CONNECTIONS 
This module operates only when connected to a PC USB bus, using the included type-A to mini-B cable. The following 
figure shows all possible input connections. 
Signal wires connected  to all inputs  should be  kept separated  from power  wires, and  when possible 
installed inside of grounded electrical ducts. 
Pt100 WIRING 
Connections of channel 1 are on terminals 6, 7 and 8. For channel 2 on terminals 2, 3 and 4. 
Connection with 3 wires from the sensor element to the module is necessary to cancel the 
cable  resistance  error  in  the  measurement.  The  3  wires  must  have  the  same  length  and 
gauge. 
To connect a Pt100 with 2 wires, connect terminals 7 and 8 (channel 1) or 3 and 4 (channel 
2). 
THERMOCOUPLE WIRING 
Connections  of  channel  1  are  on  terminals  6  and  7.  For  channel  2  on  terminals  2  and  3. 
Observe indicated polarity. 
Cables for thermocouple connection must have the same thermo-electrical characteristics of 
the  thermocouple  element  (compensation  or  extension  cable).  Observe  that  both  the 
thermocouple and the compensation cable must be connected with correct polarity. 
If  compensation  cable  is  not  used  or  is  not  connected  with  the  correct  polarity,  large 
measurement errors will arise. 
4-20 mA WIRING 
Connections  of  channel  1  are  on  terminals  6  and  7.  For  channel  2  on  terminals  2  and  3. 
Observe indicated polarity. 