Operation Manual

DISPLAY
DAT/H2O
ALT AIR
FREON
JP
5
JP
6
COMP
FAN
JP
3
VA LV E
JP
2
COMP
RUN
COMP
COM
PUMP
PUMP
L-2
VA LV E
L-1
AC
L-1
AC
L-2
FAN
L-2
FAN
L-1
HIGH PRESSURE SWITCH
T1
T2
T3
L3
L2
L1
T1
T2
T3
230 VOLT
CONDENSER
FAN
MOTOR
230 VOLT
EVAPORATOR
FAN
MOTOR
230 VOLT
CONDENSATE
PUMP
S. SW
460 VOLT
COMPRESSOR
2KVA
230 VOLT
460 VOLT
TRANSFORMER
L3
L2
L1
G
COMPRESSOR
CONTACTOR
Oceanaire, Inc.
AIR-COOLED COOLING ONLY
MODELS 2OAC6034
460 VOLT 3 PHASE
Model is factory
equipped with a condensate
pump. A condensate bucket is not
an option.
2OAC6034
NOTE:
TO CORRECT THIS:
Compressor has only one
proper rotation direction. If
compressor is unusually noisy and
does not cool, it may be running
backwards. This is not unusual for
3 phase equipment.
Unplug power cord from outlet,
remove side panel at electrical box
and reverse any two of the power
leads on the compressor contactor.
Example, move L1 wire to L2.
And move L2 wire to L1. Re-
install side panel, plug unit in and
re-start.
Plug for 2OACH6034 L16-30P
HIGH
HIGH
LOW
RUN
CAP
RUN
CAP
62K 3Watt
NC
NO
COM
Wireoac6034
X
X X X
X X X
X X
28
ArcticAire