SPECIFICATIONS
Material: Copper
FINISH
Finish: Tinned
Wire Diameter: 0.006 (in.)
Catalog Number
Nominal
Current
Cross Section
Number
of Wires
Length (ft.) Thickness (in.) Width (in.) Unit Weight (lb.) Qty.
FTCB153 30 A 5.92 kcmil 168 82 0.04 0.2 0.07 1
FTCB155 45 A 9.87 kcmil 288 82 0.04 0.3 0.11 1
FTCB158 65 A 15.78 kcmil 456 82 0.06 0.3 0.18 1
FTCB1510 75 A 19.74 kcmil 576 82 0.06 0.4 0.22 1
FTCB1516 120 A 31.57 kcmil 896 82 0.06 0.6 0.35 1
FTCB1520 140 A 39.47 kcmil 1,120 82 0.06 0.8 0.44 1
FTCB1525 150 A 49.34 kcmil 1,404 82 0.06 0.9 0.55 1
FTCB1530 180 A 59.20 kcmil 1,692 82 0.08 0.9 0.66 1
FTCB1535 200 A 69.07 kcmil 1,980 82 0.1 0.9 0.77 1
FTCB1540 220 A 78.94 kcmil 2,272 82 0.1 1 0.88 1
FTCB1550 250 A 98.68 kcmil 2,848 82 0.12 1.1 1.1 1
FTCB1560 280 A 118.41 kcmil 3,392 82 0.12 1.2 1.32 1
FTCB1570 290 A 138.15 kcmil 3,968 82 0.14 1.2 1.54 1
FTCB1575 300 A 148.01 kcmil 4,256 82 0.16 1.2 1.65 1
FTCB15100 360 A 197.35 kcmil 5,664 82 0.16 1.6 2.2 1
Wire Diameter: 0.008(in.)
Catalog Number
Nominal
Current
Cross Section
Number
of Wires
Length (ft.) Thickness (in.) Width (in.) Unit Weight (lb.) Qty.
FTCB205 45 A 9.87 kcmil 168 1,640 0.04 0.3 0.11 1
FTCB2010 75 A 19.74 kcmil 312 492 0.06 0.4 0.22 1
FTCB2016 120 A 31.57 kcmil 512 492 0.08 0.6 0.35 1
FTCB2025 150 A 49.34 kcmil 792 328 0.06 1 0.55 1
When used in parallel, the two shunts must be spaced with a minimum distance equal to the thickness of the shunt to allow air cooling.