2OAC SERIES Deluxe Portable Air-Cooled Spot Cooler ENGINEERING, INSTALLATION AND SERVICE MANUAL Form EISM-2OAC 01012019
TABLE OF CONTENTS GENERAL INFORMATION …................................ PRODUCT DATA AND SPECIFICATIONS............ PAGE 1 2 UNIT DESCRIPTION Standard Features.................................. 3 Applications / Operation.......................... 4 Electrical Configurations......................... 5 Use of Extension Cords…………………. 6 Condensate............................................ 7 Accessories………................................. 8 - 14 Inspection/Installation............................
GENERAL INFORMATION The OceanAire 2OAC is a portable air-cooled spot cooler designed for permanent or temporary spot cooling applications. The entire unit has been built in a premium sheet metal cabinet, equipped with heavy-duty casters for mobility. All 2OAC models come standard with a 10-foot power cord for electrical connection and added mobility in service.
2OAC SPECIFICATIONS MODEL: 2OAC 1211 1811 2412 3612 3632 3634 6012 COOLING CAPACITY 11,800 VOLTAGE (V/Phase) at 60Hz AMPS TOTAL WATTS IN-RUSH CURRENT (AMPS) PLUG TYPE EER COMPRESSOR HP COMPRESSOR RLA COMPRESSOR LRA EVAP CFM EVAP MOTOR HP CONDENSER CFM COND MOTOR HP CONDENSATE R-410A CHARGE (oz.) (A) HEIGHT (in.) (B) WIDTH (in.) (C) DEPTH (in.) NET WEIGHT (lb.) 115/1 208-230/1 208-230/3 460/3 208-230/1 208-230/3 460/3 10.4 14.1 14.9 19.6 17.2 8.7 32.0 20.4 14.
STANDARD FEATURES CABINET The 2OAC Series spot cooler has a cabinet that is constructed of 18 gauge steel with a polyester powder coated finish that will compliment any decor. The cool blue front compliments any surrounding space, and is insulated with sound-absorbing insulation for cool, quiet comfort. All units come equipped with handles and premium swivel casters for portability and convenient set-up. DELUXE ELECTRONIC CONTROLLER Each 2OAC unit is equipped with a deluxe electronic controller.
APPLICATIONS COOLING MODE—SPOT COOLER The 2OAC can be used in an open environment to cool specific objects or "spots". Spot Cooling is a convenient and economical way to provide air conditioning, where cooling the entire space is impractical. Cool air is discharged from the unit and is directed where it is needed. Nozzle kits can be used for directional cooling.
ELECTRICAL CONFIGURATION All 2OAC-Series units are equipped with a standard 10-foot long service cord with plug configurations and receptacle requirements as shown in this chart. 2OAC1211, 2OAC1811, 2OAC2412 and 2OAC3612 units come with LCDI (Leakage Current Detection & Interruption) devices that serve as a means of electrical protection. CAUTION DO NOT USE THE LCDI AS AN ON/OFF SWITCH FOR THE UNIT All 3-phase models are equipped with locking plugs for added connection reliability.
USE OF EXTENSION CORDS CAUTION FOR MODEL 2OAC1211 AN EXTENSION CORD CAN BE USED, PROVIDED IT IS RATED AT LEAST 15 AMPS @ 115 VOLTS WITH GROUNDING-TYPE ATTACHMENT PLUG AND GROUNDING TYPE CONNECTOR (LOAD FITTING) FOR MODEL 2OAC1811 AN EXTENSION CORD CAN BE USED, PROVIDED IT IS RATED AT LEAST 20 AMPS @ 115 VOLTS WITH GROUNDING-TYPE ATTACHMENT PLUG AND GROUNDING TYPE CONNECTOR (LOAD FITTING) FOR MODEL 2OAC2412 AN EXTENSION CORD CAN BE USED, PROVIDED IT IS RATED AT LEAST 20 AMPS @ 250 VOLTS WITH GROUNDING-TYPE
CONDENSATE For Models 2OAC1211, 2OAC1811, 2OAC24 and 2OAC36, a 5-gallon polyethylene tank is provided to collect condensate. The tank is located in the lower front section of the unit, and can be accessed though the condensate tank door. When the high water level is reached, a cut-out switch will AUTOMATICALLY cycle off the compressor/condenser fan.
2OAC ACCESSORIES NOTE - IT IS IMPORTANT TO SPECIFY MODEL NUMBER AND SERIAL NUMBER WHEN ORDERING ACCESSORIES CONDENSER RETURN CONDENSER DISCHARGE CEILING PANEL KIT (CK) CEILING PANEL KIT (CK-PL) NOZZLE KIT DISCHARGE DUCT ADAPTER DUCT FLANGE ROUND FLEX-DUCT (SOLD SEPARATELY) EVAPORATOR RETURN AIR PLENUM CONDENSER RETURN AIR PLENUM ROUND FLEX-DUCT (SOLD SEPARATELY) *NOTE: 2OAC36 and 2OAC60 come with 16” duct flanges.
2OAC ACCESSORIES NOZZLE KIT 2NK-1 2NK-2 2NK-3 (2 X 4-Inch) (2 X 6-Inch) (2 X 8-Inch) 2OAC12 2OAC18, 24 2OAC36, 60 EVAPORATOR RETURN AIR PLENUM DEP-10 (10-Inch Round) 2DEP-12 (12-Inch Round) DEP-16 (16-Inch Round) 2OAC12 2OAC18, 24 2OAC36, 60 DISCHARGE DUCT ADAPTER 2DDA-6 2DDA-10 2DDA-16 (6-Inch Round) (10-Inch Round) (16-Inch Round) 2OAC12 2OAC18, 24 2OAC36, 60 CONDENSATE PUMP KIT * 2DPC-1 115V Models 2DPC-2 230V Models * Not Required for 2OAC60’s CEILING PANEL KIT (Includes Panel, Duct, Strap and
ACCESSORIES CEILING PANEL DUCT KIT 2 x 2 CEILING DUCT-PANEL A ceiling panel kit is available for discharging the condenser air above a drop ceiling. The ceiling panel duct kits are furnished with a white vinyl coated flexible duct that allows for convenient installation. A 2ft X 2ft ceiling duct- panel is included to replace a 2ft X 2ft drop-ceiling panel where the connection is desired. VINYL COATED FABRIC DUCT The CK-12 is available for 2OAC12, 18, and 24.
ACCESSORIES DISCHARGE AIR NOZZLE KIT ASSEMBLY The optional discharge nozzle kits are used to direct the conditioned air to a specific target area. By concentrating the airflow, the nozzles increase the air velocity towards production lines to cool personnel and/or equipment. In server rooms, the nozzles can be used to direct the airflow through the rack, and remove the hot air from the equipment area.
ACCESSORIES CONDENSER RETURN AIR PLENUM Condenser return air plenums are available for installations where it is required to duct air to the inlet of the condenser. The plenum easily fits into place on the back of the unit, and is provided with a flange for connecting 12-inch or 16-inch flexible ducting. A condenser return air plenum can substantially reduce air noise and allow the unit to operate without drawing condenser air from the conditioned space.
ACCESSORIES EVAPORATOR RETURN AIR PLENUM Evaporator return air plenums are available for installations where it is required to duct air to the inlet of the evaporator. The evaporator return air plenums allow the user to connect round duct (flexible or rigid) to the return air intake to reduce air noise and increase the number of options for solving difficult application problems. The plenum attaches to the front of the unit, replacing the return air grille.
ACCESSORIES DISCHARGE DUCT ADAPTER Discharge duct adapters are available for applications where ducted evaporator discharge is required. The adapters can be easily installed on the unit without fasteners, and can be used for either vertical or horizontal ducting. The standard discharge grille is removed and the 2DDA is attached in the grille opening. 2DDA-6 for model 2OAC12, converts the evaporator discharge to a 6-inch diameter round duct.
INSTALLATION INSTRUCTIONS RECEIVING—INSPECTION Upon receiving your 2OAC unit, inspect the packaging for any damage. All units are shipped on a skid, and packaged in a triple-wall carton for added protection. BEFORE INSTALLING Check the unit for any damage. All OceanAire products are thoroughly inspected at the factory and carefully packaged. If any damage is evident, contact OceanAire IMMEDIATELY.
DELUXE ELECTRONIC CONTROLLER The 2OAC controller is equipped with many features for a more precise level of cooling and operation. Additionally, the controller can be removed from the unit and installed for remote operation, if needed (accessory parts may be required). POWER button OCEANAIRE DELUXE ELECTRONIC CONTROLLER When power is connected, the controller will display “888” momentarily, and will then disappear. Press the POWER button, then press the TEMP SELECT button until the SET POINT is displayed.
FAN SPEED—The operator can select between AUTO or MANUAL fan speed con- trol. Pressing the FAN SPEED button, will switch speed from AUTO to MANUAL. In MANUAL mode, pressing the FAN SPEED button will change fan speed from low to high. In AUTO mode, the fan speed is controlled automatically. In cooling mode, the controller automatically adjusts the fan speed to high, and as the inside temperature approaches the set point, the fan speed will reduce.
2OAC PROGRAM SETTINGS MODEL CODE SETTINGS 2OAC12 P1 = 65, P2 = 45 2OAC18 P1 = 80, P2 = 50 2OAC24 P1 = 70, P2 = 50 2OAC36 P1 = 85, P2 = 40 2OAC60 P1 = 85, P2 = 45 NOTICE Program Parameters are NOT controller default values.
REPLACEMENT PARTS PROCEDURE IT IS RECOMMENDED THAT ALL OCEANAIRE UNITS BE SERVICED BY A LICENSED TECHNICIAN WARNING—TO AVOID INJURY, DISCONNECT UNIT POWER PRIOR TO SERVICING A. FAN MOTORS 1. Remove cabinet's left-side panel (when looking at the front of the unit). 2. Evaporator fan motor—disconnect evaporator motor wires from evaporator fan contactor and power module. Condenser fan motor—disconnect condenser motor wires from condenser fan contactor. 3.
TROUBLESHOOTING GUIDE The following steps and procedures are recommended for correcting the problems indicated. In the event that the problem can not be corrected, service may be required. SERVICE SHOULD BE PERFORMED BY A QUALIFIED AIR CONDITIONING SERVICE TECHNICIAN PROBLEM: UNIT DOES NOT POWER UP CAUSE: Power interruption REMEDY: Check LCDI (on models with LCDI), and reset LCDI. Check external power supply making sure that the disconnect is ON. Check for blown fuses or tripped circuit breakers.
PREVENTIVE MAINTENANCE 2OAC Spot Coolers are designed to last a long time and to give maximum performance and reliability with minimum maintenance. To prolong the life of the unit, regular maintenance must be performed as specified below: BLOWER MOTORS The motors on all units have permanently lubricated bearings. No oiling is necessary FILTERS A clogged filter will cause the unit to operate at greatly reduced efficiencies.
2OAC12 INTERIOR VIEW Outdoor Blower/Motor Filter/Drier Indoor Blower/Motor Cool Display Evaporator Coil Condenser Coil Display Cable Control Box Condensate Tank 22
PIPING SCHEMATIC 23
WIRING SCHEMATIC FOR 2OAC1211, 1811 and 2412 CONDENSATE TANK FULL SWITCH DISCHARGE TEMP SENSOR COM OCEANAIRE NO NC POWER MODULE OPTIONAL CONDENSATE PUMP 2DPC-1 (115V) OR 2DPC-2 (208-230V) INSTALL SAFETY SWITCH IN LOW-VOLTAGE LOOP REPLACING TANK FULL SWITCH AIR-COOLED SPOT COOLER MODELS 2OAC1211, 2OAC1811 115 V / SINGLE-PHASE MODELS 2OAC2412 208-230 V / SINGLE-PHASE 24
WIRING SCHEMATIC FOR 2OAC3612 DISCHARGE TEMP SENSOR CONDENSATE TANK FULL SWITCH COM OCEANAIRE NO NC POWER MODULE Plug 6-30P OPTIONAL CONDENSATE PUMP KIT 2DPC-2 (208-230V) INSTALL SAFETY SWITCH IN LOW-VOLTAGE LOOP REPLACING CONDENSATE TANK FULL AIR-COOLED SPOT COOLER MODELS 2OAC3612 208-230 V/ SINGLE-PHASE 25
WIRING SCHEMATIC FOR 2OAC6012 DISCHARGE TEMP SENSOR OCEANAIRE POWER MODULE AIR-COOLED SPOT COOLER MODELS 2OAC6012 208-230 VOLT/ SINGLE-PHASE Plug 6-50P 26
THREE PHASE MONITOR Three-Phase units are equipped with monitors for motor protetion. The OceanAire Three-phase Monitor safeguards the unit against incorrect compressor rotation, low-voltage and/or loss of power in any one of the power legs. The monitor is installed in the control box and is equipped with an LED for diagnosis of an improper electrical condition (see diagrams below). When power is connected, the compressor WILL NOT engage until the monitor start delay has timed out.
WIRING SCHEMATIC FOR 2OAC3632 DISCHARGE TEMP SENSOR CONDENSATE TANK FULL SWITCH COM OCEANAIRE NO NC POWER MODULE Plug L15-30P OPTIONAL CONDENSATE PUMP 2DPC-2 (208-230V) INSTALL SAFETY SWITCH IN LOW-VOLTAGE LOOP REPLACING TANK FULL SWITCH AIR-COOLED SPOT COOLER MODELS 2OAC3632 208-230 V / 3-PHASE 28
WIRING SCHEMATIC FOR 2OAC3634 CONDENSATE TANK FULL SWITCH DISCHARGE TEMP SENSOR COM OCEANAIRE NC POWER MODULE Plug L16-20P AIR-COOLED SPOT COOLER MODELS 2OAC3634 460 V / 3-PHASE NO OPTIONAL CONDENSATE PUMP 2DPC-2 (208-230V) INSTALL SAFETY SWITCH IN LOW-VOLTAGE LOOP REPLACING TANK FULL SWITCH 29
WIRING SCHEMATIC FOR 2OAC6032 DISCHARGE TEMP SENSOR OCEANAIRE POWER MODULE Plug L15-30P AIR-COOLED SPOT COOLER MODEL 2OAC6032 208-230 V / 3-PHASE 30
WIRING SCHEMATIC FOR 2OAC6034 DISCHARGE TEMP SENSOR OCEANAIRE POWER MODULE Plug L16-20P AIR-COOLED SPOT COOLER MODELS 2OAC6034 460 V / 3-PHASE 31
LIMITED WARRANTY The Manufacturer (OceanAire, Inc.) warrants to the original owner that the Product will be free from defects in material or workmanship for a period not to exceed one (1) year from date of installation. If upon examination by the Manufacturer, the Product is shown to have a defect in material or workmanship during the warranty period, the Manufacturer will repair or replace, at its option, that part of the Product which is shown to be defective.
TECH NOTES 33
END USER INFORMATION MODEL: ______________________________________ SERIAL NUMBER: _____________________________ Date Purchased: ______________________________ Purchased from: _______________________________ Date Installed: _________________________________ For Technical Support or service parts, contact our Keep Cool Team at 847-583-0311 In order to receive the benefits of our warranty, please register on-line at www.oceanaire-inc.