35.4.16.1 Automatic fault clearing
If the automatic fault clearing is selected (FAULTM[1:0] = 1:1), then the channels output
disabled by fault control is again enabled when the fault input signal (FAULTIN) returns
to zero and a new PWM cycle begins. See the following figure.
FTM counter
channel (n) output
(before fault control)
FAULTIN bit
channel (n) output
(after fault control with
automatic fault clearing
and POLn=0)
the beginning of new PWM cycles
FAULTF bit
FAULTF bit is cleared
The channel (n) output is after the fault control with automatic fault clearing and POLn = 0.
NOTE
Figure 35-194. Fault control with automatic fault clearing
35.4.16.2 Manual fault clearing
If the manual fault clearing is selected (FAULTM[1:0] = 0:1 or 1:0), then the channels
output disabled by fault control is again enabled when the FAULTF bit is cleared and a
new PWM cycle begins. See the following figure.
Functional description
K20 Sub-Family Reference Manual, Rev. 2, Feb 2012