Cut Sheet

FREE-STAND STAINLESS STEEL PREFERRED-CUTOUT DISCONNECTS PREfERRED -Cu TouT STA inlESS STEEl ovERviEW
PH 763.422.2211nVent.com/HOFFMAN DISCONNECT 4
Spec-00038 O
PREFERRED-CUTOUT OVERVIEW
APPLICATION
Enclosures having the preferred cutout are sized for use with up to
200A disconnect switches and up to 400A circuit breakers unless
otherwise specied. The preferred cutout accepts the smaller
operating handle whose mounting hole centers are 4.688 in. apart.
Preferred cutouts are standard in mild steel wall-mount enclosures,
modular enclosures and some select large mild steel enclosures.
They are also present on all standard stainless steel offerings. 400
A (or greater) disconnect switches and 600 A (or greater) circuit
breakers require the “Large” or “High Amp” cutout. This cutout
accepts the larger operating handle whose mounting hole centers
are 6.500-in. apart. This large cutout is only available on PROLINE-
DD Disconnect Packages and Type 1 Free-Stand Enclosures.
Operator adapter for preferred cutouts must be ordered separately
to be used with A21S, A28S4, A4S and WS2D enclosures. Preferred
cutouts are designed to house the following:
Allen-Bradley
Bulletin 1494U universal disconnect switches with ange-mount
handles for either variable-depth or cable-operated mechanisms
Bulletin 1494V disconnect switches with ange-mount variable-
depth operating mechanisms and Bulletin 1494V ange-mount
variable-depth operating mechanisms for circuit breakers
Bulletin 140U exible cable operating mechanisms for 140U
molded case circuit breakers
Bulletin 140G exible cable and variable-depth, ange-mount,
molded case circuit breakers
Bulletin 1494C cable-operated disconnect switches with ange-
mount handles
Bulletin 194RC cable-operated ange-mount handles for use with
the NFPA 79 compliant 194R IEC rotary disconnect switches
Allen-Bradley Bulletin 1494V-R1, -R2 and -W2 operating handles and
Allen-Bradley Bulletin 1494F disconnect devices or Bulletin 1494D
circuit breaker operators will NOT t these enclosures.
ABB Controls ange-mount variable-depth operating mechanisms
for disconnect switches and circuit breakers. Also the cable version
for circuit breakers.
Eaton Cutler-Hammer Type C361 ange-mount variable-depth
operating mechanisms with disconnect switches and Type C371
ange-mount variable-depth operating mechanisms for circuit
breakers.
General Electric Type STDA ange handles and variable-depth
operating mechanisms for disconnect switches and circuit
breakers. Also SPECTRAFLEX cable operators for circuit breakers.
Siemens ITE MAX FLEX
®
ange-mount variable-depth operating
handles for circuit breakers.
Schneider Square D
®
Class 9422 disconnect switches with ange-
mount variable-depth operating mechanisms or cable mechanisms
and Class 9422 ange-mount variable-depth operating mechanisms
or cable mechanisms for circuit breakers.
These enclosures will NOT accept Square D Class 9422 bracket-
mounted disconnect devices, Class 9422TG1 or TG2 devices.
ORDERING
Order the disconnect switch, operating handle and operating
mechanism separately. See Technical Information in the Hoffman
Specier’s Guide for wire bend space available when various
manufacturers’ disconnect switches are installed. Check the
enclosure dimension drawings to verify the chosen disconnect
switch will t in the enclosure.