User guide
N1100 Controller 
NOVUS AUTOMATION  9/11 
The master password is made up by the last three digits of the serial 
number of the controller added to the number 9000. 
As an example, for the equipment with serial number 07154321, the 
master password is 9 3 2 1. 
PROGRAMS OF RAMP AND SOAK 
This feature allows the creation of Ramp and Soak Setpoint Profiles 
(Programs). Up to 7 different profiles with 7 segments each can be 
programmed. Longer profiles of up to 49 segments can be created by 
linking 2 or more profiles together. 
The figure below displays a profile model: 
Figure 8 - Example of a Ramp and Soak program 
Once a profile is defined and selected for execution, the controller 
starts to generate the SP profile automatically in accordance with the 
elaborated program. 
To execute a profile with fewer segments just program 0 (zero) for 
the time intervals that follow the last segment to be executed. 
SV 
Time 
T1 
T2 
T3 
SP0 
SP1 
SP2 
SP3 
T4=0 
Figure 9 - Program example with few segments 
The program tolerance “
ptol
” defines the maximum deviation 
between PV and SP for the execution of the profile. If this deviation is 
exceeded, the program will be halted until the deviation falls to within 
the tolerance band. 
Programming 0 (zero) in the “
Ptol
” parameter disables the program 
tolerance and the profile execution will continue regardless of the PV 
value (time priority as opposed to SP priority). 
LINK OF PROGRAMS 
It is possible to create a more complex program (up to 49 segments), 
joining two or more programs. This way, at the end of a program 
execution the controller immediately starts to run the next one, as 
indicated in the parameter “
LP
". 
To force the controller to run a given program or many programs 
continuously, it is only necessary to link a program to itself or the last 
program to the first. 
SV 
time 
T1 
T2 
T3 
T4 
T5 
T1 
T2 
T3 
T4 
SP0 
SP1 
SP2 
SP3 
SP4 
SP5 / SP0 
SP1 
SP2 
SP3 
SP4 
Program 1 
Program 2 
Figure 10 – Example of interlinked programs 
EVENT 
The Event Alarm function associates the alarms to specific segments 
of a program. The information of which alarms are to be activated or 
deactivated is given in parameters “ 
PE1
“ to “ 
PE7
. Press the 
and 
 keys until the desired alarm numbers are displayed.
The Event Alarm requires that the Alarm function be configured as 
“
rS
 “. 
Notes: 
1.  If 
PtoL
 is different than zero, the controller will wait for the PV to 
reach the first program set point SP0 in order to start the 
program execution. Otherwise, it will start promptly. 
2.  Should any power failure occur, the controller resumes the 
program execution at the beginning of the segment where it was 
interrupted.  
DETERMINATION OF PID PARAMETERS 
During the automatic tuning the process is controlled in ON / OFF 
mode in the programmed SP. Depending on the process behavior, 
oscillations may occur above or below the Setpoint. The automatic 
tuning may take many minutes to the concluded, particularly in slow 
processes.  
When the parameter ATUN is altered to YES, the automatic tuning 
is immediately initiated by the controller (provided RUN=YES, 
otherwise it will wait until this condition becomes true).  
Some recommendations for the automatic tuning process are:  
• 
avto
 = YES: make sure the controller is set for automatic control 
mode. 
•  Disable Ramp & Soak programs configuring 
Pr n
 = 0. (the 
automatic tuning algorithm expects a stable Setpoint value) 
•  Select a Setpoint that is close or equal to the desired process 
Setpoint. 
•  Enable the automatic tuning (
atvn
 = YES). 
•  Enable outputs if not yet enabled (
rvn
 = YES). 
The “TUNE” indicator on the display stays lit until the completion of 
the automatic tuning process. 
For control output types relay or pulse, the automatic tuning 
calculates the longest suitable period (cycle time (t) for the PWM 
output. The cycle time period may be reduced if the process 
experiences some oscillation.  When driving a SSR, it’s 
recommended to set (t = 1 s. 
If the automatic tuning does not result in a satisfactory control, refer 
to Table 7 for guidelines on how to correct the behavior of the 
process. 
PARAMETER  VERIFIED PROBLEM  SOLUTION 
Proportional Band 
Slow answer  Decrease 
Great oscillation  Increase 
Rate of Integration 
Slow answer  Increase 
Great oscillation  Decrease 
Derivative Time 
Slow answer or instability  Decrease 
Great oscillation  Increase 
Table 7 - Guidance for manual adjustment of the PID parameters 
MAINTENANCE 
PROBLEMS WITH THE CONTROLLER 
Connection errors and inadequate programming are the most 
common errors found during the controller operation. A final revision 
may avoid loss of time and damages. 
The controller displays some messages to help the user identify 
problems. 
MENSSAGE  DESCRIPTION OF THE PROBLEM 
----
Open input. No sensor or signal.  
Err1
Err6
Connection and/or configuration errors. 
Check the wiring and the configuration. 
Other error messages may indicate hardware problems requiring 
maintenance service. When contacting the manufacturer, inform the 
instrument serial number, obtained by pressing the key 
for more 
than 3 seconds. 










