Datasheet

2
G6DN PCB Power Relay
G
6
D
N
Characteristics
Note 1. Values in the above table are initial values.
Note 2. The contact resistance is measured with 1 A applied at 5 VDC using a fall-of-potential method.
Note 3. The insulation resistance is measured between coil and contacts and between contacts of the same polarity at 500 VDC.
Engineering Data
Contact resistance 100 mΩ max.
Operate time 10 ms max.
Release time 5 ms max.
Insulation resistance 1,000 M
Ω
min. (at 500 VDC)
Dielectric strength
Between coil and contacts 3,000 VAC, 50/60 Hz for 1 min
Between contacts of the same
polarity
750 VAC, 50/60 Hz for 1 min
Surge withstand voltage Between coil and contacts 6 kV (1.2 50 μs)
Vibration resistance
Destruction 10 to 55 to 10 Hz, 2.5 mm single amplitude (5.0 mm double amplitude)
Malfunction 10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude)
Shock resistance
Destruction 1,000 m/s
2
Malfunction 100 m/s
2
Life expectancy
Mechanical 20,000,000 operations min. (at 18,000 operations/hr)
Electrical
100,000 operations min. (3A at 250 VAC, 3 A at 30 VDC Resistive load)
80,000 operations min. (5 A at 250 VAC, 5 A at 30 VDC Resistive load)
100,000 operations min. (2 A at 250 VAC, 2 A at 30 VDC Inductive load)
Ambient temperature Operating -40°C to +90°C (with no icing or condensation)
Humidity 5% RH to 85% RH
Weight Approx. 3 g
Maximum Switching Capacity Durability Ambient Temperature vs.
Maximum Coil Voltage
Note. The maximum coil voltage refers to the
maximum voltage in a varying range of
operating power voltage, not a continuous
voltage.
Ambient Temperature vs. Must
Operate and Must Release Voltages
Shock Malfunction
50
30
10
5
3
1
0.5
0.3
0.1
1351030
100 125 277
500
1,000
Switching current (A)
AC resistive load
DC resistive load
Switching voltage (V)
2.5
250 VAC/30 VDC
Resistive load
Durability (x10
4
operations)
Switching current (A)
1 2 3 4 5 6 7 8 9 10
500
300
100
50
30
10
5
3
0
200
180
160
140
120
100
80
60
0 23304050607080 90
100
Maximum coil voltage (%)
Ambient temperature (°C)
126
90
80
70
60
50
40
30
20
10
0
0 20 40 60 80 100
20
60
40
max.
min.
max.
min.
Ambient temperature (°C)
Must operate and must release voltage (ratio of rated voltage) (%)
X
X
Z
Z'
Z'
Z
Y
Y
Y'
Y'
X
X
X'
X'
1,000
1,000
800
600
400
200
1,000
1,000
1,000 1,000
De-energized
Energized
Shock direction
Unit: m/s
2
Coil terminals
Sample: G6DN-1A
Number of Relays: 5 pcs
Test conditions: Impose a shock in the ±X,
±Y, and ±Z directions three times each with
the Relay energized to check the shock
values that cause the Relay to malfunction.
Standard:100 m/s
2