PRODUCT OVERVIEW
Raychem XL-Trace is designed for pipe freeze protection and
flow maintenance in the following applications:
• Freeze protection of general water piping (aboveground
and buried)
• Freeze protection of fire sprinkler system piping, includ-
ing sprinklers
• Flow maintenance of greasy waste lines (aboveground
and buried)
• Flow maintenance of fuel lines (aboveground)
The heating element in the XL-Trace heating cable consists
of a continuous core of conductive polymer extruded
between two copper bus wires. The XL-Trace heating cable
regulates its power output in response to pipe temperature
changes. This self-regulating technology allows XL-Trace
heating cable to be overlapped or installed on plastic pipes
without overheating.
Low total installed cost
The XL-Trace heating cable’s parallel circuitry allows it to
be cut to the exact length required, with no wasted cable. Its
flexibility allows it to be wrapped around complex fittings and
valves. All of these characteristics simplify and streamline
the design of a heat-tracing system. Installation is quick and
simple.
Low total operating cost
Building operators are assured of optimal energy efficiency
and low maintenance costs when an XL-Trace system is
specified.
The same features that make an XL-Trace system easy to
install the first time also simplify additions or changes to the
system during building renovations.
For additional information, contact your Pentair Thermal
Management representative or call (800) 545-6258.
CATALOG NUMBER
5XL1-CR/CT
5XL2-CR/CT
8XL1-CR/CT
8XL2-CR/CT
12XL2-CR/CT
VOLTAGE
120 V 208–277 V 120 V 208–277 V 208–277 V
MAXIMUM OPERATING TEMPERATURE
150°F (65°C) 150°F (65°C) 150°F (65°C) 150°F (65°C) 150°F (65°C)
MAXIMUM EXPOSURE TEMPERATURE
150°F (65°C) 150°F (65°C) 150°F (65°C) 150°F (65°C) 185°F
¹
(85°C)
¹
MINIMUM INSTALLATION TEMPERATURE
0°F (–18°C) 0°F (–18°C) 0°F (–18°C) 0°F (–18°C) 0°F (–18°C)
MINIMUM BEND RADIUS
1/2 in (12 mm) 1/2 in (12 mm) 1/2 in (12 mm) 1/2 in (12 mm) 1/2 in (12 mm)
¹
When the design requires 185°F (85°C) exposure temperature, all connections must be installed off the pipe.
XL-Trace
SELF-REGULATING HEATING CABLE
For pipe freeze protection and flow maintenance
1 / 5THERMAL MANAGEMENT SOLUTIONS
EN-RaychemXLTracePipeFreezeProtection-DS-H51349 11/13