Datasheet
CP1E-E@@(S)D@-@ CP1E-N@@(S@)D@-@/NA20D@-@
13
General Specifications
* 1 Total of 110 mm with mounting brackets.
* 2 Excluding cables.
* 3 Use the external power supply to power input devices. Do not use it to drive output devices.
* 4
This is the rated value for the maximum system configuration. Use the following formula to calculate power consumption for CPU Units with DC power.
Formula: DC power consumption = (5V current consumption ✕ 5 V/70% (internal power efficiency) + 24V current consumption) ✕ 1.1(current
fluctuation factor)
The above calculation results show that a DC power supply with a greater capacity is required.
Type AC power supply models DC power supply models
Model
CP1E-@@@S@D@-A
CP1E-@@@D@-A
CP1E-@@@S@D@-D
CP1E-@@@D@-D
Enclosure Mounted in a panel
Dimensions (H × D × W)
E/N/NA@@-type
CPU Unit with 10 I/O points (CP1E-E10D@-@): 90mm *1 × 85mm *2 × 66 mm
CPU Unit with 14 or 20 I/O points (CP1E-@14D@-@/@20D@-@): 90mm *1 × 85mm *2 × 86 mm
CPU Unit with 30 I/O points (CP1E-@30D@-@): 90mm *1 × 85mm *2 × 130 mm
CPU Unit with 40 I/O points (CP1E-@40D@-@): 90mm *1 × 85mm *2 × 150 mm
CPU Unit with 60 I/O points (CP1E-N60D@-@): 90mm *1 × 85mm *2 × 195 mm
CPU Unit with 20 I/O points and built-in analog (CP1E-NA20D@-@): 90mm *1 × 85mm *2 × 130 mm
E/N/@@S(1)-type
CPU Unit with 14 or 20 I/O points (CP1E-@14SD@-@/@20SD@-@): 90mm *1 × 79mm *2 × 86 mm
CPU Unit with 30 I/O points (CP1E-@30S(1)D@-@): 90mm *1 × 79mm *2 × 130 mm
CPU
Unit with 40 I/O points (CP1E-@40
S(1)D@-@): 90mm *1 × 79mm *2 × 150 mm
CPU Unit with 60 I/O points (CP1E-@60S(1)D@-@): 90mm *1 × 79mm *2 × 195 mm
Weight
CPU Unit with 10 I/O points (CP1E-E10D@-@): 300g max.
CPU Unit with 14 I/O points (CP1E-@14(S)D@-@): 360g max.
CPU Unit with 20 I/O points (CP1E-@20(S)D@-@): 370g max.
CPU Unit with 30 I/O points (CP1E-@30(S@)D@-@): 600g max.
CPU Unit with 40 I/O points (CP1E-@40(S@)D@-@): 660g max.
CPU Unit with 60 I/O points (CP1E-@60(S@)D@-@): 850g max.
CPU Unit with 20 I/O points and built-in analog (CP1E-NA20D@-@): 680g max.
Electrical
specifications
Supply voltage 100 to 240 VAC 50/60 Hz 24 VDC
Operating voltage range
85 to 264 VAC 20.4 to 26.4 VDC
Power consumption
15 VA/100 VAC max.
25 VA/240 VAC max.
(CP1E-E10D@-A/@14(S)D@-A/@20(S)D@-A)
9 W max. (CP1E-E10D@-D)
13 W max. (CP1E-N14D@-D/N20D@-D)
50 VA/100 VAC max.
70 VA/240 VAC max.
(CP1E-NA20D
@
-A/
@
30(S
@
)D
@
-A/
@
40(S
@
)D
@
-A/
N60(S@)D@-A)
20 W max.
(CP1E-NA20D
@
-D/N30
(S@)
D
@
-D/N40
(S@)
D
@
-D/
N60
(S@)
D
@
-D)
*
4
Inrush current
120 VAC, 20 A for 8 ms max. for cold start at room
temperature
240 VAC, 40 A for 8 ms max. for cold start at room
temperature
24 VDC, 30 A for 20 ms max. for cold start at room
temperature
External power supply
*3
Not provided.
(CP1E-E10D@-A/@14(S)D@-A/@20(S)D@-A)
24 VDC, 300 mA
(CP1E-NA20D
@
-A/
@
30(S
@
)D
@
-A/
@
40(S
@
)D
@
-A/
N60(S@)D@-A)
Not provided
Insulation resistance
20 MΩ min. (at 500 VDC) between the external AC
terminals and GR terminals
Except between DC primary current and DC
secondary current
Dielectric strength
2,300 VAC 50/60Hz for 1 min between AC external
and GR terminals Leakage current: 5 mA max.
Except between DC primary current and DC
secondary current
Power OFF detection
time
10 ms min. 2 ms min.
Application
environment
Ambient operating
temperature
0 to 55 °C
Ambient humidity 10% to 90%
Atmosphere No corrosive gas.
Ambient storage
temperature
-20 to 75 °C (excluding battery)
Altitude 2,000 m max.
Pollution degree 2 or less: Conforms to JIS B3502 and IEC 61131-2.
Noise resistance 2 kV on power supply line (Conforms to IEC61000-4-4.)
Overvoltage category Category II: Conforms to JIS B3502 and IEC 61131-2.
EMC Immunity Level Zone B
Vibration resistance
Conforms to JIS 60068-2-6.
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz
Acceleration of 9.8 m/s
2
for 100 min in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total)
Shock resistance
Conforms to JIS 60068-2-27.
147 m/s
2
, 3 times in X, Y, and Z directions
Terminal block Fixed (not removable)
Terminal screw size M3
Applicable standards Conforms to EC Directive
Grounding method Ground to 100 Ω or less.