Page 8  Combustion Research Corporation 
SUSPENSION 
 WARNING 
COLLAPSE, FIRE AND EXPLOSION HAZARD 
Improper suspension of the tube heater may result in 
collapse and being crushed. Always suspend from a 
permanent and secure part of the building structure 
that can evenly support the total force and weight of 
entire the heating system. 
Failure to maintain minimum clearance to 
combustibles may result in fire and/or explosion, 
property damage, serious injury or death. Always 
maintain minimum clearances and post clearance 
signs where needed. 
Combustion Research Corporation recommends that 
Omega II 
®
 systems are hung by means of chain. Chain 
and “S” hooks are supplied as an option. DO NOT 
STRETCH OR INSTALL CHAIN OTHER THAN IN A 
VERTICAL FASHION WHEN INITIALLY INSTALLED 
(BURNER NOT FIRING). 
If chain is not supplied by Combustion Research Corp., 
furnish a chain with a minimum 90 lb. workload (trade size 
#3 or larger). A minimum of 12" (30 cm) of hanging chain is 
recommended. This allows for system expansion and 
contraction, reducing the likelihood of reflector and radiant 
tube warping and/or expansion noise. 
CAUTION: Infrared tube systems expand and contract 
upon each call for heat. System expansion of up to 4” can 
be expected. 
Provisions must be made to limit lateral movement when 
systems are installed in site conditions where open doors 
may create a wind condition – see page 8 for guidelines. 
Radiant tubes DO NOT require sloping. 
For fine adjustment turnbuckles may be used. 
NOTES: 
  SECURE TURNBUCKLES SO THAT THEY WILL NOT 
UNWIND OR UN-SCREW.
  CRIMP "S" HOOKS CLOSED BEFORE LEAVING JOB. 
REFLECTORS ARE NOT TO BE INSTALLED ON TOP OF 
COMBINATION HANGER 
Beam Clamp 
Threaded Rod
and Turn Buckle
Secure turnbuckle 
with JAM nu
t
s or wire 
to prevent unwinding 
Chain 
Bar Clamp
Beam Clamp 
Chain 
Chain
Beam 
Wood Beam 
Concrete 
Beam 
Eye Bolt Screw 
with Washer and 
Locknut 
Suitable Expansion 
Anchor 
All ”S” Hooks MUST Be 
Manually Closed By 
Installer 
Chain 
! 