Datasheet

6
CJ1W-PA/PD
AC Input
Supply 100 to 240 V AC (allowable: 85 to 264 V AC). (Voltage selection is not required.)
DC Input
Supply 24 V DC.
LG
Ground to a resistance of 100 Ω or less to increase noise resistance and avoid electric shock.
GR
Ground to a resistance of 100 Ω or less to avoid electric shock.
RUN Output (CJ1W-PA205R Only)
The internal contact turns ON when the CPU Unit is operating (RUN or MONITOR mode). The Power Supply Unit must be in the CPU Rack to use
this output.
Alarm Output (CJ1W-PA205C Only)
The alarm output is used to notify when Power Supply Unit replacement is required. The output is normally ON. The output turns OFF when the
time until replacement is 6 months or less.
Wiring
Wire
For AC/DC power supply
For grounding wire
For alarm output
Model
Allowable power supply voltage
fluctuation range
CJ1W-PD025 19.2 to 28.8 VDC (±20%)
CJ1W-PD022 21.6 to 26.4 VDC (±10%)
Recommended wire size
AWG14 to 20
(0.517 to 2.08mm
2
)
Recommended wire size 2 mm
2
min.
Recommended wire size Use
Pushing strength
(clamping operation)
Pulling strength
(holding force)
Length of stripped
section
AWG 22 to 18
(0.32 to 0.82 mm
2
)
Connecting to PLC terminal block models
30 N max.
30 N min.
7 to 10 mm
AWG 28 to 24
(0.08 to 0.2 mm
2
)
Connecting to PLC connector models 10 N min.