user guide sensor CNiS8, CNiS8C, CNiS8DH, CNiS8DV, CNiS16, CNiS16D, CNiS32

CYCLE TIME SUBMENU:
Press
d
15) Display flashes 1
st
digit of the previous “Cycle Time” value.
Press
b
&
c
16) Press
b
and
c
buttons to enter a new “Cycle Time” value
(1 to 199 seconds).
Press
d
17) Display shows
STRD
stored message momentarily and then
advances to
RAMP
only, if it was changed, otherwise press
a
to
advance to
RAMP
Ramp Value Submenu.
A cycle time selected between 1 to 199 seconds indicates the total On/Off time
of each proportional cycle.
For example, a 15 second cycle time means that every 15 seconds the output
will turn on for part or all of the cycle.
For Relay Control Outputs, do not select a cycle time of less than 7 seconds or
the relays’ lifetime will be shortened. For a cycle time of less than 7 seconds
select SSR or DC pulse. Use an external SSR with the DC pulse option for
higher current (higher than 1 Amp).
The DEADBAND Submenu will only appear if the ON/OFF was selected
from the "Control Type" Submenu.
DEADBAND SUBMENU:
Press
d
18) Display flashes 1
st
digit of the previous “Dead Band” value.
Press
b
&
c
19) Press
b
and
c
buttons to enter a new “Dead Band” value.
Press
d
20) Display shows
STRD
stored message momentarily and then
advances to
RAMP
only, if it was changed, otherwise press
a
to
advance to
RAMP
Ramp Value Menu.
Dead Band units are the same as Proportional Band units.
The Dead Band or neutral zone is the number of counts around the set
point which the Process Variable must pass above or below the set point,
before the output changes state.
45