Datasheet
SEALED ENCLOSURE COOLING Vortex Coolers
nVent.com/HoFFmAnSUB JECT TO CHAN GE WITHO UT NOTICETHERMAL MANAGEMENT1
Spec-01032 E
VORTEX A/C ENCLOSURE COOLERS, HAZARDOUS LOCATION
VHL09, VHL15, VHL25
VHL50
INDUSTRY STANDARDS
Hazardous Location Models:
UL Classied for Class 1, Div. 2, Groups A through D; Class II,
Div. 2, Groups F & G; and Class III locations (when used with an
approved purge/pressurization system); File No. E364567.
Maintains UL/cUL Type 4, 4X when properly installed on a UL/cUL
Type 4, 4X enclosure.
APPLICATION
Hazardous Location Vortex A/C Enclosure Coolers keep enclosures
cool, clean and protect even in hazardous environments. These
systems are ideal for applications where compressed air is available
in hazardous locations. With almost no moving parts, these systems
are highly reliable and virtually maintenance free.
FEATURES
• Approved for a 175 F (80 C) maximum ambient temperature in
Class I, Div. 2; Class II, Div. 2; and Class III areas
• Built-in mechanical thermostat reduces energy consumption
• Top, side, and front mount allows for versatile installation in
conned areas
• Quieter operation with noise level of 60-75 dB
• Supplied with ve-micron, automatic drain compressed air lter,
cold ducting kit, cold air muer, and check valve
• Cooling capacities up to 5000 BTU/Hr. (1465 W)
SPECIFICATIONS
Kit includes the following items:
• Vortex Cooling Enclosure
• Enclosure pipe connections
• Air Filter
• Check Valve
• Muer with clamps
• Ducting, 10 Feet (3 Meters). More can be purchased as an
accessory.
FINISH
• Polycarbonate and stainless steel exterior with aluminum and
brass internal components
ACCESSORIES
Vortex Cooling Air Filters
Vortex Cooling Oil Filters
Vortex Cooling Generator Kits
Vortex Cooling VHL Series Air Ducting
Performance Data VHL Series for Hazardous Locations
CATALOG NUMBERS
VHL09160 VHL15160 VHL25160 VHL50160
COOLING PERFORMANCE
Cooling Capacity (BTU/Hr.) 900 1500 2500 5000
Cooling Capacity (Watts) 264 440 733 1465
Compressed Air Consumption (SCFM) 15 25 35 70
Compressed Air Consumption (SLPM) 425 708 991 1982
SOUND LEVEL
Noise Level (dB) 60 66 72 75
ENCLOSURE PROTECTION
UL Classied Class 1, Div. 2, Groups A-D; Class II, Div. 2, Groups F & G, Class III
UNIT DIMENSIONS
Height (in./mm) 8.00/203 8.00/203 8.00/203 6.44/164
Width (in./mm) 4.75/121 4.75/121 4.75/121 9.44/240
Depth (in./mm) 5.38/137 5.38/137 5.38/137 5.56/141
Weight (lb./kg) 6.70/3.04 6.7/3.04 6.8/3.08 11.4/5.17