Datasheet
CP1E-E@@(S)D@-@ CP1E-N@@(S@)D@-@/NA20D@-@
31
Specifications of Expansion I/O Units
●Input Specifications (CP1W-40EDR/40EDT/40EDT1/20EDR1/20EDT/20EDT1/8ED)
Note: Do not apply voltage in excess of the rated voltage to the input terminal.
* The response time is the hardware delay value. The delay set in the PLC Setup (0 to 32 ms, default: 8 ms) must be added to this value. For the
CP1W-40EDR/EDT/EDT1, a fixed value of 16 ms must be added.
●Output Specifications
Relay Outputs (CP1W-40EDR/32ER/20EDR1/16ER/8ER)
Note: 1. Estimating the Service Life of Relays
The service life of output contacts is as shown in the following diagram.
Item Specification
Input voltage 24 VDC +10%/-15%
Input impedance 4.7 kΩ
Input current 5 mA typical
ON voltage 14.4 VDC min.
OFF voltage 5.0 VDC max.
ON delay 1 ms max. *
OFF delay 1 ms max. *
Circuit configuration
Item Specification
Max. switching capacity
2 A, 250 VAC (cosφ = 1),
2 A, 24 VDC (4 A/common)
Min. switching capacity 5 VDC, 10 mA
Service life of
relay
(See note.)
Electrical
Resistive load 150,000 operations (24 VDC)
Inductive load 100,000 operations (240 VAC, cosφ = 0.4)
Mechanical 20,000,000 operations
ON delay 15 ms max.
OFF delay 15 ms max.
Circuit configuration
v
IN
IN
COM
4.7 kΩ
750 Ω
Input LED
Internal
circuits
COM
OUT
OUT
Output LED
Internal
circuits
Maximum
250 VAC: 2 A
24 VDC: 2 A
300
200
100
50
30
20
5
3
2
10
0.1
0.2 0.3 0.5 0.7 1 235
Life (× 10
4
)
Contact current (A)
120 VAC resistive load
24 VDC τ = 7 ms
120 VAC cosφ = 0.4
240 VAC cosφ = 0.4
24 VDC/240 VAC resistive load
Switching rate: 1,800 operations/hou
r