User guide
N1100 Controller 
NOVUS AUTOMATION  10/11 
CALIBRATION OF THE INPUT 
All inputs are factory calibrated and recalibration should only be done 
by qualified personnel. If you are not familiar with these procedures 
do not attempt to calibrate this instrument. 
The calibration steps are: 
a)  Configure the type of input to be calibrated. 
b) Configure the lower and upper limits of indication for the 
maximum span of the selected input type. 
c)  At the input terminals inject a signal corresponding to a known 
indication value a little above the lower display limit. 
d) Access the parameter “
inLC
”. With the keys 
and 
, adjust 
the display reading such as to match the applied signal. Then 
press the
P 
 key. 
e)  Inject a signal that corresponds to a value a little lower than the 
upper limit of indication. 
f)  Access the parameter “
inkC
”. With the keys 
and 
, adjust 
the display reading such as to match the applied signal. Then 
press the
P 
 key. 
Note:  When checking the controller calibration with a Pt100 
simulator, pay attention to the simulator minimum excitation current 
requirement, which may not be compatible with the 0.170 mA 
excitation current provided by the controller. 
REMOTE SETPOINT CALIBRATION 
All inputs are factory calibrated and recalibration should only be done 
by qualified personnel. If you are unfamiliar with these procedures do 
not attempt to calibrate this instrument. 
If the recalibration or the remote Setpoint is required, proceed as 
follows.  
a)  Configure the remote Setpoint type to be calibrated. 
b) Program the low and high limits of the remote Setpoint to the 
minimum and maximum values respectively. 
c)  Apply to the remote Setpoint input a known signal that is slightly 
above the low limit of that input.  
d) At the parameter “
rsL(
” use the  
 and 
 keys to show in 
the display the corresponding value of the applied signal. Then 
press the 
P 
key
.
e)  Apply to the remote Setpoint input a known signal that is slightly 
below the high limit of that input. 
f)  At the parameter “
rsk(
” use the 
 and 
 keys to show in the 
display the corresponding value of the applied signal. Then press 
the 
P 
key
. 
ANALOG OUTPUT CALIBRATION 
•
  Configure I/O 5 for the current output to be calibrated, be it control 
or retransmission. 
•
  In the screen “
Ctrl
”, program manual mode (
man
). 
•
  Connect a current meter at the analog output. 
•
  Enter the calibration cycle with the correct password. 
•
  Select the screen “
ovLC
”. Press the 
 and 
 keys for the 
controller to recognize the calibration process of the current 
output.  
•
  Read the current indicated on the current meter and adjust the 
parameter “
ovLC
” to indicate this current value (use the 
 and 
 keys) 
•
  Select the screen “
ovxC
”. Press the 
 and 
 keys for the 
controller to recognize the calibration process of the current 
output.  
•
  Read the current indicated on the current meter and adjust the 
parameter “
ovxC
” to indicate this current value  
•
  Press the   key in order to confirm the calibration procedure and 
return to the operating level. 
SERIAL COMMUNICATION 
The controller can be supplied with an asynchronous RS-485 digital 
communication interface for master-slave connection to a host 
computer (master).  
The controller works as a slave only and all commands are started by 
the computer which sends a request to the slave address. The 
addressed unit sends back the requested reply. 
Broadcast commands (addressed to all indicator units in a multi drop 
network) are accepted but no reply is sent back in this case. 
CHARACTERISTICS 
•  Signals compatible with RS-485 standard. MODBUS (RTU) 
Protocol. Two wire connection between 1 master and up to 31 
(addressing up to 247 possible) instruments in bus topology. The 
communication signals are electrically insulated from the rest of 
the device; 
•  Maximum connection distance: 1000 meters. 
•  Time of disconnection for the controller: Maximum 2 ms after last 
byte. 
•  Selectable speed; 8 data bits; 1 stop bit; selectable parity (no 
parity, pair or odd); 
•  Time at the beginning of response transmission: maximum 100 
ms after receiving the command. 
The RS-485 signals are: 
D1  D  D +
B  Bi-directional data line.  Terminal 16 
D0 
D -  A  Bi-directional inverted data line.  Terminal 17 
C 
Optional connection that improves the 
performance of the communication. 
Terminal 18 
GND 
CONFIGURATION OF PARAMETERS FOR SERIAL 
COMMUNICATION 
Three parameters must be configured for using the serial type: 
bavd
:  Communication speed. 
prty
:  Parity of the communication. 
addr
:  Communication address for the controller. 
REDUCED REGISTERS TABLE FOR SERIAL 
COMMUNICATION 
COMMUNICATION PROTOCOL 
The MOSBUS RTU slave is implemented. All configurable parameters 
can be accessed for reading or writing through the communication port. 
Broadcast commands are supported as well (address 0). 
The available Modbus commands are: 
03 - Read Holding Register  06 - Preset Single Register 
05 - Force Single Coil  16 - Preset Multiple Register 
HOLDING REGISTERS TABLE 
Follows a description of the usual communication registers. For full 
documentation download the Registers Table for Serial 
Communication  in the N1100 section of our web site – 
www.novusautomation.com
. 
P 
D: