Datasheet

CP1E-E@@(S)D@-@ CP1E-N@@(S@)D@-@/NA20D@-@
15
Item
CP1E-E@@SD@-@
CP1E-E@@D@-@
CP1E-N@@S@D@-@
CP1E-N@@D@-@
CP1E-NA@@D@-@
Communications
B-type Peripheral USB Port Conforming to USB 2.0 B type connector
Transmission
distance
5 m max.
Built-in RS-232C port
No built-in RS-232C port
Interface: Conforms to EIA RS-232C.
Communications
method
Half duplex
synchronization
Start-stop
Baud rate 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, or 115.2 kbps
Transmission
distance
15 m max.
Supported
protocol
Host Link
1:N NT Link
No-protocol mode
Serial PLC Links (master, slave)
Modbus-RTU Easy Master
Built-in RS-485 port
No built-in RS-485 port
N30/40/60S1-type only
Interface: Conforms to EIA RS-485. 2-wire sensors
No isolation
Communications
method
Half duplex
synchronization
Start-stop
Baud rate 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, or 115.2 kbps
Transmission
distance
50 m max.
Supported
protocol
Host Link
1:N NT Link
No-protocol mode
Serial PLC Links (master, slave)
Modbus-RTU Easy Master
Serial Option port
Option Board cannot be mounted.
N30/40/60 and NA20-type only
1 port
Mountable
Option Boards
One RS-232C port: CP1W-CIF01
One RS-422A/485 port (not isolated): CP1W-CIF11
One RS-422A/485 port (isolated): CP1W-CIF12
One Ethernet port: CP1W-CIF41
Communications
method
Depends on Option Board.
synchronization
Depends on Option Board.
Baud rate 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, or 115.2 kbps
Compatible
protocols
Host Link
1:N NT Link
No-protocol mode
Serial PLC Links (master, slave)
Modbus-RTU Easy Master
Number of tasks
17
One cyclic execution task
One scheduled interrupt task (always interrupt task 1)
Six input interrupt tasks (interrupt tasks 2 to 7)
Sixteen high-speed counter interrupt tasks (interrupt tasks 1 to 16)
Maximum subroutine number 128
Maximum jump number 128
Scheduled interrupt tasks 1 interrupt task
Clock
Clock function not included.
The time of error occurrence displays 01-01-01
01:01:01 Sunday
Included.
Accuracy (monthly deviation):
-4.5 min to -0.5 min at ambient temperature of 55
o
C,
-2.0 min to +2.0 min at ambient temperature of 25
o
C,
-2.5 min to +1.5 min at ambient temperature of 0
o
C
Memory
backup
Built-in EEPROM
Ladder programs and parameters are automatically saved to built-in EEPROM
A section of the Data Memory Area can be saved to the built-in EEPROM.
Battery backup With
CP1W-BAT01 Battery
(Sold separately)
Battery cannot be mounted.
CP1W-BAT01 can be used.
Maximum battery service life: 5 years
Backup Time
Guaranteed value (ambient temperature: 55
o
C):
13,000 hours (approx. 1.5 years)
Effective value (ambient temperature: 25
o
C):
43,000 hours (approx. 5 years)
CIO Area
Input Bits 1,600 bits (100 words): CIO 0.00 to CIO 99.15 (CIO 00 to CIO 99)
Output Bits 1,600 bits (100 words): CIO 100.00 to CIO 199.15 (CIO 100 to CIO 199)
Serial PLC Link Words 1,440 bits (90 words): CIO 200.00 to CIO 289.15 (words CIO 200 to CIO 289)
Work Area (W) 1,600 bits (100 words): W0.00 to W99.15 (W0 to W99)
Holding Area (H)
800 bits (50 words): H0.00 to H49.15 (H0 to H49)
Bits in this area maintain their ON/OFF status when operating mode is changed.
Auxiliary Area (A)
Read-only: 7,168 bits (448 words) A0 to A447
Read/write: 4,896 bits (306 words) in words A448 to A753
Temporary Relay Area (TR) (TR Area) 16 bits: TR0 to TR15
Timer Area (T) 256 timer numbers (T0 to T255 (separate from counters))
Counter Area (C) 256 counter numbers (C0 to C255 (separate from timers))