User guide

5
Note: The ELC 78 & ELC712 will normally be
configured as maintained. The momentary option is
intended for use with latching relays.
An EL78 configured as momentary will only have 4
channels. Relays 1, 3, 5, & 7 will provide a one second
ON pulse for channels 1, 2, 3, and 4 respectively.
Relays 2, 4, 6, & 8 will provide a one second OFF
pulse for channels 1, 2, 3, and 4 respectively.
An EL712 configured as momentary will only have 6
channels. Relays 1, 3, 5, 7, 9 and 11 will provide a
one second ON pulse for channels 1, 2, 3, 4, 5 and
6, respectively. Relays 2, 4, 6, 8, 10 and 12 will
provide a one second OFF pulse for channels 1, 2, 3,
4, 5 and 6, respectively.
Use the NEXT key to continue set-up.
0.2 CLOCK FORMAT
Toggle between 12 HR (AM/PM) or 24 HR (00:00-
23:59) clock format using the +/- key.
Press the PROGRAM key to begin programming steps
in the TIME header.
1.0 TIME MODE
This mode is used for setting time, date and daylight
saving time.
Use the NEXT key to begin programming.
1.1 SET CLOCK
Use the + and - keys to modify the flashing item.
Use the NEXT key advance to the next flashing item.
Set current hours, minutes, seconds, and day of week.