User guide
N1100 Controller 
NOVUS AUTOMATION  7/11 
CYCLE OF ALARMS 
Fva1 
Fva2 
Fva3 
Fva4 
Function Alarm
Functions of Alarms. Defines the functions for the 
alarms among the options of the Table 3. 
oFF, iErr, rS, Lo, xi, DiFL, DiFx, DiF
bla1 
bla2 
bla3 
bla4 
Blocking Alarm
Block of Alarms. This function blocks the alarms1 
to 4. 
YES
  - enables initial blocking 
NO
  - inhibits initial blocking 
xya1 
xya2 
xya3 
xya4 
Hysteresis of 
Alarm
Alarm Hysteresis. Defines the difference between 
the value of PV at which the alarm is triggered and 
the value at which it is turned off (in engineering 
units).. 
A1t1 
A2t1 
Alarm Time t1 
Defines the temporization time t1, for the alarms. 
In seconds. 
The value 0 (zero) disables the function. 
A1t2 
A2t2 
Alarm Time t2 
Defines the temporization time t2 for the alarms 
time functions. In seconds. 
The value 0 (zero) disables the function. 
CYCLE OF SCALE 
Type 
Type 
INPUT TYPE: Selects the input signal type to be 
connected to the process variable input. Refer to 
Table 1 for the available options. 
This must be the first parameter to be 
configured. 
Dppo 
Decimal Point 
Defines the decimal point position. 
vnI t 
Unit
UNIT: Defines the indication unit in  Celsius “°
(
“ or 
Fahrenheit “°
f
“
This parameter is presented whenever a 
temperature sensor is configured as input.  
0ffs 
Offset 
SENSOR OFFSET: Offset value to be added to 
the PV reading to compensate sensor error.  
Default value: zero. 
Spll 
Setpoint Low 
Limit
Defines the SP lower limit of. 
For the linear analog input types available (0-20 mA, 
4-20 mA, 0-50 mV and 0-5 V), defines the minimum 
PV indication range, besides limiting the SP 
adjustment. 
Defines lower limit for range retransmission PV and 
SP. 
Spxl 
Setpoint High 
Limit
Defines the upper limit for adjustment of SP. 
For the linear analog input types available (0-20 mA, 
4-20 mA, 0-50 mV and 0-5 V), defines the maximum 
PV indication range, besides limiting the SP 
adjustment. 
Defines upper limit for range retransmission PV and 
SP. 
e.rsp 
Enable Remote 
SP 
Enables remote SP. 
  YES
  Enables the Function 
  no
  Does not enable the Function 
This parameter is not displayed when the remote 
SP selection is defined by a Digital Input. 
rsp 
Remote SP 
Defines the signal type for the remote SP. 
  0-20
  current of 0-20 mA 
  4-20
  current of 4-20 mA 
  0-5
  voltage of 0-5 V
0-10
  voltage of 0-10 V 
Parameter displayed when remote SP is enabled. 
rsll 
Remote SP 
Low Limit
REMOTE SETPOINT LOW LIMIT: used in 
conjunction with the rSxL, scales the remote SP 
input defining the initial value in the remote SP 
indication range. 
Parameter displayed when remote SP is enabled. 
rskl 
Remote SP 
High Limit
REMOTE SETPOINT HIGH LIMIT: defines the full 
scale indication of the Remote Setpoint. 
Parameter displayed when remote SP is enabled.  
bavd 
Baud Rate 
Serial Communication Baud Rate  selection, in 
kbps: 
1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6 e 115.2  
prty 
Parity 
Parity of the serial communication. 
  none
  Without parity 
  Ewem
  Even parity 
  0dd
  Odd parity 
Addr 
Address 
SLAVE ADDRESS SELECTION: Identifies the 
controller in the network. The  possible address 
numbers are from 1 to 247.  
CYCLE DE I/OS 
Io 1 
Function of the channel I/O 1: Selection of the 
function used in the channel I/O 1, according to the 
Table 2. 
Io 2 
Function of the channel I/O 2: Selection of the 
function used in the channel I/O 2, according to the 
Table 2. 
Io 3 
Function of the channel I/O 3: Selection of the 
function used in the channel I/O 3, according to the 
Table 2. 
Io 4 
Function of the channel I/O 4: Selection of the 
function used in the channel I/O 4, according to the 
Table 2. 
Io 5 
Function of the channel I/O 5: Selection of the 
function used in the channel I/O 5, according to the 
Table 2. 
CALIBRATION CYCLE 
All of the input and output types are calibrated in the factory. If a 
recalibration is required, this should be carried out by a 
experienced personnel. If this cycle is accidentally accessed, pass 
through all the parameters (without pressing the 
 or   keys) 
until the PV/SV screen is displayed 
pass 
Password 
Input of the Access Password. 
This parameter is presented before the protected 
cycles. See item Protection of Configuration. 
(alib 
Calibration? 
Allows instrument calibration. 
YES
 - Perform calibration 
  NO - Do not perform calibration 
inL( 
Input Low 
Calibration 
Enter the value corresponding to the low scale 
signal applied to the analog input. 
See section MAINTENANCE / Input Calibration. 
ink( 
Input High 
Calibration 
Enter the value corresponding to the full scale 
signal applied to the analog input. 
See section MAINTENANCE / Input Calibration. 