User Manual
NOVUS AUTOMATION  1/11 
Controller N3
000 
UNIVERS
AL PROCESS CONTROLLER – INSTRUCTIONS MANUAL – V3.0x 
SAFETY ALERTS 
The symbols below are used on the equipment and throughout this 
document to draw the user’s attention to important operational and 
safety information. 
CAUTION or WARNING:  
Read complet e ins t ruc t ions pr ior to 
inst all ati on and operat i on of t he unit .  
CAUTION or WARNING : 
Electric al Shock H azard 
All safety related instructions that appear in the manual must be 
observed to ensure personal safety and to prevent damage to either 
the instrument or the system. If the instrument is used in a manner 
not specified by the manufacturer, the protection provided by the 
equipment may be impaired. 
PRESENTATION 
The N1100 is an ext raordinaril y v ersati l e process controller. It holds in 
one singl e i nstrument al l the mai n features needed for the vast maj ority 
of industrial processes. It accepts in a single model virtually all the 
sensors and signals used in the industry and provides the main 
output types required for the operation of diverse processes.  
The configuration c an be performed directly on the c ontroller or through 
the USB interface. The NConfig  software (free) is the configuration 
management tool. Connected to the USB of a Windows computer, the 
controller i s recogniz ed as a serial c ommunications port (COM) running 
with a Modbus RTU protocol. 
Through the USB interface, even if disconnected from the power supply, 
the configuration performed in a piece of equipment can be can be 
saved in a file and repeated in other pieces of equipment that require 
the same configuration. 
It is important that the users read carefully this manual before using 
the controller. Verify if the release of this manual matches the 
instrument versi on (the fi rmware versi on is shown when the c ontroll er 
is energized). 
•  Multi-sensor universal input (sensors and standard signals); 
•  Relay, 4-20 mA and logic pulse c ontrol outputs al l avail able in the 
standard model; 
•  Self-tuning of PID parameters; 
•  Automatic / Manual function with “bumpless” transfer; 
•  Four modes of independents alarms, with functions of minimum, 
maximum, differential (deviation), open sensor and event; 
•  Timer functions that can be associated to the alarms; 
•  Retransmission of PV or SP in 0-20 mA or 4-20 mA; 
•  Input for remote setpoint; 
•  Digital input with 5 functions; 
•  Programmable soft-start; 
•  7 setpoint profile programs with 7 segments each, with the ability 
to be linked together for a total of 49 segments; 
•  Comunicação serial RS-485, protocolo MODBUS RTU; 
•  Password for parameters protection; 
•  Universal power supply. 
CONFIGURATION 
INPUT TYPE SELECTION 
Select the input type (in parameter “
tYPE
”) from Table 1 below. 
TYPE  CODE  CHARACTERISTICS 
J 
Tc j 
 Range: -110 a 950 º C (-166 a 1742 ºF) 
K 
Tc k 
 Range: -150 a 1370 º C (-238 a 2498 ºF) 
T 
Tc t 
 Range: -160 a 400 ºC (-256 a 752 º F) 
N 
Tc n 
 Range: -270 a 1300 º C (-454 a 2372 ºF) 
R 
Tc r 
 Range: -50 a 1760 º C (-58 a 3200 ºF) 
S 
Tc s 
 Range: -50 a 1760 º C (-58 a 3200 ºF) 
B 
Tc b 
 Range: 400 a 1800 ºC (752 a 3272 ºF) 
E 
Tc e 
 Range: -90 a 730 º C (-130 a 1346 ºF) 
Pt100 
Pt 
 Range: -200 a 850 º C (-328 a 1562 ºF) 
0–50 mV 
L.0.50 
 Linear Signals 
 Programm able indication f rom-1999 to 9999 
4-20 mA 
L.4.20 
0-5 Vdc 
L0.5 
0-10 Vdc 
L0.10 
4-20 mA  
Sqrt 
 4-20 mA input with Square Root extraction.  
 Programm able indication from-1999 to 9999 
4-20 mA 
NO 
LINEAR 
ln j 
 Non Linear Analog Signals  
 Indication r ange depends on the s elected sensor 
Ln k 
ln t 
ln n 
ln r 
ln s 
ln b 
ln E 
Ln.Pt 
Table 1 - Input types 
Note: All input types are factory calibrated. 
OUTPUTS, ALARMS AND DIGITAL INPUTS CONFIGURATION 
The controller input/output channels can assume multiple functions, 
depending on configuration: control output, alarm output, digital 
output, digital input, and PV or SV analog retransmission. These 
channels are identified as I/O1, I/O2, I/O3, I/O4, I/O 5 and I/O6. 
The basic controller model comes loaded with: 
I/O1 and I/O2 - SPDT relay output; 
I/O3 and I/O4 - SPST relay output; 
I/O5 - analog output (0-20 or 4-20 mA), pulse 10 V max, digital I/O; 
I/O6 - Digital Input. 
Note: When a function is selected to operate through digital 
input, the controller does not respond to the equivalent function 
command given in the frontal keypad. 