Oxygen Equipment User Manual

 Page 15 
  5.6   Temperature  
5.6.1  The temperature of the process can be read at any time by entering the menu and 
calling for TEMPERATURE. Either °C or °F will be indicated depending on the 
position of DIP switch No. 1. Bank S1. See Section 4.8. 
5.6.2  The 0-5 Vdc and 0-1 mA analog outputs can be dedicated to follow the process 
temperature by simply placing DIP switch No. 8 in the off position. The temperature 
span of the output is set to the utility menu. See Section 4.8 and 7.4.   
  5.7 Status 
5.7.1  The DOCN600 continuously checks the integrity of all stored data and monitors the 
condition of the measuring system. If a fault is detected, the FAIL LED above the 
display will turn red. The STATUS in the operation menu will provide a numerical 
code, giving a possible cause and a suggested remedy. 
5.7.2  The following table shows the display codes, causes and remedies:   
 Code
 Possible Cause Suggested Remedy 
  0  Normal Condition  No action required 
  1  Reserved   
  2  Temperature Sensor off Scale  Verify process. Check for open or short 
     connections. 
  3  D.O. reading off Scale  Verify process. Check for open or short 
       connections. 
  4*  Memory Loss  Call your OMEGA Rep. Or OMEGA 
       directly 
 5  Reserved   
  6  Sensor Fault  Check probe membrane for perforation 
  7  Factory Setting in force, as a  Perform procedure according to Section 9.2 
      result of the ESCAPE procedure 
  NOTE: Code 4 could be a serious failure so the alarm relay will energize in addition to the red 
illumination of the FAIL LED, if DIP switch 5 Bank S1 is OFF. 
    5.8 Relay A Setpoint 
5.8.1  As shipped from the factory, Relay A is configured to control decreasing D.O. 
However, you may change the direction of control by changing the position of DIP 
switch 4 Bank S1. Please refer to Section 4.8. 










