Cut Sheet

How to Achieve a Good Electrical Connection
THE QUALITY OF AN ELECTRICAL
CONTACT IS DETERMINED BY:
TWO WAYS TO CONNECT
IN PARALLEL:
Belleville
washer
Flat
washer
Flat
washer
Belleville
washer
1. CONTACT SURFACE CONDITIONS
The surface has to be flat but not polished. Another important point: cleaning
the surfaces before connection. They must be oxide and grease free.
2. CONTACT SURFACE(S) - OVERLAP
The overlap (H) should be not less than 5 times the thickness (e)
of the thinnest of the conductors.
3. CLAMPING TORQUE CALCULATION
With a class coated bichromated bolt (SAE Grade 5), using “Belleville
and Flat” washers tightened with a torque wrench, without lubrication.
SAE Grade 5 hardware can be used except where otherwise
designated by the designer of the pieces installed
Belleville and Flat washers to provide resistance to vibration
Slotted holes are acceptable in applications where additional
forming is anticipated during installation
Bolt size 1/4”-20
5/16”-18
3/8”-16
7/16”-14
1/2”-13 9/16”-12 5/8”-11
Torque
(foot-pounds)
9 18 31 50 75 110 150
Alt - Metric
Bolt size M6 M8 M10 M12 M14 M16
Torque
(newton-meters)
13 30 60 110 174 274
Top ERIFLEX FLEXIBAR must be
stripped and bent to insure good
contact area
Install with Grade 5 or better
hardware and torque
www.erico.com
11
Grade 5 Bolt
Grade 5 Bolt
Belleville Washer
Belleville Washer
Belleville Washer
Belleville Washer
Contactor /
Circuit Breaker
Contactor /
Circuit Breaker
Grade 5 Nut
Grade 5 Nut
Flat Washer
Flat Washer
Flat Washer
Flat Washer
ERIFLEX FLEXIBAR
ERIFLEX FLEXIBAR