AIR BOSS Portable Air-Cooled Spot Cooler ENGINEERING, INSTALLATION AND SERVICE MANUAL PAC60 R410A Models PAC12
TABLE OF CONENTS PAGE GENERAL DESCRIPTION …................................. 1 PRODUCT DATA AND SPECIFICATIONS............ 2 UNIT DESCRIPTION Standard Features.................................. 3 Applications / Operation.......................... 4 Electrical.................................................. 5 Condensate............................................. 6 Accessories………................................... 7 - 13 Installation................................................
GENERAL DESCRIPTION The Oceanaire AIRBOSS is a portable air-cooled spot cooler designed for permanent or temporary cooling applications. The entire air conditioning unit has been built in an attractive sheet metal cabinet, equipped with heavy -duty casters for mobility. All Air Boss models come with a 10-foot power cord for electrical connection and added mobility in service.
AirBoss SPECIFICATIONS Deluxe Air-Cooled Portable Air Conditioners MODEL: PAC Cooling Capacity 1 1211 1811 2412 11,800 Voltage (V/Phase) at 60Hz 16,800 115/1 24,020 3612 3632 3634 6012 6032 6034 36,050 36,050 36,050 60,050 60,050 60,050 208-230/1 208-230/1 208-230/3 460/3 208-230/1 208-230/3 460/3 Cooling Amps 6 10.4 14.1 14.9 32.0 6 1180 1670 2700 3620 3620 3620 6000 6000 6000 In Rush Current (Amps) 77.5 100.
STANDARD FEATURES CABINET The AirBoss Series cabinet is constructed of 18 gauge steel with a gray polyester powder coated finish that will compliment any decor. The entire cabinet is insulated with a soundabsorbing insulation for cool, quiet comfort. All units come equipped with handles and swivel casters for portability and convenient set-up. ELECTRONIC THERMOSTAT All Air Boss unit are equipped with a non-programmable electronic thermostat.
APPLICATIONS SPOT COOLER The Air Boss can be used in an open environment to cool specific objects or "spots". Spot Cooling is a convenient and economical way to provide air conditioning where cooling the entire space is impractical. Cool air is discharged from the unit and is directed where it is needed. Nozzle kits can be used to improve direction of the cooling airflow.
SERVICE CORD All AirBoss Series units are equipped with the standard ten foot long service cord with plug configurations and receptacle requirements as shown in this chart. PAC1211, PAC1811, PAC2412 and PAC3612 units come with LCDI (Leakage Current Detection & Interruption) devices that serve as a means of electrical protection. CAUTION—DO NOT USE THE LCDI AS AN ON/OFF SWITCH FOR THE UNIT All 3-phase models are equipped with locking plugs for added connection reliability.
CONDENSATE RESERVOIR TANK For Air Boss Models PAC12, PAC18, PAC24 and PAC36, a 5-gallon polyethylene tank is provided standard, to collect condensate. The tank is located in the lower, front section of the unit. A high water level cut-out switch is used to stop the compressor and condenser fan automatically when the tank's pre-set water level has been reached. The evaporator fan will continue to run, circulating air.
ACCESSORIES CK-12 CK-16 CK-12PL (2 Req’d for 2DCP-4 2DDA-6 2DDA-10 2DDA-16 2NK-1 2NK-2 2NK-3 DEP-10 2DEP-12 DEP-16 2DCP-1 2DCP-2 2DCP-4 AIR BOSS UNIT 7
PAC – AIR BOSS ACCESSORIES NOZZLE KIT 2NK-1 (2 X 4-Inch) 2NK-2 (2 X 6-Inch) 2NK-3 (2 X 8-Inch) PAC12 PAC18, 24 PAC36, 60 EVAPORATOR RETURN AIR PLENUM DEP-10 (10-Inch Round) PAC12 2DEP-12 (12-Inch Round) PAC18, 24 DEP-16 (16-Inch Round) PAC36, 60 DISCHARGE DUCT ADAPTER 2DDA-6 (6-Inch Round) PAC12 2DDA-10 (10-Inch Round) PAC18, 24 DDA-16 (16-Inch Round) PAC36, 60 CONDENSATE PUMP KIT * PC-1P 115V Models PC-2P 230V Models * Not Required for PAC60’s CEILING PANEL KIT CK-12 PAC12, 18, 24 CK-16 PAC36, 60 CK-1
ACCESSORIES 2 x 2 CEILING DUCT-PANEL CEILING PANEL DUCT KIT, CK-12, CK-16 A ceiling panel kit is available for discharging the condenser air above a drop ceiling.. The ceiling panel duct kits are furnished with a white vinyl coated flexible duct that allows for convenient installation. A 2ft X 2ft ceiling duct- panel is included to replace a 2ft X 2ft drop-ceiling panel where the connection is desired. VINYL COATED FABRIC DUCT DUCT STRAP The CK-12 is available for all Air Boss models except the 5-ton.
ACCESSORIES DISCHARGE AIR NOZZLE KIT ASSEMBLY (2NK) The optional discharge nozzle kits are used to direct the conditioned air to a specific target area. By concentrating the airflow, the nozzles increase the air velocity towards production lines to cool personnel or equipment. In server rooms, the nozzles can be used to induce airflow through the rack to remove the hot air from the area of the equipment.
ACCESSORIES CONDENSER RETURN AIR PLENUM, 2DCP Condenser return air plenums are available for installations where it is required to duct air to the inlet of the condenser. The plenum easily attaches with one screw to the back of the unit, and is provided with flange(s) for connecting 12-inch flexible ducting. A condenser return air plenums can substantially reduce air noise and allows the unit to operate without drawing condenser air from the conditioned space.
ACCESSORIES EVAPORATOR RETURN AIR PLENUM, DEP Evaporator return air plenums are available for installations where it is required to duct air to the inlet of the evaporator. The evaporator return air plenums allow the user to connect round duct (flexible or rigid) to the return air intake to reduce air noise and increase the number of options for solving difficult cooling problems. The plenum attaches to the front of the unit, replacing the return air grill.
ACCESSORIES Discharge Duct Adapter, 2DDA AND DDA Discharge duct adapters are available for applications where ducted evaporator discharge is required. The adapters can be easily installed on the unit without fasteners, and be installed for either vertical or horizontal ducting. The standard discharge grille is removed and the DDA is attached in the grill opening. 2DDA-6 for PAC1211, converts the evaporator discharge to a 6-inch diameter round duct.
INSTALLATION INSTRUCTIONS RECEIVING—INSPECTION: Upon receiving your Air Boss unit, inspect the packaging for any damage. All units are shipped on a skid, and packaged in a triple-wall carton for added protection. In shipment, some wear may occur on the packaging. If the packaging is heavily damaged or broken, file a claim with the freight company immediately. Carefully unpack the unit and remove all wrapping materials. Save all documentation and fill out the Warranty Card and mail it to Oceanaire.
THERMOSTAT OPERATION FAN When the power is connected, the LCD screen on the thermostat will illuminate. Pressing the FAN button once, will turn on the evaporator fan blower. To turn the blower off, push the FAN button once again. COOLING MODE Ä To operate unit for cooling, push MODE button to display COOL in the window. Push down arrow button multiple times to lower set point to desired temperature.
REPLACEMENT PROCEDURE FOR PARTS IT IS RECOMMENDED THAT ALL OCEANAIRE UNITS BE SERVICED BY A LICENSED TECHNICIAN WARNING—TO AVOID INJURY, DISCONNECT UNIT POWER PRIOR TO SERVICING A. FAN MOTORS 1. Remove cabinet's left-side panel (when looking at the front of the unit). 2. Evaporator fan motor—disconnect evaporator motor wires from evaporator fan contactor and fan speed rocker switch. Condenser fan motor—disconnect condenser motor wires from condenser fan contactor. 3.
TROUBLESHOOTING GUIDE The following steps and procedures are recommended for correcting the problems indicated. In the event that the problem can not be corrected, service may be required. SERVICE SHOULD BE PERFORMED BY A QUALIFIED AIR CONDITIONING SERVICE TECHNICIAN PROBLEM: UNIT DOES NOT POWER UP CAUSE: Power interruption REMEDY: Check LCDI (on models with LCDI), and reset LCDI. Check external power supply making sure that the disconnect is ON. Check for blown fuses or tripped circuit breakers.
PREVENTIVE MAINTENANCE AirBoss Spot Coolers are designed to last a long time and to give maximum performance and reliability with minimum maintenance. To prolong the life of the unit, regular maintenance must be performed as specified below: BLOWER MOTORS The motors on all units have permanently lubricated bearings. No oiling is necessary FILTERS A clogged filter will cause the unit to operate at greatly reduced efficiencies.
PAC INTERIOR Evaporator Blower Motor Capacitors High Pressure Switch Condenser Blower Evaporator Coil Condenser Coil Capillary tube Evaporator Drain Pan Strainer Control Box Condensate Tank Casters Condensate Tank Tray Water Level Detection Control 19
SUCTION LINE EVAPORATOR BLOWER AIR EVAPOTATOR COIL CAPILLARY TUBES CONDENSER BLOWER HP RESET CONDENSER COIL ACCESS VALVES FILTER/ DRIER DISCHARGE LINE COMPRESSOR REFRIGERANT FLOW PIPING SCHEMATIC Air-Cooled Spot Cooler 20 AIR
OCEANAIRE CONDENSATE TANK FULL SWITCH NO COM NC OPTIONAL CONDENSATE PUMP KIT PC-1P (115V) OR PC-2P (208-230V) INSTALL SAFETY SWITCH IN LOWVOLTAGE LOOP REPLACING CONDENSATE TANK FULL SWITCH 21
OCEANAIRE www.oceanaire-inc.
OCEANAIRE www.oceanaire-inc.
24
OCEANAIRE www.oceanaire-inc.
OCEANAIRE www.oceanaire-inc.
USE OF EXTENSION CORDS CAUTION: FOR MODEL PAC1211 AN EXTENSION CORD CAN BE USED PROVIDED IT IS RATED AT LEAST 15 AMPS @ 115 VOLTS WITH GROUNDING-TYPE ATTACHMENT PLUG AND GROUNDING TYPE CONNECTOR (LOAD FITTING) FOR MODEL PAC1811 AN EXTENSION CORD CAN BE USED PROVIDED IT IS RATED AT LEAST 20 AMPS @ 115 VOLTS WITH GROUNDING-TYPE ATTACHMENT PLUG AND GROUNDING TYPE CONNECTOR (LOAD FITTING) FOR MODEL PAC2412 AN EXTENSION CORD CAN BE USED PROVIDED IT IS RATED AT LEAST 20 AMPS @ 250 VOLTS WITH GROUNDING-TYPE ATTACH
Three Phase Monitor Three-Phase units can be equipped with monitors for motor protection. The Oceanaire Three-phase Monitor safeguards the unit against incorrect compressor rotation, low-voltage and/or loss of power in any one of the power legs. The monitor is installed in the control box and is equipped with an LED for diagnosis of an improper electrical condition (see diagrams below). When power is connected, the thermostat WILL NOT power up, until the monitor start delay has been timed out.
MANUFACTURER’S LIMITED WARRANTY The Manufacturer (OceanAire, Inc.) warrants to the original owner that the Product will be free from defects in material or workmanship for a period not to exceed one (1) year from date of installation. If upon examination by the Manufacturer the Product is shown to have a defect in material or workmanship, during the warranty period, the manufacturer will repair or replace, at its option, that part of the Product which is shown to be defective.
USEFUL INFORMATION MODEL: SERIAL NUMBER: DATE PURCHASED: INSTALLED BY: For Technical Support, or to locate a distributor for service parts, contact Oceanaire at (847) 583-0311. Please indicate the Model Number and Serial Number of the unit to assure proper information and service parts.