User guide
N1100 Controller 
NOVUS AUTOMATION  4/11 
USB INTERFACE 
The USB interface is used for CONFIGURING or MONITORING the 
controller. The NConfig software must be used for the configuration. 
It makes it possible to create, view, save and open configurations 
from the equipment or files in your computer. The tool for saving and 
opening configurations in files makes it possible to transfer 
configurations between pieces of equipment and to make backup 
copies. For specific models, the NConfig software also makes it 
possible to update the firmware (internal software) of the controller 
through the USB. 
For MONITORING purposes you can use any supervisory software 
(SCADA) or laboratory software that supports the MODBUS RTU 
communication on a serial communications port. When connected to 
the USB of a computer, the controller is recognized as a conventional 
serial port (COM x). Use the NConfig  software or consult the 
DEVICE MANAGER in the Windows CONTROL PANEL to identify 
the COM port that was assigned to the controller. Consult the 
mapping of the MODBUS memory in the controller’s communications 
manual and the documentation of your supervisory software to 
conduct the MONITORING process. 
Follow the procedure below to use the USB communication of the 
equipment: 
1.  Download the NConfig software from our website and install it on 
your computer. The USB drivers necessary for operating the 
communication will be installed together with the software. 
2.  Connect the USB cable between the equipment and the 
computer. The controller does not have to be connected to a 
power supply. The USB will provide enough power to operate the 
communication (other equipment functions cannot operate). 
3.  Open the NConfig software, configure the communication and 
start recognition of the device.  
4.  Consult the NConfig help desk for detailed instructions about 
how to use it and solve problems. 
The USB interface IS NOT SEPARATE from the 
signal input (PV) or the controller’s digital inputs and 
outputs. It is intended for temporary use during 
CONFIGURATION and MONITORING periods. For 
the safety of people and equipment, it must only be 
used when the piece of equipment is completely 
disconnected from the input/output signals. Using the 
USB in any other type of connection is possible but 
requires a careful analysis by the person responsible 
for installing it. When MONITORING for long periods 
of time and with connected inputs and outputs, we 
recommend using the RS485 interface, which is 
available or optional in most of our products. 
INSTALLATION / CONNECTIONS 
The controller must be fastened on a panel, following the sequence 
of steps described below: 
•  Prepare a panel cut-out of 45.5 x 45.5 mm; 
•  Remove the mounting clamps from the controller; 
•  Insert the controller into the panel cut-out; 
•  Slide the mounting clamp from the rear to a firm grip at the panel. 
RECOMMENDATIONS FOR THE INSTALLATION 
•  To minimize the pick-up of electrical noise, the low voltage DC 
connections and the sensor input wiring should be routed away 
from high-current power conductors. If this is impractical, use 
shielded cables. In general, keep cable lengths to a minimum. 
•  All electronic instruments must be powered by a clean mains 
supply, proper for instrumentation. 
•  It is strongly recommended to apply RC'S FILTERS (noise 
suppressor) to contactor coils, solenoids, etc. 
•  In any application it is essential to consider what can happen when 
any part of the system fails. The controller features by themselves 
can not assure total protection. 
ELECTRICAL CONNECTIONS 
The controller complete set of features is drawn in Figure 1: 
Figure 1 - Connections of the back panel 
Power Supply Connections 
Observe the power 
requirement for the 
unit. of required power 
supply. 
Figure 2 – Power supply connections 
Input Connections 
•  Thermocouple (T/C) and 0-50 mV 
The Figure 3a indicates the wiring for the thermocouple and 0-50 mV 
signals. If the thermocouple wires need  to be extended, use 
appropriate compensation cables. 
•  RTD (Pt100): 
Figure 3b shows the Pt100 wiring, for 3 conductors. For proper cable 
length compensation, use conductors of same gauge and length). 
For 4-wires Pt100, leave one conductor disconnected at the 
controller. For 2-wire Pt100, short-circuit terminals 11 and 12. 
T/C, 0-50mV
Pt100
Figure 3a - Connection of T/C,  
0-50 mV 
Figure 3b - Connection of Pt100 a  
     3-wire 
•  4-20 mA: 
The connections for current signals 4-20 mA must be carried-out 
according to Figure 4a. 
4-20mA
Figure 4a - Current connection 
4-20 mA 
Figure 4b – Connection for 5 V 
•  5 V 
Refer to Figure 4b for connecting voltage signals. 










