Installation Guide
 Page 16 
Note on Pipe Length
The length of refrigerant piping will affect the performance and energy efficiency of the unit. Nominal 
efficiency is tested on units with a pipe length of 16.5ft (5 meters).
In North America, the standard pipe 
length is 25ft (7.5m)
. A minimum pipe run of 9.8 ft is required to minimize vibration & excessive noise.
Connection Instructions – 
Refrigerant Piping
Step 1: Cut pipes
When preparing refrigerant pipes, take extra 
care to cut and flare them properly. This will 
ensure efficient operation and minimize the 
need for future maintenance. 
1. Measure the distance between the indoor 
 and outdoor units. 
Refer to the table below for specifications on the maximum length and drop height of piping.
When connecting refrigerant piping,  do not
 let substances or gases other than the specified 
refrigerant enter the unit. The presence of other gases or substances will lower the unit’s capacity, 
and can cause abnormally high pressure in the refrigeration cycle. This can cause explosion and
injury. 
2.
Using a pipe cutter, cut the pipe a little longer 
than the measured distance.
3.
Make sure that the pipe is cut at a perfect 90° 
angle. 
Rough
90°
 DO NOT DEFORM PIPE 
 WHILE CUTTING
Be extra careful not to damage, dent, or 
deform the pipe while cutting. This will 
drastically reduce the heating efficiency 
 of the unit.
Maximum Length and Drop Height of Refrigerant Piping per Unit Model
Model Capacity (BTU/h) Max. Length, ft (m) Max. Drop Height,ft (m)
R410A Inverter Split
Air Conditioner
< 15,000 82 ft (25 m) 33 ft (10 m)
 15,000 and < 24,000 98.5 ft (30 m) 66 ft (20 m)
 24,000 and < 36,000 164 ft (50 m) 82 ft (25 m)
Refrigerant Piping Connection 










