Datasheet

G5Q PCB Power Relay
G
5
Q
2
■Characteristics
Note. The data shown above are initial values.
*1. The contact resistance is possible with 1 A applied at 5 VDC using a fall-of-potential method.
*2. Testing conditions: The insulation resistance was measured with a 500 VDC megohmmeter at the same locations as the dielectric strength was measured.
*3. This value was measured at a switching frequency of 120 operations/min.
■Engineering Data
Item Classification Standard model
Contact resistance *1 100 mΩ max.
Operate time 10 ms max.
Release time 5 ms max.
Insulation resistance *2 1,000 MΩ min.
Dielectric
strength
Between coil
and contacts
4,000 VAC, 50/60 Hz for 1 min
Between
contacts of the
same polarity
1,000 VAC, 50/60 Hz for 1 min
Impulse withstand voltage
(between coil and contacts)
8 kV (1.2 x 50 μs)
Vibration
resistance
Destruction 10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude)
Malfunction 10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude)
Shock
resistance
Destruction 1,000 m/s
2
Malfunction 100 m/s
2
Durability
Mechanical 10,000,000 operations (18,000 operations per hour)
Electrical
•NO
50,000 operations: 10 A at 125 VAC resistive load
(operation: ON for 1 sec, OFF for 3 sec)
200,000 operations: 3 A at 125 VAC resistive load
(operation: ON for 1 sec, OFF for 1 sec)
100,000 operations: 3 A at 250 VAC resistive load
(operation: ON for 1 sec, OFF for 1 sec)
100,000 operations: 5 A at 30 VDC resistive load
(operation: ON for 1 sec, OFF for 1 sec)
•NC
200,000 operations: 3 A at 125 VAC resistive load
(operation: ON for 1 sec, OFF for 1 sec)
100,000 operations: 3 A at 250 VAC resistive load
(operation: ON for 1 sec, OFF for 1 sec)
100,000 operations: 3 A at 30 VDC resistive load
(operation: ON for 1 sec, OFF for 1 sec)
Failure rate (P level)
(reference *3)
10 mA at 5 VDC
Ambient operating
temperature
-40°C to 105°C (with no icing or condensation)
Ambient operating humidity 5% to 85%
Weight Approx. 6.5 g
●Maximum Switching Capacity ●Ambient Temperature VS.
Maximum Coil Voltage
●Shock Malfunction
100
1
1 10 100 1000
Switching current (A)
Switching voltgate (V)
AC resistive load (NO)
AC resistive load (NC)
DC resistive load (NO)
DC resistive load (NC)
10
200
180
160
140
120
100
80
60
40
20
0
-40
200
-20
8023 60 85 10040 120
Maximum coil voltage (% of rated)
Ambient temperature (°C)
Z
Z'
Shock direction
Y
Y'
XX'
Z'
Z
Unit: m/s
2
Y
Y'
X
X'
1,000
1,000
1,000
1,0001,000
1,000
NO Contact
NC
Contact
300
300
Sample: G5Q-14 12 VDC
Number of Relays: 5 pcs
Test conditions: Shock is applied
in ±X, ±Y, and ±Z directions three
times each with without
energizing the Relays to check
the number of malfunctions.
Requirement: None malfuction
100 m/s
2