User’s Guide Flash Archive http://192.168.1.200 Input 1: 122 67.8 Flash Archive SP1_L(below)=044.5 F F SP1_H (above)=090.0 F Archives_Done Input 2: 77.7 Shop on line at 122 ® omega.com e-mail: info@omega.com For Latest Product Manuals omegamanual.info ® 9.0/Div 32 9.
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its products to the European New Approach Directives. OMEGA will add the CE mark to every appropriate device upon certification. The information contained in this document is believed to be correct, but OMEGA Engineering, Inc. accepts no liability for any errors it contains, and reserves the right to alter specifications without notice.
TABLE OF CONTENTS Part 1: Introduction 1.1 Safety and EMC Considerations........................................................................2 1.2 Before You Begin ................................................................................................2 1.3 Description ..........................................................................................................2 Part 2: Hardware 2.1 Wall Mounting .......................................................................................
LIST OF FIGURES: Figure 1.1 Figure 2.1 Figure 2.2 Figure 2.3 Figure 2.4 Figure 2.5 Figure 2.6 Figure 2.7 Figure 2.8 Figure 2.9 Figure 2.10 Figure 3.1 Figure 3.2 Figure 3.3 Figure 4.1 Figure 4.2 Figure 4.3 Figure 4.4 Figure 4.5 Figure 4.6 Figure 4.7 Figure 4.8 Figure 4.9 Figure 4.10 Figure 4.11 Figure 4.12 Figure 4.13 Figure 4.14 Figure 4.15 Figure 4.16 Figure 4.17 Figure 4.18 Figure 4.19 iSE and iLD Big Display on the Ethernet Network ..............................4 Mounting ..............................
NOTES, WARNINGS and CAUTIONS Information that is especially important to note is identified by the following labels: • NOTE • WARNING or CAUTION • IMPORTANT • TIP NOTE: Provides you with information that is important to successfully setup and use the iSE. CAUTION: Tells you about the risk of electrical shock. CAUTION: Risk of danger. Tells you of circumstances or practices that can effect the instrument’s functionality and must refer to accompanying documents. TIP: Provides you helpful hints.
PART 1 INTRODUCTION 1.1 Safety and EMC Considerations Refer to the CE Approvals Section. EMC Considerations • Whenever EMC is an issue, always use shielded cables. • Never run signal and power wires in the same conduit. • Use twisted-pair wires for signal connections. • Install Ferrite Bead(s) on signal wires close to the instrument if EMC problems persist. Failure to follow all instructions and warnings may result in injury! 1.
LOCAL ALARMS -- The iSE includes two 1.5 Amp output relays that are controlled by the alarm conditions you select. The relays can trigger flashing lights and a siren for example to alert personnel near the scene. With the easy Web-based setup page, the two relays can be programmed for two temperature inputs, and high or low set points, as well as alarm conditions triggered by contact closures.
TYPICAL APPLICATIONS -- The iSE is great for monitoring and recording temperature in applications such as: clean rooms, computer rooms, HVAC systems, pharmaceutical and food processing and storage, hospitals, laboratories, semiconductor fabs, electronic assembly, warehousing, museums, manufacturing, greenhouses, farm animal shelters, and many more. The following example illustrates how you can hookup an iSE, a network display (iLD), and a network camera to your network: Figure 1.
PART 2 HARDWARE 2.1 Wall Mounting Position unit where required. Mark and drill the two #4 screw holes. After bracket is mounted on the wall, align back of unit over the three bracket clips, once engaged, slide downward, the unit will snap in place. For extra security, you may screw the unit onto the bracket. Remove cover (see Section 2.4) and screw a #4 x 1/4” long self-tapping screw through the case and bracket. DRILL 0.125 [3.
2.2 DIP Switches The iSE is shipped with all DIP switches in "OFF" position. DIP Switch Usage 1) N/C - not used 2) To change to default factory settings 3) To enable/disable DHCP 4) N/C - not used Figure 2.3 DIP Switch Location To set the iSE to factory default settings, slide DIP switch #2 to ON position. Power the iSE on and wait about 10 seconds until the iSE fully boots up.
2.3 Parts of the iSE Unit Figure 2.4 Parts of the iSE Unit Table 2.1 Parts of iSE Unit ETHERNET RESET ACTIVITY NET LINK RJ45 interface for 10BASE-T connection. Button: Used for power reseting the iSE. LED (Red) Blinking: Indicates network activities (receiving or sending packets). LED (Green) Solid: Indicates good network link. DIAGNOSTICS LED (Yellow) Blinking: Indicates transmitting data from iSE to flash memory card. When DHCP enabled, it remains solid until DHCP IP address is received.
2.4 Disassembly Instruction You will need to open the unit for one of the following reasons: • To wire relay and I/O contact connectors. (Refer to Section 2.6). • To connect or replace the battery. (Refer to Section 2.7). • To change S5 jumper. In the absence of AC power, and if S5 is installed, the LCD Backlight and iSE board will be on and running on the battery power. (Refer to Section 2.7). Disconnect the power supply before proceeding. Remove cover by removing 2 screws on each side.
2.5 Network Communication Interfaces 2.5.1 10Base-T RJ-45 Pinout The 10BASE-T Ethernet network (RJ45) system is used in the iSE for network connectivity. The 10 Mbps twisted-pair Ethernet system operates over two pairs of wires. One pair is used for receiving data signals and the other pair is used for transmitting data signals. This means that four pins of the eight-pin connector are used. Figure 2.
2.8 Running on Battery Power To access the Battery and S5 jumper you must remove the cover, refer to Section 2.4. When you first connect the battery, without the AC power adaptor, the unit will be in “Sleep Mode”, in order to save power, and the LCD will display “Flash Standby” (provided that S5 jumper is not installed). When battery is installed, plug the AC adaptor into unit and push the Flash Reset Button (refer to Figure 2.4). Unit is now ready to be configured for recording the data.
2.9 Flash Memory Format A 2 Meg flash memory card is included with your product. This memory card is already formatted; however, the following procedure describes how to format your memory card. Once the memory card is formatted, all the data that had previously been recorded will be replaced by simulated test data (see Figure 2.10). 1) 2) 3) 4) 5) 6) 8) 9) Unplug the AC adaptor from the unit. Hold down the ºC/ºF button and connect the AC adaptor back into the unit. Release the ºC/ºF button.
PART 3 NETWORK CONFIGURATION 3.1 Network Protocols The iSE can be connected to the network using standard TCP/IP protocols. It also supports ARP, HTTP (WEB server), DHCP, DNS and Telnet protocols. 3.2 Ethernet (MAC) Address MAC (Media Access Control) address is your computer's unique hardware number. When you're connected to the LAN from your computer, a correspondence table relates your IP address to your computer's physical (MAC) address.
3.3 DHCP DHCP, Dynamic Host Configuration Protocol enables individual computers or devices to extract their IP configurations from a server (DHCP server). If the DHCP is enabled on your iSE, as soon as the iSE is connected to the network, there is an exchange of information between DHCP server and the iSE. During this process the IP address, the Gateway address, and the Subnet Mask will be assigned to the iSE by the DHCP server. Note that the DHCP server must be configured correctly to do such assignment.
3.5.1 Default IP Address The iSE is shipped with a default IP address set to 192.168.1.200 and Subnet Mask of 255.255.255.0. If you are going to use a Web browser or Telnet program to access the iSE using its default IP address, make sure that the PC from which you’re establishing the connection has an IP address that is in the same range as the iSE’s IP address (192.168.1.x, where x can be any number from 1 to 254. Your PC’s IP address cannot be the same as the iSE’s IP address).
PART 4 OPERATIONS This iSE can be used and configured in several ways, depending on user’s preference and network setup. It can be configured using a Web browser, like Netscape or Internet Explorer. It can also be configured using the iConnect Configuration Software. If DHCP and DNS servers are used, the connection is very simple, no need to find the right IP address or watch for network conflicts, these are all done for you by your network DHCP and DNS server.
4.1 iConnect Software The iSE may also be assigned an IP Address by using the iConnect software. a) Download the iConnect software from the website listed in this manual. b) Install iConnect software on a networked PC. This software is compatible with Windows 95, 98, NT, 2000, and XP. c) Use iConnect to assign an IP address to the iSE and access its web pages for configuration. You can also use any standard web browser to access the iSE’s web pages.
4.1 iConnect Software (continued) d) To access the iSE for Configuration: Click on the “View Webpage” button, you will access the iSE’s home page, refer to Section 4.3 for details. iSERVER HOME PAGE Read Sensor Chart Access Control Configuration Camera Location Figure 4.
4.2 Setting a New IP Address over the Network Besides using the iConnect software, you may use the iSE’s default IP address to access it and assign a new IP address to it. The iSE is shipped with a default IP address of 192.168.1.200 and Subnet Mask of 255.255.255.0. You can configure your PC’s Network connection with an IP address that is in the same range as the iSE’s IP address (192.168.1.x) and connect to the iSE using a crossover network cable between your PC and the iSE.
4.3 Setup and Operation Using the iSE Web Page • Start your web browser. • From the browser you type http://eisxxxx using the last four-digits from the MAC address label located on the device if DHCP and DNS are used. If a static IP address is used, then simply type http://x.x.x.x, where x.x.x.x is the iSE’s IP address. • The Home Page, shown in Figure 4.5, will be displayed. Figure 4.
4.3.1 Read Sensor • Click on Read Sensor . In a few seconds the following page (Figure 4.7) will appear with all default values of 100.00. Then the actual readings of Temperature will display. • This page automatically updates the Temperature readings as well as the Differential values. • Click on Main Menu to return to Home Page.
4.3.1.2 Java Runtime Environment 1.5 (5.0) Setup instructions 1. Go to your computer's Control Panel. Open the Java Plug-in 2. Click on "Settings" & "View Applets" in the "General" tab. 3. Select the "Settings" button on the General Tab Un-check the "Enable Caching" box. Then close dialog box to show the General Tab again 4. Select the "Network Settings" button on the General Tab. Proceed to the Browser tab. Follow the Browser Proxy Selection instructions below.
4.3.2 Adjustable Chart • Click on Chart , the following page (Figure 4.8) should appear. The Java™ Applet graph displays Temperature values which can be charted across the full span or within any narrow range (such as 20 to 30ºC). The time-base can display one minute, one hour, one day, one week, one month or one year.
4.3.3 Retrieving Data from Flash To retrieve and graph the data that is stored in the Flash Memory, you have two options: OPTION 1: You can use the iSE’s WEB interface to chart the data stored in the flash memory. 1. Click on the “Chart” button located on the Server Home Page, see Figure 4.5. 2. Select a time interval of Day, Week, Month or Year (Minute and Hour are not selectable for data retrieval). 3.
4.3.4 Access Control This section describes the "Access Control" page of the iSE’s Web interface. This page allows the users to set up the network and security parameters of the iSE. At the initial entrance to the “Access Control” page you will be prompted for the LOGIN Password (see Figure 4.6) prior to an ADMINISTRATOR Password. The DHCP can be enabled by setting the dip switch number 3 to ON position. ACCESS CONTROL Address http://192.168.1.
4.3.4 Access Control (continued) Camera Label: This is the text field to name the camera button on the iSE Home Page, the default is “Camera Location”. Power Recycle: Clicking this button will reset the power on the iSE. 4.3.5 Configuration Setting up the Flash Memory Card can be done in the Configuration page. From the Home Page Menu click on Configuration to get to the page (see Figure 4.11). General Description of the Configuration page: There are two general sections “Flash Card Memory” and “Server”.
CONFIGURATION http://192.168.1.50 No. Sensor Name 1 Temperature 1 3 Differential 2 CONFIGURATION Reading Command Remote End Char Display Units Remote Format Offset SRTF 0D F T0000.0 0.0 SRDF 0D F D0000.0 0.0 Temperature 2 SRHF 4 Input Contact 1 SRT2 5 Input Contact 2 F 0D 0D T0000.0 0.0 0D SRH2 Click on Sensor No. on left to modify Sensor Parameters.
4.3.5 Configuration (continued) Below are the definitions of terms used in the Configuration page. A) Configuration/Device Setup Clicking on the No. 1, 2, 3, 4 or 5 allows you to modify the Sensor Parameters (see Section 4.3.6 for more details). B) Real Time Clock RTC Date and Time: The formats are mm/dd/yyyy and hh:mm:ss. The exact formats are required otherwise an error message will appear in the Title box. Note: time is military time/24 hour based.
Example: If High/Low is selected, the temperature will be monitored against these two High and Low values. If temperature goes above High value (082.5), Relay 1 will be energized, and if temperature goes below Low value (032.5) Relay 1 will be energized. Input 1 Status: Unlatch, Latch, Clear Latch, Chart SP Input 2 Status: Unlatch, Latch, Clear Latch, Chart SP Unlatch: The relay in the iSE will be turned on (closed) when the Temperature 1 and/or Temperature 2 values fall outside of Setpoint range.
4.3.5 Configuration (continued) Status/RTC/Alarm: Select “Configuration” and “Status/RTC/Alarm”, each followed by clicking the Update button to retrieve the latest recording settings. By selecting “Status/RTC/Alarm” only, followed by clicking the “Update” button the iSE will report back all the settings, but the “Recording” settings. Start Recording: Select to initiate a recording. Configuration: Select to retrieve the latest recording settings, followed by “Status/RTC/Alarm” option.
4.3.5 Configuration (continued) G) Input Contact Closure Contact 1: Disable, Normally Open, Normally Close Contact 2: Disable, Normally Open, Normally Close Disabled: Contact is dysfunctional. Normally Open: Contact is open. If the contact is closed, there will be an Output High or Low, depending on which output is selected. Read Sensor page will display: Normal. Normally Close: Contact is closed. If the contact is open, there will be an Output High or Low, depending on which output is selected.
4.3.5 Configuration (continued) I) Remote Access Remote IP Address: iSE can establish a connection to a remote device (e.g. an iLD Remote Display with an Ethernet iSE embedded board) with this IP. Remote Port: (default 2000) the remote port number for the connection. Ports 1000 (used for HTTPget, refer to Section 4.5), 2002, 2003, and 2004 are reserved for internal use. Remote Access:** Remote Access can be enabled and disabled.
4.3.6 Sensor Parameters • In the first column of Configuration page (Figure 4.11), click on No. 1 to view and modify the Sensor Parameters page for Temperature 1. Sensor Parameters http://192.168.1.200 SENSOR PARAMETERS No. 1 Sensor Name: Temperature 1 TC Type: K Sampling Rate: 4 Remote End Char 0x: 0D Remote Display Format: T0000.0 Cnnnn.n Offset: 0.0 C Cold Junction: Disable Update Reset Cancel Click on Update button of the Configuration page to finalize updates. Main Menu Figure 4.
4.3.6 Sensor Parameters (continued) Below are some definitions of terms used in the Sensor Parameter pages. Sensor Name: a text field shown on the “Read Sensor” page. TC Type: a list of thermocouple types to select from J, K, T, E, R, S, B, C, N, and L (J Din). (See Figure 12). Sampling Rate: the number of readings per second. The options are: 2, 4, 8, and 12; if the higher sampling rate is selected, you’ll have a lower accuracy. (See Figure 12).
4.4 Telnet Setup Set the Number of Connections to 1-5 other than 0, using telnet simulation program connect to iSE. In continuous mode, the telnet teminal will receive continuous messages from the iSE. In command mode, the command can be sent to query the iSE and get a response back. Refer to Figure 3.3 Send remote reset: Telnet port 2002 will bring a terminal for admin password. After typing the password and following with the end character, the message Admin.
4.5.1 HTTPget using Port 1000 You can setup and read the information from the iSE by using the HTTPget program. The following program can be used to read data from the embedded server firmware by using TCP port 1000. The command string is sent to this TCP port, then the response can be read back from the same socket. The HTTPget.exe file is used to setup and read information from the iSE. This file will be automatically installed when you install the MailNotifier software available on our website and CD.
4.5.1 HTTPget using Port 1000 (continued) httpget -r -S “*SRTC\r” 192.168.1.
4.5.2 HTTPget and ARP to setup Device IP Address Use the iConnect software, which may be downloaded from our website, to do these IP changes whenever possible. Use ARP first to assign the mac address to a static IP address in computer arp table by this command: arp –s 192.168.1.200 00-03-34-00-06-b6 Then use the following command to assign new IP to the device: httpget –r –S "00000000" 192.168.1.200:1 where: “00000000” is admin. password. If the password is wrong, the unit will ignore the new IP.
4.6 ARP Protocol ARP is the Internet layer protocol responsible for matching or obtaining the MAC (hardware) address that corresponds to a particular IP address. The ARP command allows the user to view the current contents of the ARP cache of the local computer (residing on the same network). Microsoft includes the ARP.EXE utility for viewing and modifying the ARP cache with its Windows products.
4.7 iLog Software This is an Excel application software that can log temperature 1, temperature 2 and the differential temperature from the iSE over the local network (Ethernet) or the internet. a) Download the iLog software from the website listed in this manual. b) Install iLog software on a networked PC. This software is compatible with Windows 95, 98, NT, 2000, and XP. c) For complete information of how to use the iLog software, click on the HELP button.
4.8 Mail Notifier Software For complete information of how to use the Mail Notifier software, click on the Help menu of the main window. The Mail Notifier software generates email notifications for alarm conditions. Users can be notified automatically of alarm conditions monitored via internet connections throughout the world. By use of the email forwarding of alarm conditions, alarm conditions can be monitored on a network isolated from the internet and forwarded to connections on the Internet.
4.8.2 Program Options Setup and Configuration Complete program setup requires: • Entering a recipient for the email • Specifying connection details to MAPI services. • Defining alarms for devices, and selecting how and when the email will be active. Options Send To Email Setup Content Startup General Mail Server MAPI Use Login Box Name/Profile Password Email Address Help MS Outlook Outlook 2002 OK Cancel Figure 4.
4.8.3 Device Setting and Configuration Device setup requires: • Server IP Address: for iSE device (for example 192.168.1.200). • Socket Number: (1000 or 2000 depending on iSE settings). • Bus Address/Device ID: interface address (1 to 199). Enter "0" for RS232 interface or for iSE. • Reading Cmd: normally set to SRFT to obtain reading from the devices. If you want to change this setting, refer to list of commands in Section 4.5. • Alarm Type: (High/Low, High value, or Low value).
PART 5 SPECIFICATIONS SENSOR SPECIFICATIONS Thermocouple Input Temperature Range: refer to Thermocouple Chart Temperature Accuracy: refer to Thermocouple Chart Resolution: 1°/0.1° Temperature Stability: 0.08°C/°C Thermocouple Cold End Tracking: 0.05°C/°C Thermocouple Lead Resistance: 100 ohm max.
iSE SPECIFICATIONS INTERFACES Ethernet: Sensor: Supported Protocols: LED Indicators: LCD Display: Processor: Memory: Memory Data Flash Card: 10Base-T (RJ45) Digital 4-wire (Mini-DIN 6) TCP/IP, UDP/IP, ARP, ICMP, DHCP, DNS, HTTP, and Telnet Network Activity, Network Link, and Diagnostics 32 digits, 4.8 x 9.7mm (0.19 x 0.38”) Enhanced 8051, 22 MHz 512 Kbytes Flash, 16 Kbytes SRAM 2 Mbytes or 2 months of data storage at 10 second logging intervals, or 1 year at 1 minute logging intervals.
PART 6 FACTORY PRESET VALUES PRESET PARAMETERS Network Interface: IP Address Gateway Address Subnet Mask Device Host Name Login Password Admin Password DHCP Terminal Server: Server Type Number of Connections Port # Forward CR Remote Access (Tunneling): Remote Access Remote Port Remote IP Address LCD Backlight FACTORY DEFAULTS 192.168.1.200 0.0.0.0 255.255.255.0 eis and the last 4 digits from the MAC address 12345678 00000000 Disabled Command 5 2000 Enable Disable 2000 0.0.0.
PART 7 APPROVALS INFORMATION 7.1 CE APPROVAL This product conforms to the EMC directive 89/336/EEC amended by 93/68/EEC, and with the European Low Voltage Directive 72/23/EEC. Electrical Safety EN61010-1:2001 Safety requirements for electrical equipment for measurement, control and laboratory.
APPENDIX A GLOSSARY User of this manual should be familiar with following definitions: ARP (Address Resolution Protocol) is a protocol for mapping an Internet Protocol address (IP address) to a physical machine address that is recognized in the local network. For example, the IP address in use today is an address that is 32-bits long. In an Ethernet local area network, however, addresses for attached devices are 48-bits long.
Appendix B IP Address An IP address is a unique 32-bit address assigned to a computer and includes: • A network ID number identifying a network. • A host ID number identifying a computer on the network. All IP addresses have been divided into three smaller groups (classes) A, B and C • Class A addresses have 8-bits of network ID and 24-bits of host ID. They can support a large number of hosts, approximately 2 = 16,777,216 computers per network. The IP addresses range in binary from 00000001.xxxxxxxx.
Appendix C IP Netmask IP Netmask or Subnet Mask is a 32-bit pattern of ones and zeros used to determine network portion of an IP address from the host portion of the IP address. Subnet mask is a network ID that is created by borrowing bits from host portion of IP address and using them as part of a network ID. The table below shows a default subnet mask for address Classes A, B, and C.
Appendix D ASCII Char NUL SOH STX ETX EOT ENQ ACK BEL BS HT LF VT FF CR SO SI DLE DC1 DC2 DC3 DC4 NAK SYN ETB CAN EM SUB ESC FS GS RS US SP ! " # $ % & ‘ ( ) * + , .
Appendix / 0 1 2 3 4 5 6 7 8 9 : ; < = > ? D 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 2F 30 31 32 33 34 35 36 37 38 39 3A 3B 3C 3D 3E 3F ASCII Chart Continuation 00101111 o 111 p 00110000 112 q 00110001 113 00110010 r 114 00110011 s 115 00110100 t 116 00110101 u 117 00110110 v 118 00110111 w 119 00111000 x 120 y 00111001 121 00111010 z 122 { 00111011 123 | 00111100 124 } 00111101 125 00111110 ~ 126 00111111 DEL 127 6F 70 71 72 73 74 75 76 77 78 79 7A 7B 7C 7D 7E 7F 01101111 01110000 01110001
Appendix E iLog Error Messages Error # Description Note -10005 Failed to find the iSE. Ethernet cable is disconnected, iSE is powered off, connections across the firewall require longer “connection to socket time out” setting. -8003 User stopped logging readings. -10006 Windows socket was closed. -10007 Windows socket error. Wrong IP or wrong Port number was used. -10008 The iSE failed to respond to a request. Wrong IP or wrong Port number was used.
NOTES
NOTES
WARRANTY/DISCLAIMER OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of one (1) year from the date of purchase. In addition to OMEGA’s standard warranty period, OMEGA Engineering will extend the warranty period for one (1) additional year if the warranty card enclosed with each instrument is returned to OMEGA. If the unit malfunctions, it must be returned to the factory for evaluation.
Where Do I Find Everything I Need for Process Measurement and Control? OMEGA…Of Course! Shop on line at omega.