Electrode Holder
BF-@(R)/BS-1(T)
Complete Lineup for Use in High-temperature,
High-pressure Environments or Where
Exposed to Chemicals
• The BF-1 is ideal for liquids with low specific resistance, such as
wastewater.
•The BF-@(R) is used when a strong mounting is required.
• The BS-1 is used when high-temperature, high-pressure resistant
is required.
• The BS-1T is used when corrosion resistance is required.
Ordering Information
■ Electrode Holders ■ Accessories (Order Separately)
Note: Refer to Installing an Electrode Holder on a Tank under Level
Controller Installation in the Technical Guide for Level
Controllers for information on Level Controller installation.
Refer to PS-
@
S(R) Electrode Holder Accessories (Order
Separately) for dimensions.
Specifications
Note: 1. Two-wire Electrode Holders (R models) have a built-in resistance of 6.8 kΩ. They should be used with the Two-wire 61F Controllers.
2. There must be a sufficient ambient temperature in a high-pressure environment to prevent vapor leakage. Use the Electrode Holder
according to the following pressure-temperature curve.
Refer to Safety Precautions for Electrodes and
Electrode Holders.
Application Model
• Liquid with low specific resistance
For 1-pole electrode
• When sturdy mounting is required
For 3-pole electrode
For 3-pole electrode (2-wire)
For 5-pole electrode
For 5-pole electrode (2-wire)
BF-1
BF-3
BF-3R
BF-5
BF-5R
• Applications where resistance to high-
temperature, high-pressure is required
For 1-pole electrodes, 250°C, 1.96 MPa
BS-1
BS-1S
BS-1S-1
BS-1S2
• High-pressure application where resistance
to corrosion is required
For 1-pole electrode, SUS304 981 kPa
For 1-pole electrode, SUS316 981 kPa
For 1-pole electrode, Titanium 981 kPa
For 1-pole electrode, HAS B 981 kPa
For 1-pole electrode, HAS C 981 kPa
BS-1T SUS304
BS-1T SUS316
BS-1T TITANIUM
BS-1T HAS B
BS-1T HAS C
Application Model
Protective Cover (For PS-@S and BF-3/-4/-5)
Protective Cover (For B@-1 and B@-1S)
M18 Nut (For BS-1)
M18 Nut (For BS-1T)
F03-11
F03-19
F03-17
F03-18
Item
Model BF-1 BF-3 (R)
(See note 1.)
BF-5 (R)
(See note 1.)
BS-1 BS-1T
No. of Electrodes 1 35--- ---
Insulator material PPS resin (Metallic section is SUS.) Fluorocarbon polymer (PFA)
Insulation resistance 100 MΩ
Operating temperature Electrode section: −10 to 150°C (with no icing)
Terminal section: −10 to 70°C (with no icing or condensation)
250°C max. 180°C max.
Operating pressure Atmospheric pressure 1.96 MPa (See note 2.) 981 kPa (See note 2.)
Applications Liquids with low specific
resistance, such as
wastewater and cloudy
water
General applications for purified water
and wastewater
Boiler water level
detection or high-
temperature tanks
Acid or alkaline
solution level
detection