Installation Manual
Page 16
Note on Pipe Length
The length of refrigerant piping will affect the performance and energy efficiency of the unit. Nominal
efficiency is tested on units with a pipe length of 16.5ft (5 meters).
In North America, the standard pipe
length is 25ft (7.5m)
. A minimum pipe run of 9.8 ft is required to minimize vibration & excessive noise.
Connection Instructions –
Refrigerant Piping
Step 1: Cut pipes
When preparing refrigerant pipes, take extra
care to cut and flare them properly. This will
ensure efficient operation and minimize the
need for future maintenance.
1. Measure the distance between the indoor
and outdoor units.
Refer to the table below for specifications on the maximum length and drop height of piping.
When connecting refrigerant piping, do not
let substances or gases other than the specified
refrigerant enter the unit. The presence of other gases or substances will lower the unit’s capacity,
and can cause abnormally high pressure in the refrigeration cycle. This can cause explosion and
injury.
2.
Using a pipe cutter, cut the pipe a little longer
than the measured distance.
3.
Make sure that the pipe is cut at a perfect 90°
angle.
Rough
90°
DO NOT DEFORM PIPE
WHILE CUTTING
Be extra careful not to damage, dent, or
deform the pipe while cutting. This will
drastically reduce the heating efficiency
of the unit.
Maximum Length and Drop Height of Refrigerant Piping per Unit Model
Model Capacity (BTU/h) Max. Length, ft (m) Max. Drop Height,ft (m)
R410A Inverter Split
Air Conditioner
< 15,000 82 ft (25 m) 33 ft (10 m)
15,000 and < 24,000 98.5 ft (30 m) 66 ft (20 m)
24,000 and < 36,000 164 ft (50 m) 82 ft (25 m)