Cut Sheet
BUSBAR DISTRIBUTION SYSTEM 60mm BusBar systems
Spec-00507 L
EQUIPMENT PROTECTIONSUBJECT TO CHANGE WITHOUT NOTICEBUSBAR SYSTEMS1
SPEC-00507
BUSBAR SYSTEM OVERVIEW
INDUSTRY STANDARDS
Fuseholders:
UL 4248 Listed; File No. E230163 and E342576
cUL Listed per CSA C22.2 No. 39; File No. E230163
CSA Certified
Busbar Components:
UL 508 Listed; File No. E123577
cUL Listed per CSA C22.2 No. 14; File No. E123577
CE
APPLICATION
Busbar systems distribute power throughout a panel by enabling
components to be mounted onto adapters that snap onto three
copper bars attached to end supports connected to the back panel.
Establishing an electrical connection and mechanically fastening
in one step, this design reduces wiring time by up to 40 percent and
allows power to be easily distributed to multiple components while
being touch-safe rated to IP20. In addition, busbar systems utilize
pre-wired adapters and sliding DIN rails, enabling components to
be placed closer together while reducing the raceway and bending
radius space required. With this arrangement, the 60-mm Busbar
System consumes up to 25 percent less panel space than traditional
wiring.
•
Distributes 3-phase power, up to 690 V, coming from a main
breaker or fuse block; can also be used for single-phase or DC
power applications
•
Convenient solution for delivering power throughout panels
containing smaller devices and fed by a 100 A or higher main
breaker
•
Provides direct mounting solutions for major component
manufacturers (ABB, Allen-Bradley, Eaton, General Electric,
Siemens, Schneider Electric)
Drawings can be found on
www.pentairprotect.com
Technical information and support can be found on Wöhner’s
website at
www.woehner.de/en
Remove the “HB” prefix from Hoffman’s catalog numbers to find the
comparable Wöhner part numbers.
AMBUS, CRITO, EQUES, J-CARRIER and QUADRON are trademarks of
Wöhner GmbH & Co. KG.
FEATURES
• The 60-mm on-center distance of the busbars minimizes the
overall footprint, allowing large ampacities to be distributed in a
small space
• Ampacity range of 0–2000 A covers most key applications
• Reduces panel wiring time by up to 40 percent versus
conventional wiring
•
Electrical and mechanical connections are completed in one step
• The design and layout are efficient and can be changed at any
time; innovative terminal solutions connect wires directly to the
busbar system; no drilling or tapping is required
• Requires up to 25 percent less panel space than conventional
wiring by eliminating some raceway and reducing bending radius
space
• Provides the highest standard of safety; designed to be touch-
safe to IP20
• Snap-together design makes planning, project design and
installation easy; fuse bases and fuse switch disconnectors are
simply “clicked” onto the busbars
• Application versatility reduces inventory requirements
• Adapts to most cabinets and enclosures; position busbars
vertically or horizontally anywhere within grid dimensions for
optimum use of space
• Add components easily to extend the panel; number of
connections is minimized
• Shielded connections reduce arc flash danger
SPECIFICATIONS
• Busbar is constructed of tinned copper for superior corrosion
resistance
ORDERING
For assistance with layouts, drawings and specifying a busbar