PRESENTATION
The N1100 is an ext raordinaril y v ersati l e process controller. It holds in
one singl e i nstrument al l the mai n features needed for the vast maj ority
of industrial processes. It accepts in a single model virtually all the
sensors and signals used in the industry and provides the main
output types required for the operation of diverse processes.
The configuration c an be performed directly on the c ontroller or through
the USB interface. The NConfig software (free) is the configuration
management tool. Connected to the USB of a Windows computer, the
controller i s recogniz ed as a serial c ommunications port (COM) running
with a Modbus RTU protocol.
Through the USB interface, even if disconnected from the power supply,
the configuration performed in a piece of equipment can be can be
saved in a file and repeated in other pieces of equipment that require
the same configuration.
It is important that the users read carefully this manual before using
the controller. Verify if the release of this manual matches the
instrument versi on (the fi rmware versi on is shown when the c ontroll er
is energized).
Multi-sensor universal input (sensors and standard signals);
Relay, 4-20 mA and logic pulse c ontrol outputs al l avail able in the
standard model;
Self-tuning of PID parameters;
Automatic / Manual function with “bumpless” transfer;
Four modes of independents alarms, with functions of minimum,
maximum, differential (deviation), open sensor and event;
Timer functions that can be associated to the alarms;
Retransmission of PV or SP in 0-20 mA or 4-20 mA;
Input for remote setpoint;
Digital input with 5 functions;
Programmable soft-start;
7 setpoint profile programs with 7 segments each, with the ability
to be linked together for a total of 49 segments;
Comunicação serial RS-485, protocolo MODBUS RTU;
Password for parameters protection;
Universal power supply.
CONFIGURATION
INPUT TYPE SELECTION
Select the input type (in parameter “
tYPE
”) from Table 1 below.
TYPE CODE CHARACTERISTICS
J
Tc j
Range: -110 a 950 º C (-166 a 1742 ºF)
K
Tc k
Range: -150 a 1370 º C (-238 a 2498 ºF)
T
Tc t
Range: -160 a 400 ºC (-256 a 752 º F)
N
Tc n
Range: -270 a 1300 º C (-454 a 2372 ºF)
R
Tc r
Range: -50 a 1760 º C (-58 a 3200 ºF)
S
Tc s
Range: -50 a 1760 º C (-58 a 3200 ºF)
B
Tc b
Range: 400 a 1800 ºC (752 a 3272 ºF)
E
Tc e
Range: -90 a 730 º C (-130 a 1346 ºF)
Pt100
Pt
Range: -200 a 850 º C (-328 a 1562 ºF)
0–50 mV
L.0.50
Linear Signals
Programm able indication f rom-1999 to 9999
4-20 mA
L.4.20
0-5 Vdc
L0.5
0-10 Vdc
L0.10
4-20 mA
Sqrt
4-20 mA input with Square Root extraction.
Programm able indication from-1999 to 9999
4-20 mA
NO
LINEAR
ln j
Non Linear Analog Signals
Indication r ange depends on the s elected sensor
Ln k
ln t
ln n
ln r
ln s
ln b
ln E
Ln.Pt
Table 1 - Input types
Note: All input types are factory calibrated.
OUTPUTS, ALARMS AND DIGITAL INPUTS CONFIGURATION
The controller input/output channels can assume multiple functions,
depending on configuration: control output, alarm output, digital
output, digital input, and PV or SV analog retransmission. These
channels are identified as I/O1, I/O2, I/O3, I/O4, I/O 5 and I/O6.
The basic controller model comes loaded with:
I/O1 and I/O2 - SPDT relay output;
I/O3 and I/O4 - SPST relay output;
I/O5 - analog output (0-20 or 4-20 mA), pulse 10 V max, digital I/O;
I/O6 - Digital Input.