CJ1W-PA/PD
*1. Disconnect the Power Supply Units LG terminal from the GR terminal when testing insulation and dielectric strength. Testing the insulation and
dielectric strength with the LG terminal and the GR terminals connected will damage internal circuits in the CPU Unit.
*2. Supported only when mounted to CPU Rack.
*3. The inrush current is given for a cold start at room temperature. The inrush control circuit uses a thermistor element with a low-temperature
current control characteristic. If the ambient temperature is high or the PLC is hot-started, the thermistor will not be sufficiently cool, and the
inrush currents given in the table may be exceeded by up to twice the given values. When selecting fuses or breakers for external circuits,
allow sufficient margin in shut-off performance.
*4. Maintain an ambient storage temperature of 25 to 30°C and relative humidity of 25% to 70% when storing the Unit for longer than 3 months
to keep the replacement notification function in optimum working condition.
*5. Change the applied voltage gradually using the adjuster on the Tester. If the full dielectric strength voltage is applied or turned OFF using the
switch on the Tester, the generated impulse voltage may damage the Power Supply Unit.
*6. CJ1W-PD022 is not insulated between the primary DC power and secondary DC power.
*7. Internal components in the Power Supply Unit will deteriorate or be damaged if the Power Supply Unit is used for an extended period of time
exceeding the power supply output capacity or if the outputs are shorted.
External Interface
CJ1W-PA205R
CJ1W-PA205C
CPU Rack
dimensions
90.7 to 466.7 × 90 × 65 mm (W × H × D) (not including cables)
Note: W = a + b + 20 × n + 31 × m + 14.7
a: Power Supply Unit: PA205R and PA205C = 80; PA202 = 45; PD025 = 60; PD022=27
b: CPU Unit: CJ1-H or CJ1 = 62; CJ1M-CPU1@ = 31; CJ1M-CPU2@ = 49
The total width is given by the following: W = 156.7 + n × 20 + m × 31, where n is the number of 32-point I/O Units or I/O Control Units
and m is the number of other Units.
Safety measures Conforms to cULus and EC Directives.
Item Specifications
Model CJ1W-PA205R CJ1W-PA205C CJ1W-PA202 CJ1W-PD025 CJ1W-PD022
POWER
PA205R
DC24V
AC240V
OUTPUT
RUN
INPUT
AC100-240V
L2/N
L1
POWER Indicator
Lit when 5 V are being output from the Power Supply Unit.
AC input
LG
GR
RUN output
External connection terminals
POWER
Ye a r s
CJ1W-PA205C
TEST
NC
NC
AC100-240V
INPUT
L2/N
L1
L
+
ALARM
OUTPUT
DC30V,50mA
NORMAL:ON
ALARM :OFF
Replacement notification display
POWER indicator
Lit: 5-V output from Power Supply Unit.
TEST switch
The TEST switch can be used to
temporarily turn OFF the alarm output
that notifies when replacement is
needed.
Alarm output
(replacement notification output)
LG
AC input
Terminals
external connect
GR