Cut Sheet

ACCESSORIES Bonding and grounding
PH 763.422.2661nVent.com/HOFFMAN NETWORKING 2
Spec-00498 F
LAYIN LUG
Dual-rated, UL486B listed lay-in lug bonds end of cable securely to
rack. Made of electroplated 6061-T6 aluminum. Requires 3/16-in.
hex key (not included).
Bulletin: DBG
Catalog Number
For Cable
Size Range Size (in.) Size (mm)
Pkg. Qty.
DGLG #14 AWG to 2/0 1.75 x 1.50 44 x 38 10
COMPRESSION LUGS
Compression lugs terminate copper or tinned-copper conductors
for connection to busbars, cabinets, racks, and cable runway.
Color-coded by conductor size. Made of electroplated, tinned
copper. Require two screws (not included).
Bulletin: DBG
Catalog Number
Cable
Size
(#)
On-Center
Dimension
Between
Holes
Required
Screw
Size
Color
Code
Pkg.
Qty.
DGCL61 6 .625 1/4 Blue 10
DGCL62 6 1.00 3/8 Blue 10
DGCL21 2 .625 1/4 Brown 10
DGCL22 2 1.00 3/8 Brown 10
DGCL201 2/0 1.00 3/8 Black 10
DGCL402 4/0 1.00 3/8 Purple 10
HE AV Y DU T Y CTA P S
C-Taps splice two stranded or solid connectors together. Made of
copper. Require a crimping tool (not included) to correctly tighten
C-Taps around connectors.
Bulletin: DBG
Catalog Number
Conductor Run Conductor Tap
Pkg. Qty.
DGT1 #2 stranded or solid #4 stranded, #8 solid 10
DGT2 #2 stranded or solid #2 stranded or solid 10
INSULATED GROUND JUMPER KIT
Fastens across splices to provide a secure ground between sections
of ladder rack. Made of #6 AWG x 7 strand wire with green THW
insulation and two-hole compression lugs mounted on each end.
Includes fasteners.
Bulletin: DBG
Catalog Number
Conductor Type L (in.)
L (mm)
DGJ #6-7 Stranded 12.00 305
cULus requires 2 kits per splice on all painted ladder sections
RACK JUMPER KIT
Grounds rack or cabinet to common bonding network under floor
or overhead. Made of #6 AWG x 7 strand wire with green THW
insulation and two-hole compression lug mounted on one end.
Includes fasteners.
Bulletin: DBG
Catalog Number
Conductor Type Length (ft.)
Length (m)
DGRJ #6-7 stranded 9 2.7