Cut Sheet
Table Of Contents
TORK PHOTOCONTROLS
441
FEATURES
APPLICATIONS
SPECIFICATIONS
FEATURES
APPLICATIONS
5000M SERIES
DELAYED RESPONSE UTILITY GRADE
MOV SURGE ARRESTOR
PHOTOCONTROL
5000M SERIES
For use on streets, highways and
other luminaries equipped with
locking type receptacles, where
most stringent surge protection
is needed.
SENSOR: Conformal coated CdS photocell resists effects
of moisture and airborne contaminants. Photocell responds
to the light spectrum near to that of a human eye.
OPERATION: Delayed response prevents false switching
due to light from vehicles or lighting, etc.
STANDARDS: Meets UL773 and ANSI C136.10 including
color designations. Also meets EEI NEMA standards.
ANSI DOME COLOR-CODE: Grey 105-130VAC,
Maroon 208-277VAC, Blue 105-285VAC,
Yellow 480VAC, Green 347VAC.
HOUSING: Polycarbonate housing and window, UV
stabilized for permanent color. Provides high impact
performance, flammability resistance, and electrically
safe operations.
CONTACTS: Bi-metal provides positive snap action
switching, reducing bounce and prolonging contact life.
ON/OFF: Turn-ON is 1 to 3 fc. Turn-OFF
to Turn-ON ratio is 5 max.
TIME DELAY: ON and OFF.
CELL: CdS, epoxy conformal coated ½”
and 1" diameter models.
SURGE ARRESTOR: 380 joule MOV
(metal oxide varistor) exceeds ANSI and
NEMA requirements.
LOCKING PRONGS: Solid brass for
maximum corrosion resistance and
electrical conductivity.
TEMPERATURE RANGE:
-40 °F to +140 °F (-40 °C to +60 °C).
FAIL MODE: ON.
WARRANTY: 3 years.
CAT.
NO.
UPC
CODE
VOLTAGE
(VAC) 50-60Hz
LIGHT
SENSOR
RATING
TUNGSTEN BALLAST
5001M 61012 105-130 1" 2000W 1800VA
5004M 61013 208-277 1" 3470-4620W 2080-2770VA
5007M 61014 105-130/208-285 1/2"
2000W/
3470-4620W
1800VA/
2080-2770VA
5008M* 61017 480 1" 7500W 4800VA
5021M 61015 105-130 1/2" 2000W 1800VA
5024M 61016 208-277 1/2" 3470-4620W 2080-2770VA
5026M** 61045 347 1/2" 5760W 3470VA
*Not UL listed or CSA certified. **CSA certified only.
NEW!
NL1
Line
(Black)
105 to 305 volt
single phase grounded
supplies and loads
Load (Red)
Load
Neutral
(White)
105 to 285 volt
single phase grounded
supplies and loads
Receptacle Surface
2
3
/16"
3
3
/16"
2"