Datasheet
A22NE-PD
18
A22NE-PD A22NE-P A22E Common Note
Common Accessories and Tools
• After storing the product for a long time exceeding 1 year, perform,
at a minimum, inspections of the operating characteristics, contact
resistance, insulation resistance, and dielectric strength as well as
evaluate the product under the working conditions.
• This product is intended for indoor use only. Using the product
outdoors will result in failure.
• Do not wire anything to the release holes.
• Do not tilt or twist a flat-blade screwdriver while it is inserted into a
release hole on the terminal block. The terminal block may be
damaged.
• Insert a flat-blade screwdriver into the release holes at an angle.
The terminal block may be damaged if you insert the screwdriver
straight in.
• Do not allow the flat-blade screwdriver to fall out while it is inserted
into a release hole.
• Do not bend a wire past its natural bending radius or pull on it with
excessive force.
Doing so may cause the wire disconnection.
• Do not insert more than one wire into each terminal insertion hole.
• When mounting on a device with high airtightness, test operation
in advance. There is a risk that the negative pressure will prevent
the Operation Unit of from returning.
• Although the contacts of an A22NE-PD can be used with both the
standard loads and microloads, once a contact has opened or
closed under a load, you cannot again connect a small-capacity
load. Doing so could roughen the contact surface, and result in
loss of contact reliability.
• In the case of loads where an inrush current occurs when the
contact is opened or closed, the durability may reduce due to
extreme wear on the contacts.
If necessary, insert a contact protection circuit.
• If a contact weld, the lock lever might not return to the release
position, and contact inversion might not occur. In such a case,
move the lock lever to the release position, and remove the Switch
Unit from the Operation Unit.
Wiring
1. Connecting Wires to the Push-In Plus Terminal Block
Part Names of the Terminal Block
Connecting Wires with Ferrules and Solid Wires
• Insert the solid wire or ferrule straight into the terminal block until
the end strikes the terminal block.
• If a wire is difficult to connect because it is too thin, use a flat-blade
screwdriver in the same way as when connecting stranded wires.
Connecting Stranded Wires
Use the following procedure to connect the wires to the terminal block.
1. Hold a flat-blade screwdriver at an angle and insert it into the
release hole. The angle should be appropriately 10 to 15°. If the
flat-blade screwdriver is inserted correctly, you will feel the spring
in the release hole.
2. With the flat-blade screwdriver still inserted into the release hole,
insert the wire into the terminal hole until the end strikes the
terminal block.
3. Remove the flat-blade screwdriver from the release hole.
Precautions for Correct Use
Release
hole
Terminal
(insertion) hole
Ferrule terminal or
solid wire
(2)
(1)
(3)
Flat-head screwdriver
Approx.
10 to 15°