Cut Sheet

Product: 29532C
VFD, 3C #4/0 Str BC XLPE Ins + #3 Symm. Seg. Gnd (3 of #8) Str BC, CTS,
Blk PVC Jkt, 600/1000V TC-ER 90C Dry/Wet 1000V CSA AWM I/II A/B
Product Description
Belden Basics VFD, 3 Conductor 4/0AWG (19x10) Bare Copper XLPE Insulation M4 Color Code + 3AWG Symmetrical Segmented Ground (3 of 8AWG) Bare
Copper Stranded, Overall Dual Copper Tapes Helically Applied Shield, Black PVC Outer Jacket, 600/1000V TC-ER 90C Dry/Wet 1000V CSA AWM I/II A/B
SUN RES DIR BUR Oil Resistant
Technical Specifications
Product Overview
Suitable Applications: Variable Frequency Drives (VFD); AC Motor and Drive Systems
Construction Details
Conductor
Element Number of Element Size Stranding Material Notes
Conductor(s) 3 4/0 AWG 19x10 BC - Bare Copper
Ground 3 8 AWG 7x16 BC - Bare Copper Segmented Grounds
Insulation
Element Material Nom. Thickness Color Code
Conductor(s) XLPE - Cross-Linked Polyethylene (Thermoset) 0.059 in (1.5 mm) Black and Numbered
Ground No Insulation
Outer Shield
Shield Type Material Coverage
Helical Tape Bare Copper (BC) 100%
Helical Tape Bare Copper (BC) 100%
Outer Jacket
Material Nom. Thickness Nom. Diameter Ripcord
PVC - Polyvinyl Chloride 0.083 in (2.1 mm) 1.536 in (39.01 mm) Yes
Overall Cable Diameter (Nominal): 1.536 in (39.01 mm)
Electrical Characteristics
Electricals
Element Nom. Conductor DCR
Nom. Capacitance
Cond-to-Cond
Nom. Capacitance Cond-to-Other
(Conds + Shield)
Nom. Characteristic
Impedence
Nom. Velocity of
Prop.
Max. Current
Conductor(s)
0.052 Ohm/1000ft (0.17
Ohm/km)
33 pF/ft (110 pF/m) 60 pF/ft (200 pF/m) 56 Ohm 55%
260 Amps per Conductor at 30ºC
(per NEC)
Voltage
UL Voltage Rating
1000 V (TC, CSA AWM I/II A/B)
Mechanical Characteristics
Temperature
UL Temperature Operating

Summary of content (2 pages)