Manual
Controller N1100 
NOVUS AUTOMATION  5/8 
CONFIGURATION PARAMETERS 
OPERATION CYCLE 
PV Indication 
(Red)
SV Indication 
(Green)
PV  AND  SV  INDICATION:  The  status  display  shows  the 
present value  of PV (Process Variable). The parameter 
display shows SV (Set Variable). 
The status display shows “---
------
----
--
-“ whenever PV exceeds the 
maximum range or there is no signal at the input. In case of 
hardware error the status display will show Ern
ErnErn
Ern, where n is 
the error code. 
avto
avtoavto
avto 
CONTROL MODE: YES  indicates automatic control mode 
(closed loop, PID or ON/OFF). NO indicates manual control 
mode  (open  loop).  Bumpless  transfer from  auto  ↔ to 
manual mode is available. If in doubt program YES. 
PV Indication 
(Red)
MV Indication 
(Green)
MANIPULATED VARIABLE VALUE (MV): The upper display 
shows PV value and the lower display shows the percentage 
of MV applied to the control output. When in manual control 
the MV value can be manually changed. When in auto mode 
the MV value can only be viewed. 
To distinguish the MV display from the SV display, the MV 
is shown flashing intermittently. 
Pr n
Pr nPr n
Pr n 
RAMP  AND  SOAK  PROGRAM  SELECTION:  Selects  the 
ramp  and  soak  program  to  be  executed  (7  programs 
possible). Refer to chapter 7 for R&S description. 
rvn
rvnrvn
rvn 
CONTROL  ENABLE:  YES  means  that  the  control  output 
and alarms are enabled and NO means they are disabled. 
AUTO TUNING CYCLE 
atvn
atvnatvn
atvn 
AUTO-TUNE:  YES  enables  the  auto  tuning  of  the  PID 
parameters and NO disables it. 
Pb
PbPb
Pb 
PROPORTIONAL  BAND:  Percentage  of  maximum  input 
span. Select zero for ON/OFF control. 
xyst
xystxyst
xyst 
CONTROL  HYSTERESIS  (in  engIneering.  units):  This 
parameter is only shown for ON / OFF control (Pb=0). 
‘ ir‘
‘ ir‘‘ ir‘
‘ ir‘
INTEGRAL  RATE:  Integral  time  constant  in  repetitions  per 
minute (Reset). 
dt
dtdt
dt 
DERIVATIVE TIME: Derivative time constant, in seconds. 
(t
(t(t
(t 
CYCLE TIME: PWM period in seconds. Can only be viewed 
if proportional band is other than zero. 
act
actact
act 
CONTROL ACTION: For Auto Mode only. 
•
  rE
rErE
rE  Reverse Action usually used for heating. 
•
  dir
dirdir
dir  Direct Action usually used for cooling. 
bias
biasbias
bias 
Offset for  MV  (manual reset). Range:  -100 % to  +100  %. 
Default value: 0. 
ovll
ovllovll
ovll 
OUTPUT LOW LIMIT: minimum percentage value  for  MV 
(Manipulated Variable) when in automatic control and PID. 
Default value: 0.0 % 
ovxl
ovxlovxl
ovxl 
OUTPUT HIGH LIMIT: Maximum percentage value for MV 
when in automatic control and PID. Default value: 100.0% 
sfst
sfstsfst
sfst 
SOFT START: Time in seconds during which the controller 
limits  the MV  value  progressively  from 0  to  100  %. It  is 
enabled  at  power  up  or  when  the  control  output  is 
activated. If in doubt set zero. 
Sp.a1 
Sp.a1 Sp.a1 
Sp.a1 
Sp.a2 
Sp.a2 Sp.a2 
Sp.a2 
Sp.a3 
Sp.a3 Sp.a3 
Sp.a3 
Sp.a4
Sp.a4Sp.a4
Sp.a4 
ALARM PRESET: Tripping point for alarm 1, 2, 3 and 4. 
RAMP AND SOAK PROFILE PROGRAMMING CYCLE 
tbas
tbastbas
tbas 
TIME  BASE:  Selects the  time base  for the  ramp  and  soak. 
Valid for all profile programs. 
 0
 0 0
 0  - PT1 to PT7 values are in seconds; 
 1
11
1  - PT1 to PT7 values are in minutes; 
Pr n
Pr nPr n
Pr n 
PROGRAM TO BE  VIEWED:  Selects  the  ramp and  soak 
profile  program  to  be edited/viewed  in  the following  cycle 
prompts (7 programs available). 
ptol
ptolptol
ptol 
RAMP  AND  SOAK  TOLERANCE:  maximum  deviation 
between PV and SV. Whenever this deviation is exceeded 
the time counter is halted until deviation lowers to within the 
tolerance. Set zero to disable this function. 
Psp0
Psp0Psp0
Psp0 
Psp7
Psp7Psp7
Psp7 
RAMP AND SOAK SET POINTS (0  to 7):  Set  of 8  SV 
values  which  define  the ramp  and soak  profile  segments. 
See also PT1 to 7 and PE1 to 7 below. 
Pt1
Pt1Pt1
Pt1 
Pt7
Pt7Pt7
Pt7 
RAMP  AND  SOAK  SEGMENTS  TIME  (1  to  7):  Set  of  7 
time intervals in minutes or seconds (9999 max.) for the 7 
segments of the ramp and soak program. 
Pe1
Pe1Pe1
Pe1 
Pe7
Pe7Pe7
Pe7 
RAMP  AND  SOAK  EVENT  (1  to  7): Set  of  7  values that 
define  which alarms must be activated during a ramp and 
soak  program  segment.  Alarm  function  depends  on  “rS
rSrS
rS” 
setting (Table 3). 
lp
lplp
lp 
LINK TO PROGRAM: Number of the next profile program 
to  be  linked  to follow  the  current  profile. Profiles  can  be 
linked to make larger programs of up to 49 segments. 
ALARM CYCLE 
Fva1
Fva1Fva1
Fva1 
ALARM 1 FUNCTION: Select options from Table 3. 
Fva2
Fva2Fva2
Fva2 
ALARM 2 FUNCTION: Select options from Table 3. 
Fva3
Fva3Fva3
Fva3 
ALARM 3 FUNCTION: Select options from Table 3. 
Fva4
Fva4Fva4
Fva4 
ALARM 4 FUNCTION: Select options from Table 3. 
bla1
bla1bla1
bla1 
bla2
bla2bla2
bla2 
bla3
bla3bla3
bla3 
bla4
bla4bla4
bla4 
ALARM BLOCK 1 TO 4: This function blocks the alarm at 
power-up when the units is first energized. 
YES enables and NO inhibits this blocking function. When 
enabled the alarm will not be active at power-up waiting for 
PV (Process Variable) to reach a non-alarm situation. From 
this point on the alarm will be free to actuate should a new 
alarm situation occur. 
xya1
xya1xya1
xya1 
xya2
xya2xya2
xya2 
xya3
xya3xya3
xya3 
xya4
xya4xya4
xya4 
ALARM  HYSTERESIS:  Defines  the  differential  range 
between the PV value at which the alarm is turned on and 
the value at which it is turned off (in engineering units). 
A1t1
A1t1A1t1
A1t1 
ALARM  1 TIME 1: Defines the time (6500 sec. max.) 
during which the alarm 1 output will be ON when alarm 1 is 
active. Program zero to disable this function. 
A1t2
A1t2A1t2
A1t2 
ALARM 1 TIME 2:   Defines the  OFF state  time for  the 
alarm 1 output, after being ON during the time selected on 
ALARM 1 TIME 1. Program zero to disable this function. 
A2t1
A2t1A2t1
A2t1 
ALARM 2 TIME 1: Defines the time (6500 sec. max.) during 
which the alarm 1 output will be ON when alarm 1 is active. 
Program zero to disable this function 
A2t2
A2t2A2t2
A2t2 
ALARM 2 TIME 2: Defines the time during which the alarm 
2 output will be, after being ON during the time selected on 
ALARM  2  TIME  1.  Program  zero  to  disable  this  function. 
Table 4 shows the advanced features that can be achieved 
with these time functions. 