TRX+
green D0 TRX-
blue Hold line do not connect
yellow Buzzer do not connect
orange LED green do not connect
purple Tamper do not connect
Caution
Floating communication lines may cause spurious emissions, invalidating
certification. Ensure all communication lines are properly biased and ter-
minated.
Input Hold line
This input makes it pos-
sible to connect 2 read-
ers in parallel (e.g. at
NetAXS).
Reader 1
Reader 2
Hold line 2
Hold line 1
NetAXS
GND
Tamper line
Physical tamper switches:
tear-off
enclosure
The electronic switch opens when
the operating voltage +U_b fails.
mechanical tamper switch
electronic tamper switch
Tamper line
4 Operation
When a credential is read successfully, the light ring lights briefly, the
sounder sounds a short tone and the credential associated code is sent
to the Host system.
The light ring and sounder are also controllable by the Host system.
Reader output formats are determined by the personalization of the cre-
dential and/or configuration of the reader; on SmartTech and MultiTech
readers the behaviour of the light ring and sounder can be modified
through configuration.
4.1 Short briefing of buttons and LEDs
4.1.1 OmniAssure Touch Mullion
A
E
B
C
D
A LED light ring
B LED green
C LED yellow
D Duo LED red/green
E Activate the BLE credential by touching the touch-sensitive sur-
face
4.1.2 OmniAssure Touch Mullion 12 key
A LED light ring
B LED green
C LED yellow
D Duo LED red/green
E Activate BLE / Acknowledge: execute the PIN code
F Clear PIN code entry
G Numeric keypad for PIN entry (PIN= Personal identification num-
ber)
4.2 Requirements to credential type and operation
The following notes and information can be found in the product
accompanying documents of the panels:
NetAXS 123 V6 (Wiegand)
ProWatch 6k (Wiegand)
Pro32 (Wiegand)
Mercury EP1502 (OSDP)