Manual
Controller N1100 
NOVUS AUTOMATION  2/8 
•  RTD (Pt100) 
Figure 4 shows the Pt100 wiring, for 3 conductors. Terminals 10, 11 
and 12  must have the same wire resistance for proper cable length 
compensation. For 2 wire Pt100, short circuit terminals 11 and 12. 
4-20mA
4-20mA
100R
Figure 5 – Current wiring  Figure 6 – Remote SP input 
•  4-20 mA 
Refer to Figure 5. (The controller provides an internal electronic 
shunt for the input current. No changes in the circuit are necessary). 
•  Remote setpoint 
Input available at terminals 9 and 10. The user must connect a 100 Ω 
resistor shunt as indicated in Figure 6. 
•  Digital Input 
I/O3  and I/O4  can be  used as digital  inputs,  accepting  either  dry 
contact  or  NPN  open  collector  signals.  Figure  7a  shows  a  switch 
driving the  I/O3 digital input.  I/O4 can be  used analogously. The 
digital input at I/O5 is driven only by dry contact signals. Figure 7b 
shows a typical digital input wiring for I/O5. 
Figure 7a – Digital input at I/O3  Figure 7b – Digital input at I/O5 
•  Digital Output 
I/O3, I/O4 and I/O5 can also be configured as digital outputs (I/O3 and 
I/O4 provide a 5 Vdc output signal whereas I/O5 a 12 Vdc signal). An 
example of usage is shown in Figure 8 for the I/O3 and in Figure 9 for 
the I/O5. I/O5 is electrically isolated from the sensor input. 
Figure 8 – I/O3 driving a SSR.  Figure 9 – I/O5 digital output wiring. 
OPERATION 
The front panel is shown in Figure 10. 
Figure 10 - Front panel parts 
Status display/PV: shows the value of PV (Process Variable). When 
in programming mode, shows the parameter name. 
Parameter display/SV: shows the SV (Setpoint Variable) value and 
the value of other parameters of the controller. 
COM Indicator: Flashes when communication messages are sent by 
the controller. 
TUNE Indicator: Lights during the execution of PID automatic tunning. 
MAN Indicator: Lights when the controller is in manual. 
RUN Indicator: Lights when the controller is active, with control and 
alarm outputs enabled. 
OUT Indicator: For relay or pulse control output, reflects the actual 
state of the output. If an analog output is assigned for control, lights 
continuously. 
A1, A2, A3 and A4 Indicators: Status of the alarms. 
P
 - PROG key: used to walk through the menu cycles 
 - BACK key: go back to the previous displayed parameter 
 -  INCREASE  and 
  -  DECREASE  keys:  Used  to  change 
parameter values 
When the controller is turned on, its firmware version is displayed for 
3  seconds,  after  which the  controller  starts  normal  operation.  The 
values of PV and SV are displayed and the outputs are enabled. 
Before the controller is ready to  be  used in a given process, it 
requires some basic configuration, such as: 
•  input  type  (T/C,  Pt100,  4-20  mA,...)  at  the  “tYPE
tYPEtYPE
tYPE”  prompt, 
according to Table 1. 
•  output type at “I/O 1”, “I/O 2”,... “I/O 5” prompts (see Table 2). 
•  setpoint variable SV. Set the remaining parameters. 
•  PID parameters (or hysteresis for ON / OFF control). 
Other functions, including alarms, ramp and soak, timer, digital input, 
etc., may be useful for a better system performance. The parameters 
are grouped in 7 cycles. 
CYCLE  ACCESS 
1- Operation  Free access parameters * 
2- Tuning 
3- R&S Program 
4- Alarms 
5- Input Configuration 
6- I/Os 
7- Calibration 
Reserved access parameters ** 
*  These parameters can  be  viewed  but  not  changed  if  the cycle  is 
protected. 
** Requires a key combination to access the cycle. 
Press 
P
 to advance and 
 to go back in the menu cycle. 
Keep pressing the 
P
 or 
 key to move fast forward or backward. 
Press 
 and 
P
 simultaneously to move from one cycle to the next 
one. 
At the end of each cycle the controller returns to the operation cycle. 
PROGRAM SECURITY 
Each menu cycle can be locked (protected) by pressing 
 and 
simultaneously  for  3  seconds.  Press 
  and 
  for  3  seconds  to 
unlock. A short blink of the display confirms the lock/unlock change. 
This will  alternately lock  or unlock  the 
  and 
  keys  to avoid 
tampering. 
For further protection, the unlock operation through the keypad may 
be disabled  by  changing the position of an  internal  strap inside the 
controller: 
When PROT is OFF, the  user is allowed to lock  and unlock  the 
cycles using  the  keypad  as  explained  above.  If  PROT  is  ON,  the 
cycles lock / unlock operation is disable. 








