Cut Sheet
FLEXIBLE CONDUCTORS Power shunts
Spec-01138 D
EQUIPMENT PROTECTIONSUBJECT TO CHANGE WITHOUT NOTICEPOWER AND GROUNDING CONNECTIVITY23
POWER SHUNTS
PBC BRAIDED POWER SHUNT
FEATURES
• Ideal for transformer-busduct link
• Undrilled palms can be customize by power press to fit customer
specific designs
• Extra flexible power connection and good resistance to vibration
SPECIFICATIONS
• Wire Diameter: 0.006 (in.)
• Material: Copper
FINISH
• Finish: Tinned
/
$
%
&
Catalog Number
Cross Section .T 30 K .T 50 K
Length
L (in.)
A (in.) B (in.) C (in.)
2 Bar Current
Coefficient
Qty.
PBC100X250 197.35 kcmil 349 A 462 A 9.84 1.38 1.58 0.28 1.72 2
PBC100X500 197.35 kcmil 349 A 462 A 19.7 1.38 1.58 0.28 1.72 2
PBC120X250 236.82 kcmil 385 A 511 A 9.84 1.38 1.58 0.3 1.72 2
PBC150X250 296.03 kcmil 440 A 583 A 9.84 2.17 1.97 0.32 1.72 2
PBC150X500 296.03 kcmil 440 A 583 A 19.7 2.17 1.97 0.32 1.72 2
PBC200X250 394.70 kcmil 550 A 729 A 9.84 2.17 1.97 0.35 1.72 2
PBC200X500 394.70 kcmil 550 A 729 A 19.7 2.17 1.97 0.35 1.72 2
PBC250X300 493.38 kcmil 651 A 863 A 11.8 3.35 1.97 0.41 1.72 2
PBC300X400 592.06 kcmil 716 A 948 A 15.75 3.35 2.36 0.43 1.65 2
PBC400X400 789.41 kcmil 853 A 1,131 A 15.75 3.35 3.15 0.43 1.6 2
PBC500X400 986.76 kcmil 917 A 1,216 A 15.75 4.13 3.94 0.43 1.65 2
PBC600X450 1,184.12 kcmil 1,101 A 1,459 A 17.7 4.13 3.94 0.51 1.6 2
PBC800X450 1,578.82 kcmil 1,376 A 1,823 A 17.7 4.13 3.94 0.55 1.6 2
PBC1000X450 1,973.52 kcmil 1,651 A 2,188 A 17.7 4.13 3.94 0.63 1.6 2
PBC1200X500 2,368.23 kcmil 1,982 A 2,626 A 19.7 4.92 4.72 0.69 1.6 2
When used in parallel, the two shunts must be spaced with a minimum distance equal to the thickness of the shunt to allow air cooling.