User’s Guide Series Shop on line at ® ® omega.com e-mail: info@omega.com For Latest Product Manuals omegamanual.
TABLE OF CONTENTS Part 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 1.1 Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 1.2 Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 1.3 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 Part 2 Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
.3.6 4.3.6.1 4.3.6.2 4.3.6.3 4.3.6.4 4.3.6.5 4.3.6.6 4.3.7 4.3.8 4.3.8.1 4.3.9 4.4 4.5 4.5.1 4.5.2 4.6 4.7 4.8 4.8.1 4.8.2 4.8.3 4.8.4 Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33 Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33 Setpoints & On/Off Control . . . . . . . . . . . . . . . . . . . . . . . . . .34 Alarms 1 & 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LIST OF FIGURES: Figure 1.1 Figure 2.1 Figure 2.2 Figure 2.3 Figure 2.4a Figure 2.4b Figure 2.5 Figure 2.6 Figure 2.7a Figure 2.7b Figure 2.8 Figure 2.9 Figure 2.10 Figure 2.11 Figure 2.12 Figure 3.1 Figure 3.2 Figure 3.3 Figure 3.4 Figure 4.1 Figure 4.2 Figure 4.3 Figure 4.4 Figure 4.5 Figure 4.6 Figure 4.7 Figure 4.8 Figure 4.9 Figure 4.10 Figure 4.11 Figure 4.12 Figure 4.13 Figure 4.14 Figure 4.15 Figure 4.16 Figure 4.17 Figure 4.18 Figure 4.19 Figure 4.20 Figure 4.21 Figure 4.
Figure 4.23 Figure 4.24 Figure 4.25 Figure 4.26 Figure 4.27 Figure 4.28 Figure 5.1 Figure 5.2 Figure 5.3 HTTPget Example of Polling End Device . . . . . . . . . . . . . . . . .51 ARP Commands and Responses . . . . . . . . . . . . . . . . . . . . . . .52 iLog Software Logging Data for End Device . . . . . . . . . . . . . . .53 Mail Notifier Main Window . . . . . . . . . . . . . . . . . . . . . . . . . . . .55 Mail Notifier Profile Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PART 1 INTRODUCTION 1.1 Safety Considerations This device is marked with the international caution symbol. It is important to read this manual before installing or commissioning this device as it contains important information relating to Safety and EMC (Electromagnetic Compatibility). This instrument is a panel mount device protected in accordance with EN 61010-1:2001, electrical safety requirements for electrical equipment for measurement, control and laboratory.
1.2 Before You Begin Inspecting Your Shipment: Remove the packing slip and verify that you have received everything listed. Inspect the container and equipment for signs of damage as soon as you receive the shipment. Note any evidence of rough handling in transit. Immediately report any damage to the shipping agent. The carrier will not honor damage claims unless all shipping material is saved for inspection.
1.3 Description (continued) The wireless sensors transmit up to four hundred feet 400’ (approx. 120 meters-without obstructions or interference) to a zSeries monitor-controller connected directly to an Ethernet network and the Internet. The wireless system complies with IEEE 802.15.4 operating at 2.4 GHz. The zSeries DIN Rail monitor and controller can monitor up to eight (8) wireless sensors.
1.3 Description (continued) The virtual chart viewed on the web page is a JAVA™ Applet that records a chart over the LAN or Internet in real time. With the zSeries system there is no need to invest time and money learning a proprietary software program to log or chart the data. Chart scales are fully adjustable on the fly. For example, the chart can display one minute, one hour, one day, one week, one month or one year.
PART 2 HARDWARE 2.1 Physical Characteristics and Mounting 2.1.1 Front and Side Views N/C 1 DEFAULT 2 DHCP 3 N/C 4 ON ON 1 8 OFF NOT USED ETHERNET RESET BUTTON CONNECTOR (NOT USED) ACTIVITY NET LINK TX RX ETHERNET LEDS ETHERNET JACK REMOTE DISPLAY PROGRAMMER CONNECTION (NOT USED) 1 OUTPUT / POWER CONNECTOR OUTPUTS OUTPUT 1 & 2 ALARM 1 & 2 LEDs L(+) N(-) 6 ANTENNA CONNECTOR POWER LED Figure 2.
2.1.2 Front Panel The front panel connections are shown in Figure 2.2. Figure 2.2 Front Panel Power and Output Connections Table 2.1 Front Panel Connector POWER OUTPUT 1 AC/DC Power Connector: All models Based on one of the following models: Relay SPDT Solid State Relay (SSR) Pulse Analog Output (Voltage and Current) OUTPUT 2 Based on one of the following models: Relay SPDT Solid State Relay (SSR) Pulse Network Communication Interface Section: ETHERNET RJ45 interface for 10BASE-T connection.
N/C 1 DEFAULT 2 DHCP 3 N/C 4 ON NOT USED ACTIVITY NET LINK TX RX 2.1.3 Dimensions L(+) N(-) 6 OUTPUTS 8 1 ON 1 Figure 2.
2.1.4 Assembly and Mounting 2.1.4.1 Mounting Instruction MOUNTING To install unit onto DIN Rail: 1) Tilt unit, position mounting slot onto DIN Rail, as shown. 2) Push unit towards DIN Rail and it will snap into place. Figure 2.4a Mounting - Installation To remove unit from DIN Rail: 1) Insert flat screw-driver into tab and push downwards. 2) Unit will detach from DIN Rail. Figure 2.
2.1.4.2 Antenna Mounting Instruction For best reception: connect the antenna directly to the wiDR, if the device is not installed in a metal panel or enclosure. If the wiDR is behind a metal panel or in a cabinet, use a coaxial cable to position the antenna outside outside of the enclosure in the open air. Use the shortest cable that can reach a suitable location. The antenna on this wiDR and any End Devices should be installed in a vertical position, pointing towards the sky.
2.1.5 Electrical Installation 2.1.5.1 Power Connections Warning: Do not connect ac power to your wiDR until you have completed all output connections. This wiDR must only be installed by a specially trained electrician with corresponding qualifications. Failure to follow all instructions and warnings may result in injury! Connect the main power connections as shown below. Figure 2.6 Main Power Connections Table 2.
2.1.5.2 Wiring Outputs C OUTPUT 1 OUTPUT 2 OUTPUT 1 OUTPUT 2 This wiDR has two factory installed outputs. The SPDT Mechanical Relay, SPST Solid State Relay, Pulse and Analog Output Connection are shown below. 0.5 A (T) SSR NO External Load C 3 A (T) NC RELAY NO External Load Figure 2.
2.1.5.
2.1.5.3 Dip Switches To change the DIP switches, follow the instructions below: 1. Locate the 4 and 8 position DIP switches. The wiDR is shipped with all DIP switches in "OFF" position To set the Wireless and Ethernet settings to Factory Default, Refer to Section 7. N/C 1 DEFAULT 2 DHCP 3 N/C 4 4 Position DIP Switch for Ethernet settings 8 Position DIP Switch for Wireless settings ON ON 1 8 OFF Figure 2.
2.2 Network Communication Interfaces 2.2.1 10Base-T RJ-45 Pinout The 10BASE-T Ethernet network (RJ-45) system is used in the wiDR for network connectivity. The 10 Mbps twisted-pair Ethernet system operates over two pairs of wires. One pair is used for receiving data signals and the other pair is used for transmitting data signals. This means that four pins of the eight-pin connector are used.
PART 3 NETWORK CONFIGURATION 3.1 Ethernet (MAC) Address MAC (Media Access Control) address is your computer's unique hardware number. When you're connected to the LAN from your computer, a correspondence table relates your IP address to your computer's physical (MAC) address. The MAC address can be found on the label of your wiDR (see Figure 3.
3.3 DHCP (continued) The wiDR is shipped with DHCP disabled (factory default). If fixed or static IP address is desired, the DHCP must be disabled. The DHCP can be enabled by setting the DIP switch # 3 to the “ON” position Figure 3.2 4 Position DIP Switch Setting the wiDR’s IP address to 0.0.0.0 will also enable DHCP. 3.4 DNS DNS, Domain Name System enables computers and devices to be recognized over a network based on a specific name instead of IP addresses.
3.5 IP Address Every active device connected to the TCP/IP network must have a unique IP address. This IP address is used to establish a connection to the wiDR. Every computer using TCP/IP should have a unique 32-bit address which is divided into two portions, the network ID and the host ID. For instance, every computer on the same network uses the same network ID. At the same time, all of them have a different host ID. For more details about the IP address see Appendix B. 3.5.
3.5.2 Changing TCP/IP Properties on Your Computer Go to your computer’s Control Panel then Network Connections. Pick the network with the proper Ethernet card. Right click and choose Properties Look for Internet Protocol Version 4 (TCP/IPv4), click on it and press Properties Figure 3.3 Network Connections Setup the IP address (in this case, 192.168.1.1) as shown below and press OK You can access the Coordinator’s web server via any internet browser using IP address of 192.168.1.200.
PART 4 NETWORK OPERATIONS This wiDR can be used and configured in several ways, depending on user’s preference and network setup. It can be configured using a Web browser, like Internet Explorer. It can also be configured using the iConnect Configuration Software. If DHCP and DNS servers are configured to exchange information, the connection will be very simple. All you need to do is to enable DHCP on the wiDR (see Section 3.
4.1 iConnect Software The wiDR may also be assigned an IP Address by using the iConnect software. a) Download the iConnect software from the website listed in this manual. b) Install iConnect software on a networked PC. This software is compatible with Windows 95, 98, NT, 2000, and XP. c) Use iConnect to assign an IP address to the wiDR and access its web pages for configuration. You can also use any standard web browser to access the Wireless System’ web pages.
4.1 iConnect Software (continued) d) To access the Wireless System for Configuration: Click on the “View Webpage” button, you will access the Wireless System’s home page, refer to Section 4.3 for details. WIRELESS SENSOR HOME PAGE Figure 4.
4.2 Setting a New IP Address over the Network Besides using the iConnect software, you may use the wiDR’s default IP address to access it and assign a new IP address to it. The wiDR is shipped with a default IP address of 192.168.1.200 and Subnet Mask of 255.255.255.0. You can configure your PC’s Network connection with an IP address that is in the same range as the wiDR’s IP address (192.168.1.x) and connect to the wiDR using a crossover network cable between your PC and the wiDR.
4.3 wiDR’s Configurations and Operations Using a web browser, you should be able to view the wiDR’s homepage. • Start your web browser. • From the browser you type http://wisxxxx using the last four-digits from the MAC address label located on the wiDR (see Figure 3.1), if DHCP and DNS are used. If a static IP address is used, then simply type http://x.x.x.x, where x.x.x.x is the wiDR’s IP address. • The Home Page, will be displayed. Figure 4.
4.3 wiDR’s Configurations and Operations (continued) LOGIN ADMINISTRATOR http://192.168.1.200 http://192.168.1.200 LOGIN ADMINISTRATOR Figure 4.6 LOGIN and ADMINISTRATOR Passwords There are 2 different access levels: 1. ADMINISTRATOR Password (administrator) allows certain groups and individual users to access and modify parameters without any restrictions. The default password is 00000000. This password can be up to 16 alphanumeric case-sensitive characters. 2.
4.3.2 Get Readings from the End Device Once you see the End Device’s LED blinking periodically, it means it is sending data which will appear on the “Readings” page. To view the data in a chart format, you can use the “Chart” page. Click on Readings from the Home Page, the following page will appear, showing updates of the Process and Ambient Temperature. Figure 4.
4.3.2 Get Readings from the End Device (continued) ID: End Device ID/address Sequence: Sequence number [0-255 ]. The Sequence number is incremented for each newly received data. Therefore, it indicates if the sensor is transmitting data successfully. Strength: It is the radio signal strength (0-100%), the higher the better. Success: 0-100%, a low success rate indicates a longer data delay, shorter battery lifetime and high network traffic. Battery: The total voltage of the battery in the End Device.
4.3.3 Java Runtime Environment Setup If your computer does not have Java installed, please download from java.sun.com. You can change the Java setting by clicking its icon in Control Panel. To load the applet, you have to enable the web browser and disable cache. 4.3.3.1 Java Runtime Environment 1.7 Setup Instructions 1. Go to your computer's Control Panel. Open the Java Plug-in Verify that the path is correct. Figure 4.9 Java 1.
4.3.3.2 Browser Proxy Selection Accessing wiDR units within your internal network • Usually when the computer and wiDRs are on an internal network, you will not use Proxy server access. • You should un-check the "Use Browser Settings" option on the "Proxy" tab. Accessing wiDR units using the internet • Often the web browser will use Proxy server access to the internet. In such cases, the default Java runtime settings on the "Proxy" tab should suffice.
4.3.4 Chart Click on Chart from the Home Page, the following page will appear. The Java™ Applet graph displays Process Temperature and Ambient Temperature. It can be charted across the full span or within any narrow range (such as 20 to 30ºC). If a blank screen appears without any “java application running” or image of a “Java logo”, please verify you have the latest Java Runtime Environment installed and configured according to the instructions (refer to Section 4.3.3.1).
4.3.4 Chart (continued) Title: wiDR’s name, assigned in "Network Setup" page. Save Current Graph: Save the current graph in PNG (Portable Network Graphics) format. The filename has the extension .png. Max/Min Temperature: Maximum and minimum temperature of the current graph. If a sensor is selected (trend line and sensor name turns bold), its most current temperature reading is shown here. Reading “Open” indicates that no sensing device is detected.
4.3.5 Controller Setup Click on Controller will appear. from the Home Page. In a few seconds the following page Setup Input Setpoints & On/Off A Analog Out Alarm 2 This portion of the menu will be different only if you have the Analog Output Option installed in your wiDR. B Please refer to local regulations for the maximum allowed transmission power. C D Figure 4.
4.3.5 Controller Setup (continued) Below are the definitions of terms used in the Controller Setup page. A) Setup: Clicking on the options shown, allows user to modify the different parameters shown under this menu (see Section 4.3.6. Setup Page for more details) B) Monitor: If you have the DIN Rail version of the zSeries, leave settings as shown below (default) as there is no front panel display; Scrolling: Checked, default. End Device ID: Not applicable.
4.3.6 Setup This section is used to configure the wiDR online. Click on the specific settings to change the parameters on that section 4.3.6.1 Input Control End Device ID: Insert the End Device ID number that will be used as input to control Filter: This option allows the user to specify the number of readings stored in the Digital Averaging Filter. Choice of: 1, 2, 4, 8, 16, 32, 64, 124. Temperature Unit: Unit of temperature readings, [ ºC or ºF ]. SETUP Address http://192.168.1.
4.3.6.2 Setpoints & On/Off Control Auto Setpoint Deviation: If “enabled”, allows changes to Setpoint 1 to be made automatically to Setpoint 2. This mode is very helpful if the Temperature changes often. In Setpoint Deviation Mode, set SP2 a certain number of degrees or counts away from SP1--this relation remains fixed when SP1 is changed. For instance: Setting SP1=200 and SP2=20 and enabling SP Deviation means that the absolute value of SP2=220. Moving SP1 to 300, the absolute value of SP2 becomes 320.
4.3.6.2 Setpoints & On/Off Control (continued) SETUP Address http://192.168.1.200 SETUP Setpoints & On/Off Control Auto Setpoint Deviation Disabled Setpoint 1 Setpoint 2 0 100 Permanent Store On/Off 1 DeadBand Action On/Off 2 DeadBand Action Disabled 0 Reverse Disabled 0 Direct Update Cancel Main Menu Figure 4.
4.3.6.3 Alarms 1 & 2 Alarm 1 (or 2) Relay: to enable or disable (no alarm functions) the alarms . Alarm 1 (or 2) Low: editable box for the low alarm value. Alarm 1 (or 2) High: editable box for the high alarm value. Active: If Above, Alarm condition triggered when the process variable is greater than the Alarm Hi Value (Low value ignored). If Below, Alarm condition triggered when the process variable is less than the Alarm Low Value (Hi value ignored).
4.3.6.3 Alarms 1 & 2 (continued) SETUP Address http://192.168.1.200 SETUP Alarm 1 Alarm 1 Relay Alarm 1 Low Enabled Alarm 1 High Active Normally Latch Absolute Alarm at Power On: Alarm could be 100 0 triggered immediately by non-controlling end device at startup. Above Open Unlatched Absolute Enabled Update Cancel Main Menu Figure 4.
4.3.6.4 Analog Output Retransmission This menu will appear only if you have the Analog Output Option installed in your wiDR. SETUP Address http://192.168.1.200 SETUP Analog Output Retransmission Retransmission Voltage/Current Enabled Input Low Output Low Input High Output High 0 Voltage 0.00 Min. 0V 1000 10.00 Max. 10V Update Cancel Main Menu Figure 4.
4.3.6.5 Display This submenu is for the 1/8 DIN Panel Meter-Controller version of the zSeries it allows the user to select the color of the display--green, red, amber. If you have the DIN Rail version of the zSeries, leave settings as shown below (default) as there is no front panel display; however the small LEDs will perform as described in Table 4.1 when these settings are used. See Figure 2.1 and Table 4.1 for LED location and descriptions. SETUP Address http://192.168.1.
4.3.6.6 Passcode ID This submenu is for the 1/8 DIN Panel Meter-Controller version of the zSeries. and is used to prevent unauthorized tampering with the setup parameters. The meter provides protection by requiring the user to enter the ID Code before allowing access to subsequent menus of the meter’s front panel. If the ID Code entered does not match the ID Code stored, the meter responds with an error message and access to subsequent menus will be denied.
4.3.7 Network Setup Click on Network Setup from the Home Page, the following page will appear. A B C Figure 4.
4.3.7 Network Setup (continued) A) General Secured Applet: If checked, the LOGIN password is required to open “Readings” and “Chart” pages. Title: wiDR’s name [maximum of 16 alphanumeric characters], shows on the "Chart" and "Reading" pages. B) Terminal Server TCP/UDP*: The wiDR supports TCP and UDP protocols (default is TCP). If UDP is selected, it can be configured either for Broadcast UDP or Directed UDP. In case of Broadcast UDP, the wiDR will transmit the data to every node on the network.
4.3.8 End Device Setup Click on End Device from the Home Page, the following page will appear. END DEVICE SETUP Address http://192.168.1.
4.3.8 End Device Setup (continued) The End Device Setup Page is for configuring the End Device parameters such as Name and Update Rate. #: End Device ID/address configured on the End Device. Click on the number (1 to 8) to view device and modify End Device Parameters. Name: Name of an End Device, shows on the "Readings" and "Chart" pages. It is modified on the "End Device Parameters" page. Update: How often the wiDR is expected to receive data from an End Device.
4.3.8.1 End Device Parameters END DEVICE PARAMETERS Address http://192.168.1.200 END DEVICE PARAMETERS End Device 1 Device Name: ABCDEFGH Update: 120 Sec Sensor1 Remote Display Format: 0000000F Remote End Char(Hex): 0x 0D Offset(xxxx): 0 Display: C Alarm Sensor2 Remote Display Format: 0000000F Remote End Char(Hex): 0x 0D Offset(xxxx): 0 C Update Cancel Device Reset Main Menu Figure 4.
4.3.8.1 End Device Parameters (continued) Device Name: Name of this End Device, this is a text field and can take up to 16 alphanumeric characters Update (Seconds): How often this End Device is sending its data to the wiDR. The default shown "update second" is 120 seconds. This update corresponds to the sampling rate configured by using the Configuration Wizard. For detailed steps on how to configure the sampling rate, please refer to Section 4.1 of the UWTC Manual.
4.3.8.1 End Device Parameters (continued) If the end character for instance is 20 (Hex representation of space), the data will then appear as: T75F T74F If nothing is set for the "Remote End Char" field, the wiDR will then forward the data to the LAN with no characters followed. Offset: If it’s determined that the readings are slightly off, the user can manually assign numerical values to adjust the readings for temperature. The unit must be in degree C. Display: Not used for the wiDR.
4.3.9 Access Control (continued) Login Password: This allows users to access and modify all of the Wireless System Home Page menu items, except “Access Control”, which requires an Administrator password. The default Login password is 12345678. This password can be up to 16 alpha-numeric case-sensitive characters. If there is no Login Password assigned (blank box) the Wireless System will not require a password to access and modify any of the menu items, except the “Access Control” page.
4.4 Telnet Setup In the “Network Setup” page, under the Terminal Server section, set the TCP Connections to 1 to 5 other than 0, and use a telnet emulation program to connect to the wiDR (using Port 2000). The command can be sent to query the wiDR and get a response back. Table 4.2 List of ASCII/Telnet Commands (01 indicates End Device #1) Command *SR01a\r *SR01b\r *SR01e\r *SR01f\r *SR01g\r *SR01h\r *SR01i\r *SR01j\r *SR01k\r *SR01l\r *SR01m\r *SR01n\r *SR01o\r *SR01p\r *SR00z\r Description Reading from
4.5 HTTPget Program The Httpget software is used to send a single HTTP or TCP request to the wiDR. In contrast, the telnet or Hyperterminal programs allow a continuous connection with multiple requests to be sent to the wiDR. Generally HTTPget is used for simply programming an IP address to the wiDR or for quickly obtaining a reading from a End Device. The wiDR must be configured from the “Network Setup” page so that the "TCP Connections" indicates any number between 1 and 5.
4.5.1 HTTPget using Port 2000 (continued) where: -r –S are parameters needed for the the command string Command (See Table 4.2) 192.168.1.135 is an IP address 2000 is a socket port number -C1 closes the TCP connection after 1 second -q displays no error messages once the connection is closed Figure 4.23 HTTPget Example of Polling End Device #2,6,7 Table 4.
4.6 ARP Protocol ARP is the Internet layer protocol responsible for matching or obtaining the MAC (hardware) address that corresponds to a particular IP address. The ARP command allows the user to view the current contents of the ARP cache of the local computer (residing on the same network). Microsoft includes the ARP.EXE utility for viewing and modifying the ARP cache with its Windows products.
4.7 iLog Software This is an Excel application software that can log temperature from the wiDR over the local network (Ethernet) or the internet. a) Download the iLog software from the website listed in this manual. b) Install iLog software on a networked PC. This software is compatible with Windows 95, 98, NT, 2000, XP, Windows Vista and Windows 7 (32 and 64-bit).
4.7 iLog Software (continued) Table 4.4 iLog Excel Applications The iLog application actually consists of several Excel files, though most supported devices can be accessed by the main iLog program. The main program is listed as "iLog", plus a version number, under the Start Menu program links (those links available by clicking the Start button on the Windows taskbar). In the following table, the iLog File column shows how many sensors are logged by the main iLog file.
4.8 Mail Notifier Software For complete information of how to use the Mail Notifier software, click on the Help menu of the main window. The Mail Notifier software generates email notifications for alarm conditions. Users can be notified automatically of alarm conditions monitored via internet connections throughout the world. By use of the email forwarding of alarm conditions, alarm conditions can be monitored on a network isolated from the internet and forwarded to connections on the Internet.
4.8.2 Program Options Setup and Configuration Complete program setup requires: • Entering a recipient for the email • Specifying connection details to MAPI services. • Defining alarms for devices, and selecting how and when the email will be active. Options Send To Email Setup Content Startup General Mail Server MAPI Use Login Box Name/Profile Password Email Address Help MS Outlook Outlook 2002 OK Cancel Figure 4.
4.8.3 Device Setting and Configuration The wiDR and End Devices should first be configured and ready to use. Make sure to have the following settings in the ”Network” web page of the wiDR (Figure 4.21) .
4.8.3 Device Setting and Configuration (continued) Alarm Editor Device Info (1 of 2) Server IP Address 192.168.1.200 Socket Number 2000 Bus Address/Device ID 3 OK Cancel Help Description Add Src ID Dev1 Reading Cmd zRdgA SR##a Del Only Monitor Access to iServer device Alarm Configuration Alarm Type Alarm High Info Message Alarm High 73 Email Interval Alarm Low 0 Monitor Interval 0.5 min. Alarm Hold Time 0.0 min. 0.05 hrs. Figure 4.28 Mail Notifier Device Setting 4.8.
Part 5 ENVIRONMENT / OPERATING CONDITIONS The End Device and wiDR monitor-controller are designed to be fixed mounted and operated in a clean and dry environment. Care should be taken to prevent the components of your wireless system from being exposed to moisture, toxic chemicals, extreme cold or hot temperature that are outside the specification listed in this manual. The following is a list of basic good practice you should apply when operating this Wireless System. 1.
7. Where possible, try to ensure an uninterrupted line-of-sight between nodes. Avoid obscuring objects (e.g. metal pillars, posts, sign) near the antenna. A close object obscures a wider range of solid angle. 8. It is important to understand that the environment may change over time due to new equipment or machinery being installed, building construction, etc. If new obstacles exist between the End Device and wiDR, antenna angle may need to be re-adjusted and/or the unit has to be relocated. 9. An IEEE 802.
5.2 With Line-of-Sight When installing the wiDR it is important to position your device in such a way to optimize the antenna location within what’s known as the “Fresnel Zone”. The Fresnel Zone can be thought of as a football-shaped invisible tunnel between two locations that provides a path for RF signals between the End Device and the wiDR. Figure 5.2 Fresnel Zone In order to achieve maximum range, the football-shaped path in which radio waves travel must be free of obstructions.
5.3 Without Line-of-Sight When line-of-sight is not possible, signal penetrates and is reflected by different objects to reach the destination. Therefore, it is important to learn about how these materials would affect signal propagation. Depending on the thickness, moisture content and angle of incidence, a wall may allow between 1% and 25% of the radio power to pass through. Metal panel or metalized glass window will not allow much radio power to pass through.
PART 6 SPECIFICATIONS ON/OFF CONTROL OUTPUT 1 & 2 Relay: 250 Vac or 30 Vdc @ 3 A (Resistive Load), SPDT Solid State Relay (SSR): 20 to 265 Vac @ 0.05 to 0.5 A (Resistive Load); continuous DC Pulse: Non-Isolated; 10 Vdc @ 20 mA Analog Output (Output 1 only) Non-Isolated, 0 to 10 Vdc or 0 to 20 mA, 500 max Operation: Direct (cool), reverse (heat); deadband; single sensing input Configuration Output 1 and 2 can be configured as Alarm 1 and 2, respectively.
GENERAL Line Voltage/Power: Low Voltage/Power Option: External Fuse Required: Time-Lag, IEC 127-3 recognized: Time-Delay, UL 248-14 listed: Environmental Conditions: Dimensions: Software: 90 to 240 Vac +/-10%, 50 to 400 Hz*; 110 to 375 Vdc, equivalent voltage; 4 W * No CE compliance above 60 Hz 12 to 36 Vdc or 24 Vac** +/-10%; 3 W External power source must meet Safety Agency Approvals. **Units can be powered safely with 24 Vac power but, no Certification for CE are claimed.
WIRELESS COMMUNICATION (continued) Radio Power Output: 100 mW (20 dBm), 10 mW (10 dBm) Limitations on Equivalent Isotropic Radiated Power (EIRP) levels in the European Community and other countries applies. An improper combination of power level can result in an EIRP above the allowed amount per regulations. See Appendix F. Data Rate: Modulation: Receiver Sensitivity: Bit rate 250 Kp/s; Symbol rate 62.
PART 7 FACTORY PRESET VALUES To set the Wireless and Ethernet settings back to Factory Default do the following to the DIP switches (see Figure 2.10). To set the Ethernet board to Factory Default settings: 1) Put the 4 position DIP switch #2 to ON position (it does not matter if the wiDR is On or Off). 2) Power-cycle the wiDR and wait about 10 seconds until the wiDR fully boots up.
Table 7.
Table 7.1 Factory Preset Values (continued) Analog Output Retransmission Retransmission Enabled Voltage/Current Voltage Input Low 0 Output Low 0.00 Input High 1000 Output High 10.00 Monitor Scrolling R End Device ID Permanent Store 0 Transmit Power PID (Network ID) 13106 (version x.x) Channel 12 Transmit Power Range 20 dBm Misc iSeries Firmware Ver x.
Table 7.
APPENDIX A GLOSSARY User of this manual should be familiar with following definitions: ARP (Address Resolution Protocol) is a protocol for mapping an Internet Protocol address (IP address) to a physical machine address that is recognized in the local network. For example, the IP address in use today is an address that is 32-bits long. In an Ethernet local area network, however, addresses for attached devices are 48-bits long.
Appendix B IP Address An IP address is a unique 32-bit address assigned to a computer and includes: • A network ID number identifying a network. • A host ID number identifying a computer on the network. All IP addresses have been divided into three smaller groups (classes) A, B and C • Class A addresses have 8-bits of network ID and 24-bits of host ID. They can support a large number of hosts, approximately 2 = 16,777,216 computers per network. The IP addresses range in binary from 00000001.xxxxxxxx.
Appendix C IP Netmask IP Netmask or Subnet Mask is a 32-bit pattern of ones and zeros used to determine network portion of an IP address from the host portion of the IP address. Subnet mask is a network ID that is created by borrowing bits from host portion of IP address and using them as part of a network ID. The table below shows a default subnet mask for address Classes A, B, and C.
Appendix D ASCII Char NUL SOH STX ETX EOT ENQ ACK BEL BS HT LF VT FF CR SO SI DLE DC1 DC2 DC3 DC4 NAK SYN ETB CAN EM SUB ESC FS GS RS US SP ! " # $ % & ‘ ( ) * + , .
Appendix / 0 1 2 3 4 5 6 7 8 9 : ; < = > ? D 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 2F 30 31 32 33 34 35 36 37 38 39 3A 3B 3C 3D 3E 3F ASCII Chart Continuation 00101111 o 111 p 00110000 112 q 00110001 113 00110010 r 114 00110011 s 115 00110100 t 116 00110101 u 117 00110110 v 118 00110111 w 119 00111000 x 120 y 00111001 121 00111010 z 122 { 00111011 123 | 00111100 124 } 00111101 125 00111110 ~ 126 00111111 DEL 127 6F 70 71 72 73 74 75 76 77 78 79 7A 7B 7C 7D 7E 7F 01101111 01110000 01110001
Appendix E iLog Error Messages Error # Description -8003 Note User stopped logging readings. -10005 Failed to find the wiDR. Ethernet cable is disconnected, iServer is powered off, connections across the firewall require longer “connection to socket time out” setting. -10006 Windows socket was closed. -10007 Windows socket error. Wrong IP or wrong Port number was used. -10008 The wiDR failed to respond to a request. Wrong IP or wrong Port number was used. -10011 No data was sent.
Appendix F Warnings and Regulatory Information (continued) The following alert sign indicates that there are restrictions on usage of the equipment in regards to power limitations on Equivalent Isotropic Radiated Power (EIRP) levels in the European Community. The following are user restrictions: • Wideband Data Transmission Systems on the band 2400 – 2483.5 MHz in Europe is limited to a Maximum of 10 mW (10dBm) for Direct Sequence Spread Spectrum (DSSS).
NOTES ______________________________________________________________________________ ______________________________________________________________________________ ______________________________________________________________________________ ______________________________________________________________________________ ______________________________________________________________________________ ______________________________________________________________________________ ________________________________
NOTES ______________________________________________________________________________ ______________________________________________________________________________ ______________________________________________________________________________ ______________________________________________________________________________ ______________________________________________________________________________ ______________________________________________________________________________ ________________________________
NOTES ______________________________________________________________________________ ______________________________________________________________________________ ______________________________________________________________________________ ______________________________________________________________________________ ______________________________________________________________________________ ______________________________________________________________________________ ________________________________
WARRANTY/DISCLAIMER OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of one (1) year from the date of purchase. In addition to OMEGA’s standard warranty period, OMEGA Engineering will extend the warranty period for one (1) additional year if the warranty card enclosed with each instrument is returned to OMEGA. If the unit malfunctions, it must be returned to the factory for evaluation.
Where Do I Find Everything I Need for Process Measurement and Control? OMEGA…Of Course! Shop on line at omega.