Specification
POLARIS™
Pre-Insulated Connectors
Max Ampacity for “Free Air” Installation:
NSi Industries LLC
800.321.5847
www.nsiindustries.com
SIZE OF  
CONNECTOR
# OF 
PARALLEL   
CONDUCTORS
# OF  
CONNECTOR 
WIRE PORTS
COPPER 
CONDUCTOR   
(AMPS)
ALUMINUM 
CONDUCTOR 
(AMPS)
250
2 4 527 410
250
3 6 790 615
250
4 8 1053 820
350
2 4 657 514
350
3 6 985 770
350
4 8 1314 1028
500
2 4 806 631
500
3 6 1209 946
500
4 8 1612 1262
600
2 4 1035 810
600
3 6 1554 1215
600
4 8 2070 1620
750
2 4 1178 930
750
3 6 1767 1395
750
4 8 2356 1860
To enable users to achieve desired ampacity with a 
UL listed pre-insulated connector through paralleling, 
NSi Industries’ Polaris
™
 line of connectors have been 
fully tested and meet the specifications for UL 486 
A/B for 90°C conductor (copper and aluminum) in 
accordance with the National Electrical Code (NEC). 
De-rating of conductors per the NEC can vary 
depending on the type of installation (i.e. conductors 
in free air, conductors in a wireway, number of 
conductors in a wireway, etc.) and size of conductors 
(250KCMIL-500KCMIL de-rated by 65%, 600KCMIL 
and larger de-rated by 75%). It is expected that 
the wire connectors will be used with parallel feeds 
meeting the NEC. See the chart to the right that shows  
the maximum ampacity for connectors, assuming a 
“free air” installation.
Although these connectors have been tested in the 
worst case condition (Line conductor(s) on one end of 
the connector and load conductor(s) on opposite end 
of connector), laboratory tests have shown that the 
connector will run cooler if the load is “distributed”. 
The recommendation is to stagger the line and load 
conductors (line-load-line-load-line-load) throughout 
the wire connector. If that is not possible, another 
practice that would run cooler is to place the main/
line conductors in the center of the connector and 
the load/tap conductors on the outer ports of the 
connector.
SPECIFICATION 
SHEET
PROJECT INFORMATION: 
JOB: 
APPROVALS: 

