User guide
N1100 Controller 
NOVUS AUTOMATION  3/11 
PROMPT 
TYPE 
ACTION 
Off 
Disabled  Output is not used as alarm. 
Ierr 
Sensor Break 
(input Error) 
Activated when the input signal of PV is 
interrupted, out of the range limits or Pt100 
in short-circuit.  
Rs 
Event 
(ramp and Soak) 
Can be activated at a specific segment of 
program. 
rfail 
-  Reserved 
Lo 
 Minimum value 
(Low) 
SPAn
PV 
Ki 
Maximum value 
(High) 
SPAn 
PV 
Difl 
Minimum 
Differential  
(differential 
Low) 
Positive SPAn  Negative SPAn 
SV 
PV 
SV - SPAn 
SV 
PV 
SV - SPAn 
Difk 
Maximum 
Differential  
(differential 
High) 
SV 
PV 
SV + SPAn 
SV 
PV 
SV + SPAn 
Positive SPAn  Ngative SPAn  
Dif 
Differential 
(differential) 
SV 
PV 
SV + SPAn 
SV - SPAn 
SV 
PV 
SV - SPAn 
SV + SPAn 
Positive SPAn  Nagative SPAn   
Table 3 – Alarm functions 
Where SPAn refers to Setpoints of Alarm “
SPA1
”, “
SPA2
”, “
SPA3
” 
and “
SPA4
”. 
ALARM TIMER MODES 
The controller alarms can be configured to perform 4 timer modes: 
•  Continuous (normal mode). 
•  One pulse with defined duration; 
•  Delayed activation; 
•  Repetitive pulses; 
The illustrations in Table 4 show the behavior of the alarm output for 
various combinations of times T1 and T2. The timer functions can be 
configured in parameters 
A1t1
, 
A1t2
, 
A2t1
 and 
A2t2
. 
OPERATION
T 1  T 2  ACTION 
Normal 
operation 
0  0 
Alarm Event
Alarm
Output
Activation for 
a defined time 
1 s to 
 6500 s 
0 
Alarm Event
Alarm
Output
T1
Activation with 
delay 
0 
1 s to 
6500 s 
Alarm Event
Alarm
Output
T2
Intermittent 
activation 
1 s to 
6500 s 
1 s to 
6500 s 
Alarm Event
Alarm
Output
T1
T2
T1
Table 4 - Temporization Functions for the Alarms 
The LEDs associated to the alarms will light when the alarm 
condition is recognized, not following the actual state of the output, 
which may be temporarily OFF because of the temporization. 
ALARM INITIAL BLOCKING 
The initial blocking option inhibits the alarm from being recognized 
if an alarm condition is present when the controller is first energized. 
The alarm will be enabled only after the occurrence of a non-alarm 
condition followed by a new occurrence for the alarm. 
The initial blocking is useful, for instance, when one of the alarms is 
configured as a minimum value alarm, causing the activation of the 
alarm soon upon the process start-up, an occurrence that may be 
undesirable.  
The initial blocking is disabled for the sensor break alarm function. 
SQUARE ROOT EXTRACTION 
When the input type is configured as 
SQRT
  the controller assumes 
the input as a 4-20 mA while extracting the square root of the applied 
input signal. 
ANALOG RETRANSMISSION OF PV AND SP  
The analog output, when not used for control purposes, is available 
for retransmitting the PV and SP values in 0-20 or 4-20 mA. This 
analog output is electrically isolated from other inputs and outputs.  
The analog output signal is scalable, with the output range defined by 
the values programmed in the parameters “
SPLL
” and “
SPkL
”. 
It is possible to obtain a voltage output by installing a resistor shunt 
(550 Ω max.) to the current output terminals (terminals 7 and 8). The 
actual resistor value depends on the desired output voltage span. 
SOFT-START 
The soft-start feature avoids abrupt variations in the power delivered 
to the load regardless of the system power demand. 
This is accomplished by defining a limiting ramp for the control output. 
The output is allowed to reach maximum value (100 %) only after the 
time programmed in the soft-start parameter has elapsed.  
The Soft-start function is generally used in processes that require slow 
start-up, where the instantaneous application of 100 % of the available 
power to the load may cause damages to parts of the system.  
In order to disable this function, the soft-start parameter must be 
configured with 0 (zero). 
REMOTE SETPOINT 
The controller can have its Setpoint value defined by an analog, 
remotely generated signal. This feature is enabled through the 
channels I/O3, I/O4 or I/O5 when configured as digital inputs and 
configured with the function 
rsp
 (Remote SP selection) or through 
the parameter 
E.rsp
. The remote Setpoint input accepts the signals 
0-20 mA, 4-20 mA, 0-5 V and 0-10 V.  
For the signals of 0-20 and 4-20 mA, a shunt resistor of 100 
Ω
 is 
required between terminals, as shown in Figure 4c. 
CONTROL MODE 
The controller can operate in two different manners: Automatic mode 
or Manual mode. 
The parameter “
avto
” defines the control mode to be adopted. 
In Automatic mode the controller defines the amount of power to be 
applied on the process.  
In Manual mode the user himself defines this amount of power. The 
user can then adjust the MV percentage while displaying PV/MV. 
PID AUTOMATIC MODE 
For the Automatic mode, there are two different strategies of control: 
PID automatic control and ON/OFF automatic control. 
PID control has its action based on a control algorithm that takes into 
account the deviation of PV with respect to SP, the rate of change of 
PV and the steady state error. These parameters are particular to a 
system and can be obtained automatically by the controller’s Auto 
Tune feature (
Atvn
 parameter). 
On the other hand, the ON/OFF control (obtained when 
Pb
=0) 
operates with 0 % or 100 % of power, when PV deviates from SP. 
The determination of parameters 
Pb
, 
Ir
 and 
Dt 
is described in 
the item DETERMINATION OF PID PARAMETERS of this manual. 










