Specification Sheet

REVISED – March 24, 2006 submitom-SS.doc (2/19/07)
THERMOSTAT FEATURES
Thermostat connects to standard 2" x 4" electrical
single gang box.
Single pole.
Underwriter's Laboratories (UL) listed for the U.S. &
Canada.
Vertical mounting on 2" x 4" single gang outlet box.
Color-coded lead wire connections.
Dial with temperature in Fahrenheit, 50° F to 90° F
temperature range.
Multiple burners can be controlled by one
thermostat.
SPECIFICATIONS
CRC Part No.:
5484.00 - Heating only (Wt. – 0.5 Lbs., 0.23 kg)
Dimensions:
4-1/2" (114 mm) x 2-3/4" (70mm)
Mounting:
NEMA single gang box (2-9/32" (83 mm) screw
centers.
Control Range:
50°F (10°C) to 90°F (32°C)
Electrical Ratings:
50-60Hz 120 VAC
Full Load 9.0 AMP
Resistive 22 AMP
Note: This thermostat is also suitable for 24 VAC
operation.
Wiring:
INSTALLATION & CHECKOUT
MOUNTING
Position thermostat on inside wall about 5" (1.5m)
above floor, mounted on 2" x 4" vertical electrical
outlet box. A 4" square junction box requires a mud
ring adapter (not provided). Do not mount thermostat
where it can be affected by drafts, direct radiant heat
from the heater as well as the sun or other sources of
heating or cooling.
Wire as shown in figure 1.
Remove cover by pulling out at the bottom. Install
thermostat by screwing base to electrical box. DO
NOT press on the bimetal sensor or set point knob to
seat the thermostat to the electrical box - thermostat
will be damaged.
SETTING AND CHECKOUT
Turn on power. Raise the temperature setting to
energize the heating load. The heater will turn on.
The heater will turn off when the temperature rises to
the set point.
Lower the temperature setting to lowest setting to de-
energize the heating load. The heater will turn off
THERMOSTAT
Infrared
Heater
L1 L2
Figure 1
70
50 90
80
60
COMBUSTION
RESEARCH
CORPORATION
Part No. 5484.00 Thermostat
Line Voltage Wall Thermostat