User Manual
DigiGate Profibus 
NOVUS AUTOMATION  8/11  
Tables for data interchange 
Reading Table: 
Fig. 8 – Reading of the Modbus slaves by the Profibus master 
The Reading Table or Input Table contains the values read of the Modbus network equipment registers (according to 
the equipment configuration), besides a status register (1st position of the table). The table corresponds to the field of 
data sent from the DigiGate to the Profibus master. Its format is as follows: 
Position 0 
Status Register – in details as follows 
Position 1 
Register value of the equipment in the Modbus network 
Position 2 
Register value of the equipment in the Modbus network 
................. 
....................................................................................................... 
Position 121 
Register value of the equipment in the Modbus network 
At the equipment configuration the table positions are associated to the Modbus registers which are to be made 
available. All positions are values of 16 bits. The table size is preset (122 words of 16 bits), the size of the data block 
sent to the Profibus network, however, is configurable and may not correspond to the table in its totality. 
Status Register 
Bit15  Bit14  Bit13  Bit12  Bit11  Bit10  Bit9  Bit8  Bit7  Bit6  Bit5  Bit4  Bit3  Bit2  Bit1  Bit0 
DV  WDN  RS1  RS0  ET2  ET1  ET0  EQ  AN7  AN6  AN5  AN4  AN3  AN2  AN1  AN0 
•  Bit 15 – DV (Data Valid) – This bit is inverted, becoming equal to bit 15 of the control register when the input 
table has been updated. 
•  Bit 14 – WDN (Write Done) - This bit is inverted, becoming equal to bit 14 of the control register when a 
writing operation has been performed in the Modbus network. 
•  Bit 13, Bit 12 – RS1, RS0 (Reset State) 
00 – Gateway not reset 
01 – At least one reading scan operation of the Modbus already executed 
10 – First writing operation performed (invalid) 
11 – First reading and first writing operation already performed. 
•  Bit 11, Bit 10, Bit 9 - ET2, ET1, ET0 (Error Type) 
000 - No error 
001 - Parity error 
010 - CRC error 
011 – Byte Time out error – response not complete 
100 – Response Delay error – no response 
101 - Exception error– probable incoherency in the message requested to the slave 