User manual
Table Of Contents
- POWER LIMITER
- CONTENT
- 1. DESCRIPTION AND OPERATION
- 1.1 APPLICATION
- 1.2 Technical Brief
- 1.2.1 Basic technical parameters are shown below in table 1.3
- 1.2.2 Measured and calculated parameters output to the display unit, their effective range limits and tolerances are given below in Table 1.4.
- 1.2.3 Programmable parameters and their variability ranges are shown below in table 1.5.
- 1.2.4 Operating controls and the dimensions of the ОМ-310 are shown in fig.1.1.
- 1.2.5 Power Limiting Functions
- 1.2.6 Protection functions
- 1.3 Product package contents
- 1.4 Equipment features and operation
- Current protection. Maximum current protection
- Load Engagement and Automatic Reset Control
- 2. INTENDED USE
- 2.1. SAFETY
- 2.2 ОМ-310 device control
- 2.3 OM-310 pre-operation procedure
- INTENDED USE
- 2.4.1 ОМ-310 operation before load relay closure
- 2.4.2 OM-310 operation before load relay closure
- 2.4.3 Characterizing relay operation
- 2.4.4 Work with RS-232/RS-485 interface under MODBUS protocol in RTU mode.
- 2.4.5 The load energize/de-energize remote control via RS-232/RS-485 interface.
- 2.4.6 Load energize/de-energize via remote breaker
- 2.4.7 Fault conditions system
- 2.4.8 Faulty conditions log
- 2.4.9 Load start/cutoff control with use of OM-310 front panel
- 3. Maintenance
- 4. Transportation and storage
- 5. Period of service, storage, and manufacturer’s warranty
- Appendix 1- Dependent time delay current based protection types:
- 8 -
ОМ-310
NOVATEK-ELECTRO
Settings and read-off
parameters
Code pa-
rameters
Minimum
values
Max.
values
Default
setting
Operation
Address
tection function per-
mission
1- protection function permitted, after-
tripping automatic reset prohibited
2- protection function permitted, after-
tripping automatic reset permitted
Load Engagement and Automatic Reset Control
Automatic reset (AR)
time, sec
0
900
5
183
AR prohibited for all
faults (except voltage
faults)
0
1
1
0 - AR prohibited
1- AR permitted
parameter value is effective for all
types of faults except voltage faults.
,
,
parameters shall be used
to
prohibit
AR in case of voltage
faults
184
Load relay operation
permitted after OM de-
vice power-on
0
2
1
0 – manual load start from OM-310
front panel
1- load start after AR delay time
load start after 2 sec delay
185
Load start/cutoff control
with use of OM-310
front panel
0
3
0
0 - prohibited
1- load energizing permitted
2- emergency load de-energizing per-
mitted
3- load energizing and de-energizing
permitted
See par. 2.4.9
186
Miscellaneous
Time within which av-
erage current value is
measured, sec
10
600
60
Time within which average current
value is measured (parameters iS1,
iS2, iS3 from Table 1.5)
187
Min number of setting
parameters mode ena-
ble
0
1
1
0-mode disabled
1- mode enabled
The mode change is enabled in the
service-engineer mode only.
188
Indication on OM-310
display panel before
load energize
0
2
1
0- line voltage Uab
1-active power PoA
2-AR time countdown
189
Parameter indication
mode
0
1
1
0-parameter value indicated continuously
1-parameter
value
indicated
within
15s
190
Complete equipment
operation time, days
0
999
0
when MODBUS/RS-232 interface data
transfer is utilized, the operation time
is transferred in hours
191
User access code
0
9
0
0 – keyboard unlocked
1-9 – user password
192
Service engineer
access code
000
999
123
000-access to service engineer level -
permitted
000-999 – service engineer password
193
System reset to factory
settings
0
1
0
After value 1 has been recorded and
parameter setup mode exited, the fac-
tory set parameters will be restored
194
(RS-485/ RS-232) serial interface parameters
OM-310 device commu-
nication address
1
247
1
195
Transfer rate
0
1
0
0: 9600 baud; 1: 19200 baud;
Transfer rate change will take effect af-
ter power-off/ and restarting power-on.
196
OM-310 response to
loss of connection
0
3
0
0-continue without warning
1- warning message, continue opera-
tion
2-warning message and load relay de-
energize, AR permitted after commu-
nication has been restored
3-warning message and load relay de-
197